Thomelec - Ke-Fkr4 ENG

The document describes a phase failure and phase sequence device. It protects 3 phase systems by monitoring for phase failures, incorrect phase sequence, and voltage asymmetry. It has adjustable thresholds for asymmetry, over/under voltage, and delay time. It de-energizes its contact for detected faults.

Uploaded by

Gabriel Delfino
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views

Thomelec - Ke-Fkr4 ENG

The document describes a phase failure and phase sequence device. It protects 3 phase systems by monitoring for phase failures, incorrect phase sequence, and voltage asymmetry. It has adjustable thresholds for asymmetry, over/under voltage, and delay time. It de-energizes its contact for detected faults.

Uploaded by

Gabriel Delfino
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

®

ke – FKR4 General:
In three phase systems, when phase sequence is correct and there is no asymmetry between phases, normal
PHASE FAILURE and LED is turned on and relay contact is energised. Protection functions of ke-FKR4 are given below.
PHASE SEQUENCE DEVICE
► Asymmetry % Adjustment ► Phase Failure:
► Phase Sequence In case of absence of at least one phase, relay immediately de-energises its contact and E2 LED is turned on.
► Over&Under Voltage L1
% Adjustment L2
► Phase Failure
► Delay Time Adjustment L3
N

1-2 t1 = 2 sec.
t2 = 0,5 sec.
t1 t2 < t1 t1 < t2 t2 t1

► Phase Sequence:
In case of wrong phase order, both of E1 and E2 LEDs are turned on at the same time and relay does not
energise its contact. If phase order is corrected, both of E1 and E2 LEDs are turned off and relay energises its
contact. L1,L2,L3 L1,L3,L2 L1,L2,L3 L2,L3
%
Over L1,L2,L3
Asym. Under
Failure
Phase 1-2
Failure
% ► Voltage Asymmetry (asym. %) (5-17.5 %) :
Asym.
Phase to phase asymmetry is adjusted using the adjustment knob in the range of (5-17.5%). If asymmetry
Normal exceeds adjusted value, LED E1 starts to flash and at the end of delay time (1-10s) E1 LED is turned on
(t) continuously and relay contact is de-energised.
Delay To return normal state, voltage asymmetry value must be under 20% of adjusted value (hysteresis). If phase –
Time
phase asymmetry value returns to normal region in a shorter time then adjusted delay time, relay does not de-
energise its contact and LED E1 stops flashing.
Example: Let's say that asymmetry value is set to 15% for a 3 x 380VAC. In this case, relay contact is de-
energised at (380-(380x0.15))=323 V.
Re-energising the contact is performed at 323+(380x15%x20%)= 334V. (20% is the hysteresis).

(Vmax - Vmin)
Asym % = x 100
+ % Asm.
380
Hys
Vnom
Hys = 380 x (Asym %) x (20 %) - % Asm.
Application Areas: Hys
-Protection of electrical motors Level
-Protection of 3 phase systems 1-2
t t <t t

► Voltage Adjustment Range: ± (0,5 - 0,30)


Under Voltage Umin=(0.70-0.95)xUn and Over Voltage Umax=(1.05-1.30)xUn.
As long as the voltage values do not exceed adjusted values, normal LED is kept on and relay contact is
TECHNICAL DATA:
energized. Hysteresis is 15%. LED E2 indicates that the adjusted voltage range is exceeded. There is only one
Rated Voltage : 3 Phase and 1 Neutral adjustment knob for both over and under voltage values.
230 VAC L1,L2,L3
Operating Range : (0.8 – 1.2)xUn Umax Over Voltage
(Un nominal voltage)
Un Normal Normal
Frequency : 50/60 Hz Umin
Asymmetry Adj. : Phase to phase
5 - 17,5% Under Voltage
Over-Under Adj. : Phase to Neutral
5 – 30% 1-2
Delay Time Adj. : 1 – 10 sec. t t
Output Contacts : Normally Open
(1-2) Contact Simple Connection :
Contact Current : Max. 5 A / 240 VAC L1
Power Consumption : < 8 VA L2
Device Protection L3
Class : IP20 N
Connector Protection
Class : IP00
Ambient Temperature : -5°C....+50°C
Connection Type : To connection rail
in electrical panel
Dimensions : 28x82x80 mm

L1,L2,L3 : 3 x 380 V ac
16 mm

L1,N : 220 V ac
2
mm

L1 L2 L3
80

Load
Max. 5A
240 Vac

N
28 mm 35 mm 3 1
82 mm