0% found this document useful (0 votes)
292 views

3.-Modulo IDNET S4100-0100 - SIMPLEX

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
292 views

3.-Modulo IDNET S4100-0100 - SIMPLEX

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

4100ES Fire Control Panels

UL, ULC, CSFM Listed; FM, NYC Addressable Fire Detection and Control Basic Panel Modules and Accessories
Fire Dept Approved*

Features current draw and voltage drop margin under both primary power and
secondary battery standby
• Efficiencies include lower strobe currents, wiring distances up to 2 to
3 times farther than with conventional notification, support for more
appliances per IDNAC SLC, and the ability to use smaller gauge wiring –
all providing installation and maintenance savings with high assurance
that appliances that operate during normal system testing will also
operate during worst case alarm conditions
• IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert
addressable notification appliances, and remote 4009 IDNAC
Repeaters to extend power and wiring distance even farther

Optional modules and connections


• Fire Alarm Network Interfaces, city connections, and up to five (5)
RS-232 ports for printers and terminals
• Building Network Interface Card (BNIC) for Ethernet connectivity
options (see data sheet S4100-0061 )
• Side mounted DACT assembly requiring minimal panel space; DACT is
compatible with IP Communicators
• Emergency communications systems (ECS) equipment; 8 channel
digital audio or 2 channel analog audio
• Additional IDNet 2 communications SLCs, IDNet 2+2 Modules with
quad short circuit isolating output loops; additional power supplies,
alarm relays, and auxiliary relays
• LED/switch modules and panel mount printers; VESDA Air Aspiration
Systems interface, ASHRAE BACnet Interface, TCP/IP Bridges
• Battery brackets for seismic area protection
• 4100ES compatible legacy interface modules, including control of
Figure 1: 4100ES cabinets are available with conventional (non-addressable) NACS
one, two or three bays (2 bay cabinet shown)
• 8-point zone/relay module, each point is selectable as an IDC input or
Compatible with Simplex ES Net or 4120 Fire Alarm Networks relay output. Class A IDCs require 2 points (one out and one return).
Relays rated for 2 A @ 30 VDC (resistive). Configurable as normally
Master Controller (top) bay standard equipment
open or closed.
• 32-Bit Master Controller with color-coded operator interface and
raised switches for high confidence feedback 4100ES Listings reference:
• Dual configuration program CPU, convenient service port access, and • UL 864, Fire Detection and Control (UOJZ), and Smoke Control Service
capacity for up to 2500 addressable points (UUKL), Releasing Device Service (SYZV)
• CPU assembly includes 2 GB dedicated compact flash memory for on- • UL 1076. Proprietary Alarm Units - Burglar (APOU)
site system programming and information storage • UL 2017, Process Management Equipment (QVAX), Emergency Alarm
• An Enhanced Power Supply (EPS) and battery charger (9 A output) System Control Units (FSZI)
with on-board: IDNAC SLCs (signaling line circuit) for addressable • UL 1730, Smoke Detector Monitor (UULH)
appliance control, an IDNet 2 Module for addressable device control; • UL 2572, Mass Notification Systems (PGWM)
and programmable function auxiliary output
• CAN/ULC S527, Control Units for Fire Alarm Systems (UOJZ7), Releasing
• Also available with InfoAlarm Command Center expanded content user Device Service (SYZV7)
interface (see data sheet S4100-0045 )
• ULC/ORD-C1076 Proprietary Burglar Alarm Units and Systems (APOU7)
Standard addressable device interfaces include: • ULC/ORD-C100 Smoke Control System Equipment (UUKL7)
• 250 point addressable device IDNet 2 SLC that supports TrueAlarm
analog sensors and IDNet communications monitoring and control Software Feature Summary
devices with an electrically isolated output channel allowing use with
either shielded or unshielded, twisted or untwisted single pair wiring; CPU provides dual configuration programs
and providing dual short circuit isolating output loops • Two programs allow for optimal system protection and commissioning
• MINIPLEX Transponder and remote LCD and LED annunciator support efficiency with one active program and one reserve; downtime is
via RUI+ (isolated or un-isolated) communications port (see Standard reduced because the system stays running during download
CPU Bay Module Details) PC based programmer features
Standard power supplies (EPS) provide enhanced power delivery • Convenient front panel accessed Ethernet port for quick and easy
IDNAC SLCs to addressable notification appliances download of site-specific programming
• With IDNAC SLCs, a constant 29 VDC source voltage is maintained • Modifications can be uploaded as well as downloaded for greater
during alarm, even during battery operation, allowing strobes to service flexibility; AND, firmware enhancements are made via software
operate at higher voltage with lower current and ensuring a consistent downloads to the on-board flash memory

This product has been listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0251 for allowable values
and/or conditions concerning material presented in this document. NYC Fire Dept COA #6151. At the time of publication only UL and ULC listings are applicable to ES Net network products. Additional
listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

• "Install Mode" allows grouping of multiple troubles for uninstalled


modules and devices into a single trouble condition (typical with future
phased expansion); with future equipment and devices grouped into
a single trouble, operators can more clearly identify events from the
commissioned and occupied areas
• Module level ground fault searching assists installation and service by
locating and isolating modules with grounded wiring
• "Recurring Trouble Filtering" allows the panel to recognize, process,
and log recurring intermittent troubles (such as external wiring ground
faults), but only sends a single outbound system trouble to avoid
nuisance communications
• WALKTEST silent or audible system test performs an automatic self-
resetting test cycle
• Support for TrueAlarm individual analog sensing and IDNAC
addressable notification with front panel information and selection
access

Introduction
4100ES fire panels provide extensive installation, operator, and service
features with point and module capacities suitable for a wide range of
system applications. An on-board Ethernet port provides fast external
system communications to expedite installation and service activity.
Dedicated compact flash memory archiving provides secure on-site
system information storage of electronic job configuration files to meet
NFPA 72 (National Fire Alarm and Signaling Code) requirements.

Modular design
A wide variety of functional modules are available to meet specific
system requirements. Selections allow panels to be configured for either
Figure 2: 4100ES Module Placement
stand-alone or networked fire control operation.
Reference in 3-Bay Cabinet

ES panel compatibility with ES Net Mechanical Description


Simplex ES Network (ES Net) is a next generation IP based fire network • Boxes can be close-nippled; each box provides convenient stud
that uses industry standard network technology and infrastructure and markers for drywall thickness and nail-hole knockouts for quicker
allows for simplified network upgrades, easy terminal connectivity and IP mounting
file transfer between nodes; and advanced network diagnostics.
• Smooth box surfaces are provided for locally cutting conduit entrance
ES fire alarm control panels can be upgraded to operate on an ES holes exactly where required
network by adding an ES Net NIC to the panel. • Cabinet assembly design has been seismic tested and is certified to
To upgrade an existing 4120 network to ES Net, all of the 4120 NIC cards IBC and CBC standards as well as to ASCE 7 categories A through F,
on the network loop must be replaced with ES Net NICs. requires 4100-7912 option for additional legacy card stabilizer brackets
and battery brackets as detailed on data sheet S2081-0019
Note: ES NICs and 4120 NICs cannot be mixed on the same network
• The latching front panel assembly easily lifts off for internal access
loop.
• Modules are power-limited (except as noted, such as relay modules)
For more detailed information on ES Net, consult datasheet S4100-0076 , • The NEMA 1/IP30 box is ordered separately and available for early
and talk to your local Simplex product supplier. installation
• Doors are available with tempered glass inserts or solid; boxes and
Module Bay Description doors are available in platinum or red
The Master Controller Bay (top) includes a standard multi-featured • Boxes and door/retainer assemblies are ordered separately per system
enhanced power supply (EPS) with IDNet 2 Module, the master requirements; refer to data sheet S4100-0037
controller board, two vertical expansion blocks, and operator interface
equipment.
The Expansion Bays include a Power Distribution Interface (PDI)
for connection of single or multiple block modules, and/or slot style
(motherboard/daughter card) modules.
The Battery Compartment (bottom) accepts two batteries, up to 50
Ah, to be mounted within the cabinet without interfering with module
space.

Page 2 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

Operator Interface Detail Reference Table 1: TrueAlarm Addressable Sensor Reference


The following illustration identifies the primary functions of the operator
interface.

Figure 5: TrueAlarm Photo/


Figure 4: TrueAlarm
Heat Sensor in CO Base
Photo Sensor with Base

Programmable sensitivity
Programmable sensitivity of each sensor can be selected at the control
panel for different levels of smoke obscuration (shown directly in
percent) or for specific heat detection levels. To evaluate whether the
sensitivity should be revised, the peak value is stored in memory and can
be easily read (or downloaded as a report) and compared to the alarm
threshold directly in percent.
Figure 3: Operator interface
CO sensor bases
CO sensor bases combine an electrolytic CO sensing module with a
IDNet Addressable Device and IDNAC Addressable TrueAlarm analog sensor to provide a single multiple sensing assembly
Notification Appliance Control using one system address. The CO sensor can be enabled/disabled,
Overview.The 4100ES EPS power supply with IDNet 2 Module provides used in LED/Switch modes and custom control, and can be made public
addressable initiating device and IDNAC addressable notification for communication across a fire alarm Network. (refer to data sheet
appliance Signaling Line Circuits (SLCs) that supervise wiring connections S4098-0052 for details)
and the individual device/appliance communications status on their
SLC. With these 2-wire SLCs, initiation, monitoring, and control devices TrueAlarm heat sensors
such as manual fire alarm stations, TrueAlarm sensors, control relays, TrueAlarm heat sensors can be selected for fixed temperature detection,
and sprinkler waterflow switches; and notification appliances such with or without rate-of-rise detection. Utility temperature sensing is also
as strobes and horns can communicate their identity and status and available, typically to provide freeze warnings or alert to HVAC system
receive fire alarm system control. Additional interface modules include problems. Readings can selected as either Fahrenheit or Celsius.
circuit isolators, conventional IDC zone adapters, and interface to other
TrueSense Early Fire Detection
system circuits such as fans, dampers, and elevator controls.
Multi-sensor 4098-9754 provides photoelectric and heat sensor data
using a single 4100ES IDNet address. The panel evaluates smoke
IDNet Addressable Device Operation activity, heat activity, and their combination, to provide TrueSense
Each addressable device on an IDNet communication channel early detection. For more details on this operation, refer to data sheet
is continuously interrogated for status condition such as: normal, S4098-0024 .
off-normal, alarm, supervisory, or trouble. Both Class B and Class A
operation is available. Sophisticated poll and response communication
techniques ensure supervision integrity and allow for "T-tapping" of
Diagnostics and Default Device Type
the circuits for Class B operation. Devices with LEDs pulse the LED Sensor Status
to indicate receipt of a communications poll and can be turned on TrueAlarm operation allows the control panel to automatically indicate
steady from the panel. With addressable devices, the location and when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72
status of the connected device is monitored and logged, and displayed requirement for a test of the sensitivity range of the sensors is fulfilled
on the operator interface LCD and on remote system annunciators by the ability of TrueAlarm operation to maintain the sensitivity level of
with each device having its own 40 character custom label for precise each sensor. CO Sensors track their 10 year active life status providing
identification. indicators to assist with service planning. Indicators occur at: 1 year, 6
months, and end of life.
TrueAlarm Addressable Sensor Operation
Modular TrueAlarm sensors
Addressable initiating device communications include operation of
TrueAlarm smoke and temperature sensors. Smoke sensors transmit Modular TrueAlarm sensors use the same base and different sensor
an output value based on their smoke chamber condition and the CPU types (smoke or heat sensor) and can be easily interchanged to
maintains a current value, peak value, and an average value for each meet specific location requirements. This allows intentional sensor
sensor. Status is determined by comparing the current sensor value to substitution during building construction when conditions are
its average value. Tracking this average value as a continuously shifting temporarily dusty. Instead of covering smoke sensors (causing them to
reference point filters out environmental factors that cause shifts in be disabled), heat sensors may be installed without reprogramming the
sensitivity. control panel. The control panel will indicate an incorrect sensor type,
but the heat sensor will operate at a default sensitivity to provide heat
detection for building protection at that location.

IDNet Addressable Device Wiring Reference


IDNet Addressable Channel Capacity
The CPU bay standard power supply (EPS) provides an IDNet 2
Module providing a signaling line circuit (SLC) that supports up to 250
addressable monitor and control points intermixed on the same pair

Page 3 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

of wires. IDNet 2 and IDNet 2+2 Module SLCs are isolated from other Virtual NACs Provide Control Convenience
system reference voltages to reduce common mode noise interaction For control convenience, IDNAC notification appliances can be grouped
with adjacent system wiring. Additional 250 address IDNet 2 or IDNet into Virtual NACS (VNACs) for group control, grouping that can be made
2+2 Modules are available. across SLCs, not defined by their wiring connection.
Table 2: IDNet 2 and IDNet 2+2 SLC Wiring Specifications Panel Control Convenience
Specification Rating Applicable operation settings for each appliance can be programmed
4000 ft (1219 m); 50 without having to replace appliances or remove them from the wall or
Maximum Distance 1 - 125
ohms ceiling. An appliance's VNAC notification zone can be easily changed
from Control Panel per
2500 feet (762 m); 35 through programming without having to add additional circuits, conduit,
Device Load 126 - 250
ohms and wiring. Audible and visible appliances for non-Fire Emergency
Up to 12,500 ft (3.8 Communications notification can be programmed to operate separately
Total Wire Length Allowed With “T” Taps for on the same pair of wires as the fire alarm notification appliances. The
km);
Class B Wiring result is lower installation, retrofit, and overall life-cycle cost of ownership
0.60 µF
compared with traditional conventional notification systems.
Maximum Capacitance Between IDNet 2
1 µF
Channels Installation, Retrofit, and Life-Cycle Cost Benefits
0.8 mA supv., 1 mA With each addressable appliance capable of being controlled separately
alarm; on the same two-wire IDNAC SLC, installation time and expense for
Loading per device
2 mA per activated both retrofit and new construction can be significantly reduced. When
device LED Class B wiring is used, wiring can be "T-tapped" allowing more savings
Shielded or unshielded, in distance, wire, conduit (size and utilization), and overall installation
Wire Type and Connections twisted or untwisted efficiency.
wire*
Location Information, Diagnostics and Troubleshooting
Terminals for 18 to 12
2 Each addressable notification appliance has its own 40 character
Connections AWG (0.82 mm to 3.31 custom label to identify the location of the appliance and to aid in
2
mm ) troubleshooting fault conditions. In conventional notification systems,
IDNet 2 and IDNet 2+2 Module Compatibility: IDNet conventional appliances are not capable of communicating with the
communicating devices and TrueAlarm sensors including QuickConnect control panel. Fault reporting on a conventional system is limited to
and QuickConnect2 sensors the circuit wiring and the entire area (zone) covered by appliances on
Note: * Some applications may require shielded wiring. Review your the notification appliance circuit (NAC) making it much more difficult
system with your local Simplex product supplier. and costly to locate and correct the source of a problem. Using the
TrueAlert magnet test allows each appliance to individually identify
IDNAC SLC Control of TrueAlert and TrueAlert ES its candela setting and address and to briefly operate if desired, and
using the TrueAlert ES Appliance Self-Test feature provides detailed
Addressable Notification
performance verification per appliance.
Addressable notification appliance communications include
operation of TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible
only (A/O, horn), Audible/Visible (A/V, horn/strobe), and strobes of TrueAlert ES Appliance Self-Test Operation
Speaker/Visible (S/V) notification appliances. (S/V appliances require On-Board Test Sensors
separate speaker wiring.) IDNAC SLC addressable communications
TrueAlert ES appliances are equipped with on-board sensors to detect
allow each horn and strobe to be individually controlled using a single
strobe and/or horn output allowing efficient and unobtrusive Self-
two-wire circuit, confirms the wiring connections to the individual
Testing. When Automatic Self-Test is initiated from the control panel,
notification appliance's electronic circuit, and confirms communications
each appliance within the selected VNAC group will briefly operate and
between each appliance and the fire alarm control panel. Addressable
then report its Self-Test status to the control panel, all within several
communications increases supervision integrity versus conventional
seconds. Silent Self-Test can be selected to test only visible appliance
notification systems by providing supervision beyond the circuit wiring to
if desired. The control panel is in a trouble condition during testing
each individual appliance and by constantly verifying the ability of each
and in the event of an alarm, Self-Test is automatically terminated.
appliance to communicate with the control panel.
Additionally, Automatic Self-Test can be scheduled to occur at a
Individual Appliance Status and Settings convenient time on a regular basis (Requires version 2.03.01 or higher
The fire alarm control panel monitors and records each addressable software).
notification appliance status, type of appliance, and its configured Automatic Self-Test
appliance settings. A fault in any individual appliance automatically
Automatic Self-Test results are communicated to the control panel with
reports a trouble condition to the control panel.
a time and date stamp and are stored in memory. Results are viewable
at the front panel display and printed reports can be generated from the
panel service port.

Individual Self-Test
Individual Self-Test is selected from the control panel when individual
appliances need to be observed to operate. Each appliance in the
selected VNAC group will turn on its LED until individually activated by
applying a magnet. After performing the individual test, the appliance
LED turns off to indicate completion. Results are recorded the same as
during the automatic test.

Figure 6: TrueAlert ES Addressable Appliance Reference

Page 4 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

IDNAC SLC Hardware Reference 4100-6032, without disconnect switches) can be selected for
conventional dual circuit city connections
EPS Power Supplies
• Alarm Relay Module (4100-6033) provides three Form C relays that are
EPS Power Supplies provide three, 3 A IDNAC SLCs for control and used for Alarm, Trouble, and Supervisory, rated 2 A resistive @ 32 VDC
power to TrueAlert ES and TrueAlert addressable notification appliances.
Both power supplies incorporate an efficient switching design that EPS (Enhanced Power Supply) with IDNet 2 Module Details
provides a regulated output of 29 VDC, even during battery operation. • Rating is 9 A output with "Special Application" appliances
With 29 VDC minimum output at the panel, addressable notification • Outputs are power-limited, except for the battery charger
SLCs can support wiring distances 2 to 3 times farther than available
• Provides system power, battery charging, auxiliary power, earth
with conventional notification, or support more appliances per SLC, or
detection, on-board electrically isolated IDNet 2 Module with 250
work with smaller gauge wiring, or combinations of these benefits, all
point SLC, three on-board 3 A IDNAC SLCs, and provisions for either
resulting in installation and maintenance savings with high assurance
an optional City Connect Module or an optional Alarm/Supv/Tbl Relay
that appliances that operate during normal system testing will operate
Module
during worst case alarm conditions.
• IDNet 2 Module SLC Output provides Class B or Class A
communications for up to 250 addressable devices with dual short
IDNAC SLC Appliance Wiring Reference circuit isolating loop outputs
IDNAC SLC Capacity
Note: The "IDNet 2 Module" replaced the "IDNet 1+ Module" and the
Up to 127 addresses and up to 139 unit loads (appliances are typically
term "EPS with IDNet 2 Module" replaces the term "EPS+"
one unit load, devices such as Isolators may require more than one load,
• Note: The “IDNet 2 Module” replaced the “IDNet 1+ Module” and the
refer to individual device data sheet for specific information)
term “EPS with IDNet 2 Module” replaces the term “EPS+”. DCAI (Dual
Table 3: IDNAC SLC Appliance Wiring Reference Class A IDNAC Isolator) Module creates two Class A outputs from
Specification Rating one IDNAC SLC Class B Input; up to two can be connected to one
IDNAC SLC, with up to 6 total per EPS; total Class A output loop current
Recommended wire type UTP, unshielded twisted pair
is limited to the 3 A rating of the IDNAC SLC
Maximum wire length allowed
with "T-Taps" for Class B wiring, 10,000 ft (3048 m) • Battery Charger is dual rate, temperature compensated, and
per SLC charges up to 50 Ah sealed lead-acid batteries mounted in the battery
Maximum wire length per SLC compartment (33 Ah for single bay cabinets). UL listed for charging up
4000 ft (1219 m) to 110 Ah batteries mounted in an external cabinet (see data sheet
to any appliance
S2081-0012 for details)
Appliance Supervisory Current 1 unit load = 0.8 mA per appliance
2 • Battery and Charger Monitoring includes battery charger status
Terminals for 18 to 12 AWG (0.82 mm and low or depleted battery conditions; status information provided
Wiring connections 2
to 3.31 mm ) to the master controller includes analog values for: battery voltage,
Installation Instructions (see for charger voltage and current, actual system voltage and current, and
579-1015
more information) individual IDNAC SLC currents
• Low Battery Cutout is selectable for each EPS power supply,
Standard CPU Bay Module Details Canadian models are shipped selected, other models are shipped
unselected
Master Controller and Motherboard
• Mounts in Slot 2 of a two slot motherboard and provides one Class B 2 A Programmable Output
or Class A, RUI+ communications channel configurable for isolated or • Select for conventional non-synchronous NAC operation to provide
un-isolated operation supervised reverse polarity for sounder base power, Suppression
• Slot 1 of the motherboard is primarily for an optional network Release Peripheral (SRP) power, or other coded NAC operation
interface card or secondarily for the 4100-6038 dual RS-232 board requirements
communications • Select for Auxiliary (AUX) operation for sounder base power, 4-wire
• RUI+ and RUI communications controls up to 31 remote devices per detector power, or door holder; supervised AUX operation does not
master controller at up to 2500 ft (762 m) for single run, or 10,000 require an end-of-line relay to provide power-limited operation
ft (3048 m) total if wiring is Class B and T tapped; if more distance is 8-Point Zone/Relay Module Details
required, up to four total RUI channels are supported; add up to three
• Select as IDC or Relay; configure up to 8, Class B IDCs, or up to
4100-1291 RUI Expansion Modules (4100-1291 provides unisolated
4, Class A IDCs; or up to 8, Relay outputs rated 2 A resistive @ 30
RUI communications)
VDC (N.O. or N.C.); or combinations of IDCs and Relays; each zone is
• Compatible RUI+ and RUI remote equipment includes: MINIPLEX separately configurable as an IDC or Relay output
transponders, 4603-9101 LCD Annunciators, 4602-9101 Status
• IDC Support: each IDC supports up to 30, two-wire devices. Zone relay
Command Units (SCU), 4602-9102 Remote Command Units (RCU),
modules may be powered directly from the control unit power supply
4602 Series LED Annunciator Panels, 4100 Series 24 I/O and LED/
or through the optional 25 VDC regulator module where required for
Switch modules, (4602 series annunciators require un-isolated
2- wire detector compatibility (refer to 2-Wire Detector Compatibility
communications).
document 579-832 for additional details).
• Up to 4 RUI channels (combination of built-in RUI+ and optional RUI
• IDC EOL resistor values are selectable as: 3.3 kΩ, 2 kΩ, 2.2 kΩ, 3.4
modules) are supported
kΩ, 3.9 kΩ, 4.7 kΩ, 5.1 kΩ, 5.6 kΩ, 6.34/6.8 kΩ, and 3.6 kΩ + 1.1 kΩ; see
• Open slot space on the left of the CPU motherboard is available for instructions for more details
either another dual slot motherboard, or for one or two block modules
(refer to Figure 2)

EPS Mounted Optional Modules (select one)


• City Connect Module (4100-6031, with disconnect switches, or

Page 5 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

Master Controller Selection Information


Table 4: Master Controller and Expansion Bay Selection
Model Model Type and Listing Description Current
Without IDNet devices:
Supervisory = 425 mA
4100-9311 120 VAC, 50/60 Hz Input UL Alarm = 735 mA
4100ES Master Controller Assembly with LCD Note: Master Controller current does not
display, operator interface and RUI+ isolated subtract from 9 A output rating
or un-insolated output communications Without IDNet devices:
interface; 9 A EPS (Enhanced Power Supply)
Supervisory = 425 mA
120 VAC, 50/60 with battery charger, electrically isolated 250
4100-9312 English ULC Alarm = 735 mA
Hz Canadian point IDNet 2 Module, three Class B IDNAC
SLCs, one 2 A output configurable for Auxiliary Note: Master Controller current does not
Power or Simple NAC operation and expansion subtract from 9 A output rating
slot for City Circuit or Alarm/Supv/Tbl Relay Without IDNet devices:
option. Supervisory = 425 mA
120 VAC, 50/60
4100-9313 French ULC Alarm = 735 mA
Hz Canadian
Note: Master Controller current does not
subtract from 9 A output rating
4100ES Master Controller Assembly with LCD
display, operator interface and RUI+ isolated
or un-insolated output communications
interface; 9 A EPS (Enhanced Power Supply)
with battery charger, electrically isolated 250 Without IDNet devices:
4100-9511 220-240 VAC, 50/60 Hz Input UL
point IDNet 2 Module, three Class B IDNAC Supervisory = 425 mA
SLCs, one 2 A output configurable for Auxiliary Alarm = 735 mA
Power or Simple NAC operation and expansion Note: Master Controller current does not
slot for City Circuit or Alarm/Supv/Tbl Relay subtract from 9 A output rating
option
4100ES Master Controller Assembly ; same as
4100-9331 120 VAC, 50/60 Hz input UL above models except without LCD Display and
Operator Interface
Without IDNet devices:
4100ES Master Controller Assembly ; same as Supervisory = 425 mA
120 VAC, 50/60 Hz input,
4100-9332 ULC above models except without LCD Display and Alarm = 735 mA
Canadian, English
Operator Interface Note: Master Controller current does not
subtract from 9 A output rating
4100-2300 Expansion Bay Assembly; order for each required expansion bay
4100-2303 Slot Module Stabilizer Bracket, used when expansion bays have style modules
Table 5: Communication Modules
Model Description Size Supv. Alarm
Network Access Dial-in Service Modem, mounts to 4100-6078 or 4100-6061 Network
4100-6055 N.A. 60 mA 60 mA
Interface Card, requires telephone line connection
4100-1291 Un-isolated Remote Unit Interface Module (RUI); up to 3 maximum per control panel 1 Slot 85 mA 85 mA
4100-6031 Select one per EPS. City Circuit, with disconnect switches N.A. 20 mA 36 mA
4100-6032 Maximum one City City Circuit, w/o disconnect switches N.A. 20 mA 36 mA
Circuit module per Alarm/Supv/Tbl Relay, 3 Form C relays, 2 A @
4100-6033 panel N.A. 15 mA 37 mA
32 VDC
4100-6046 Dual Port RS-232 standard interface (single block) 3maximum 1Block 60mA 60mA
RS-232
4100-6038 Dual Port RS-232 with 2120 interface (slot module) Modules per 1Slot 132 mA 132 mA
panel
4100-6079 SafeLINC Internet Interface (refer to data sheet S4100-0062 for details) 2 Blocks 145 mA 145 mA
4190-6104 TrueInsight Remote Monitoring Module (refer to data sheet S4100-0063 for details) Side Mt. 62 mA 73 mA
4100-6101 Physical Bridge, Class B, includes 1 modem module and 2 wired modules 1Slot 210 mA 210 mA
4100-6102 Physical Bridge, Class X, includes 2 modem and 2 wired modules 2Slots 300 mA 300 mA
4100-6048 VESDA Aspiration System Interface (refer to data sheet S4100-0026 for details) 1Slot 132 mA 132 mA
DACT, Point or Event Reporting; 1 shipped unless 4100-7908 is selected; 2 max. per
4100-6080 SideMt. 30 mA 40 mA
system; includes 2, 2080-9047 cables, 14 ft (4.3 m) long, RJ45 plug and spade lugs

Page 6 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

Module Selection Information


Table 6: Additional Enhanced Power Supplies, Expansion Power Supply, and Accessories
Model Voltage Listing Description Size Supv. Alarm
4100-5311 120 VAC UL & ULC Enhanced Power Supply (EPS) with IDNet 2 Module; 9 225 mA 490 mA
A Enhanced Power Supply with battery charger, electrically
isolated 250 point IDNet 2 Module, three Class B IDNAC add IDNet
4 Blocks
SLCs, one 2 A output configurable for Auxiliary Power or device
4100-5313 220-240 VAC UL & ULC Right Side
Simple NAC operation, and expansion slot for City Circuit or currents
Alarm/Supv/Tbl Relay option; 120 VAC model has selectable separately
low battery cutout
4100-5325 120 VAC UL & ULC Expansion EPS; 9 A Expansion EPS, functionally identical 4 Blocks
to the Enhanced Power Supply except without the IDNet 2 125 mA 220 mA
4100-5327 220-240 VAC UL & ULC Right Side
Module
4100-5101 120 VAC UL & ULC Expansion Power Supply (XPS); 9 A output, 3 built-in
Class A/B conventional (non-addressable) 3 A NACs that
2 Blocks 50 mA 50 mA
4100-5102 220-240 VAC UL & ULC can also be selected as 2 A auxiliary power output, 2 A
separate auxiliary power output; without battery charger
Expansion Power Supply (XPS); 9 A output, 3 built-in
Class A/B conventional (non-addressable) 3 A NACs that
120 VAC,
4100-5103 ULC can also be selected as 2 A auxiliary power output, 2 A 2 Blocks 50 mA 50 mA
Canadian
separate auxiliary power output; without battery charger;
Canadian model has low battery cutout
4100-5115 NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only N.A. 25 mA 25 mA
Dual Class A IDNAC Isolator (DCAI), converts a single Class B IDNAC SLC input to
two Class A or two Class B SLC outputs; provides short circuit isolation between each
Class A or B output circuit; connect up to two DCAI Modules per IDNAC SLC input up
to a maximum of 6 DCAI Modules per EPS; each isolated output SLC used requires one
4100-6103 IDNAC address; the total current remains controlled by the Class B input source SLC 1 Block 8.3 mA 18.5 mA
at 3 A maximum; each isolated loop supports up to 30 device addresses (note: up to
30 additional device addresses may be installed between each 4905-9929 TrueAlert
Addressable Isolator+ Module, not to exceed the maximum address and unit loading
specifications for the IDNAC channel)
1.5 A
4100-5152 12 VDC Power Option, 2 A maximum 1 Block
maximum
included w/
4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block
loads
3 A maximum
with 2.5A
Voltage Regulator Module, 22.8 to 26.4 VDC (25VDC nominal); isolated and resettable
4100-5130 1 Block load, 4.9A
output; includes earth detection circuit and trouble relay for status monitoring
maximum
with 4 A load
4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet
4100-0638 4100 Slot Module Additional 24 VDC Harness; needed when 4100 Slot module requirements exceed 2 A from EPS

Note: for additional non-addressable Power Supplies, refer to data sheet S4100-0031.
Table 7: 8 Zone Initiating Device Circuits
Model Type Supv. Alarm
4100-5005 Class B 75 mA 195 mA
4100-5015 Class A 75 mA 195 mA

Note: Modules are for use with all 4100U systems and 4100ES systems version 3.03.05 or earlier. IDC Modules are 1 slot size.

Page 7 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

Table 8: 8-Point Zone/Relay Card (requires 4100ES Version 3.04.01 or later)


Model Description Size Supv. Alarm
8 point zone/relay 4x5” flat module. Mounts in any open block in a master
controller or expansion bay. Alarm current shown is for 8 Class B IDCs using 3.3K
4100-5013 end-of-line-resistors with 4 in alarm and 4 in standby. Standby current shown 1 block 83 mA 351 mA
is for all 8 IDCs in standby. Refer to 579-1236 Zone/Relay Module Installation
Instructions for additional information.
25V regulator harness for 8 point zone/relay module. One required for each 8
point zone/relay module to be powered by the 4100-5130 25V regulator module. A
4100-6305 N/A N/A N/A
maximum of (5) 8 point zone/relay modules may be powered from the 4100-5130
per bay.
Table 9: System Option for Seismic Compliance
Model Description
4100-7912 System option for Seismic compliance, provides additional stabilizer brackets required for legacy style cards
Table 10: Addressable Interface Modules
Model Description Supv. Alarm
IDNet 2 Module, 250 point capacity; electrically no devices 50 mA 60 mA
isolated output with two short circuit isolating Class 50 devices 90 mA 150 mA
4100-3109* B or Class A output loops, 1 block; standard on EPS 125 devices 150 mA 225 mA
with IDNet 2 Module; alarm currents for 50 and above
devices includes 20 device LEDs in alarm 250 devices 250 mA 350 mA
IDNet 2+2 Module, 250 point capacity; electrically no devices 50 mA 60 mA
isolated output with four short circuit isolating Class B 50 devices 90 mA 150 mA
or Class A output loops, 1 block; mounts in expansion 125 devices 150 mA 225 mA
4100-3110* bay or available master controller bay module locations
only, not applicable for EPS mounting; alarm currents
for 50 and above devices includes 20 device LEDs in 250 devices 250 mA 350 mA
alarm
IDNet Short Circuit Isolating Loop Output Module; mount up to two on a 4100-3109 module; for use with 4100-3109
4100-3111* modules in expansion bays or available master controller bay module locations only; not applicable for mounting on a
4100-3109 mounted on an EPS; this option is for aftermarket field installation only
Four Loop IDNet Master Controller; for the Master Controller Assemblies listed in Master Controller Selection
Information, this option moves the standard IDNet 2 Module from the Master Controller EPS to an available block space in
4100-3112
the master controller bay and adds 2, 4100-3111 IDNet Loop Output Modules.
Requires selection of Factory Built Option 4100-7905; current requirements remain the same.
Note: *

Loading per IDNet device (no LEDs on) = 0.8 mA supervisory and 1 mA alarm.

Total of initiating SLCs per CPU, including VESDA Interface, is 30.

Each IDNet 2 and IDNet 2+2 Short Circuit Isolating Loop Output can be individually controlled for system diagnostics and can be assigned a public
point for Fire Alarm Network annunciation.
Table 11: Relay Modules; Non power-limited (for mounting in expansion bay only)
Resistive Inductive
Model Description Size Supv. Alarm
Ratings Ratings
4100-3202 4 DPDT w/feedback 10 A @ 250 VAC 10 A @ 250 VAC 2 Slots 15 mA 175 mA
2 A @ 30 VDC/ 1/2 A @ 30
4100-3204 4 DPDT w/feedback 1 Block 15 mA 60 mA
VAC VDC/120 VAC
3 A @ 30 1-1/2 A @ 30
4100-3206 8 SPDT 1 Block 15 mA 190 mA
VDC/120 VAC VDC/120 VAC
Current Calculation Notes:
To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered by panel power
supplies.
To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel SLC and NAC loads and all
external loads powered from panel power supplies.
Table 12: End User Programming Software (requires 4100-8802)
Model Description
4100-8802 Programming Software (select)

Page 8 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

Table 13: End User Programming Software Selection (select maximum of one each from below)
Model Description
4100-0292 Custom Labels Editing; allows editing of 40 Character Custom Labels for non-system user points
Access Level/Passcode Editing; allows user to re-assign Access Levels and Passcodes for each display function;
4100-0296 Acknowledge, Alarm Silence, System Reset, Point Enable/Disable, WALKTEST Enable/Disable, Clear History Logs, Change
Time & Date, etc.
4100-0295 Port Vectoring Setup and Control; Allows vectoring of events to PC Annunciator, Printers, LCD Annunciators, etc.
WALKTEST Configuration Setup and Control; Allows user to create or edit WALKTEST groups used to test system
initiating devices and signals by a single person, these groups allow an inspector to conduct a one-person WALKTEST in
4100-0298
a specific area of a building (or different buildings), and limit the activation of the building signals to only the intended
area; up to 8 WALKTEST groups are supported
Table 14: Miscellaneous Accessories
Model Description
4100-1279 Single blank 2” display cover; 4100-2302 provides a single plate for a full bay
4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules
4100-9856 4100ES Canadian French Appliqué Kit; Simplex, 4100ES, Contrôle Incendie
4100-9868 Special Purpose Appliqué Kit: Simplex, Elevator Recall Control and Supervisory Control Unit, 4100ES
4100-9869 Special Purpose Appliqué Kit: Simplex, Sprinkler Waterflow and Supervisory Station, 4100ES
4100-6029 Smoke Management Application Guide; required for UUKL listing
Tamper Switch, one per cabinet assembly if required; monitors solid door for panels with solid door; monitors the
4100-6034
internal retainer panel for panels with glass door (not the glass door); has a built-in addressable IDNet IAM
Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper)
2081-9031
470 Ω, 1 W, encapsulated, two 18 AWG leads (0.82 mm2 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)

Network Interface and Network Media Card Product Selection


4100ES fire alarm control units are compatible with Simplex ES Net network or 4120 network fire alarm products.
• Refer to datasheet S4100-0076 for additional information on compatible ES Net fire alarm products.
• Refer to datasheet S4100-0056 for additional information on compatible 4120 network fire alarm products.

Page 9 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

General Specifications
Table 15: General Specifications
Specification Description
120 VAC Models 4.6 A maximum @ 102 to 132 VAC, 50/60 Hz
2.3 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for
Enhanced Power Supplies (EPS) 220-240 VAC Models
220/230/240 VAC
Input Power Battery Input Rating 12 A maximum @ 24 VDC (during battery operation)
120 VAC Models 4 A maximum @ 102 to 132 VAC, 60 Hz
Expansion Power Supplies (XPS) 2 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for
220-240 VAC Models
220/230/240 VAC
9 A output for "Special Application" appliances

Note:
Total Power Supply
Output Rating The 9 A output rating of the EPS was determined such that optional
module currents, and external device and appliance currents can be Output switches to
Power Supply Output directly added together, not to exceed 9 A total. battery backup during
Ratings for EPS 3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit loads; mains AC failure or
IDNAC SLC Ratings
DC-DC converter circuit is >92% efficient over operating range brownout conditions
Output terminals are rated for 18 to 12 AWG with duplicate output
terminals rated for two wires each, allowing up to four (4) Class B
IDNAC SLC Wiring
branch circuit T-taps to be made in the cabinet; additional T-taps
may be made in external wiring junction cabinets or boxes
Auxiliary Power Tap 2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC)
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex
Compatible Special Application Appliances
product representative for compatible appliances
UL listed for battery charging of 6.2 Ah up to 115 Ah (batteries larger than 50 Ah require a
Battery Charger Ratings Battery capacity range
remote battery cabinet); ULC listed for charging up to 50 Ah batteries
for EPS (sealed lead-
Charger characteristics and Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL
acid batteries)
performance Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Including module currents and auxiliary power outputs; NAC outputs
Power Supply Output Total Power Supply Output are rated 9 A output for "Special Application" non-addressable
Output switches to
Ratings for XPS Rating appliances; 4 A output for "Regulated 24 DC" power (see details
(nominal 28 VDC on below); 6 A output with each NAC selected as auxiliary power output battery backup during
mains AC failure or
AC; 24 VDC on battery Auxiliary Power Tap 2 A maximum
brownout conditions
backup) NACs Programmed for 2 A maximum per NAC; 5 A Rated 19.1 to 31.1 VDC
Auxiliary Power maximum total
Special Application Simplex horns, strobes, and combination horn/strobes and speaker/strobes (contact your Simplex product representative
Appliances for compatible appliances)
Regulated 24 DC
Power for other UL listed appliances; use associated external synchronization modules where required
Appliances
Operating Temperature 32° to 120°F (0° to 49° C)
Environmental
Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum

Expansion Bay Module Loading Reference

Figure 7: Expansion Bay Reference

Size Definitions:
• 1 Block = 4" W x 5.65" H (102 mm x 144 mm); (often called 4 x 5 modules)
• 1 Slot = 2" W x 11.3" H (51 mm x 287 mm), typically a motherboard with daughter card

Page 10 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

Operator Interface
Convenient Status Information
With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. Features include a two-line
by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in Figure 8.
LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door
provides access to the control switches and allows further inquiry by scrolling the display for additional detail.

Operator Interface Features


• Convenient and extensive operator information is provided using a logical, menu-driven display
• Multiple automatic and manual diagnostics for maintenance reduction
• Alarm and Trouble History Logs (up to 1000 entries for each, 2000 total events) are available for viewing from the LCD, or capable of being printed to
a connected printer, or downloaded to a service computer
• Convenient PC programmer label editing
• Password access control

Figure 8: Operator interface features

Page 11 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

Mounting and CPU Bay Module Reference

Figure 9: Mounting and CPU Bay Module Reference (* indicates supplied modules)

Note:

1. Side View dimensions are shown with minimal cabinet and door protrusion from the exterior wall. For 6 inch stud construction with minimum pro-
trusion shown, the door will open 90 degrees. To allow the door to open 180 degrees, the exposed cabinet dimension from the exterior wall must be a
minimum of 3 inches (76 mm) for both 4 inch and 6 inch stud construction.

2. A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved, dedicated
Earth connection per NFPA 70, Article 250, and NFPA 780.
Table 16: Reference Notes
Note PID
Note 1 4100-6052
Note 2 4100-6101
Note 3 4100-6102
Note 4 4100-6048
Note 5 4100-5005 or 4100-5015
Note 6
4100-6038
Note 7
Note 8 4100-6031
Note 9 4100-6032
Note 10 4100-6033

Page 12 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

TrueAlert ES Appliance Self-Test Last Test ResultsReport Example

Figure 10: TrueAlert ES Appliance Self-Test Last Test Results Report Example


Results Description
• NORMAL = Works correctly
• NO OUT = No Output, no light or sound was detected
• NOT TST = No result. Either the appliance did not return a result before the test ended or the test was conducted as silent (strobes only) and audible
appliance was not activated
• N/A = Not applicable (no strobe, on audible only, etc.)
• UNSUPP = Appliance not compatible with Self-Test (TrueAlert addressable appliance not TrueAlert ES addressable appliance)

Note: Additional TrueAlert ES Self-Test information is detailed in ES Operating Instructions 579-197 shipped with the panel.

TrueAlert ES Appliance Self-Test All Test ResultsReport Example

Figure 11: TrueAlert ES Appliance Self-Test All Test Results Report Example

TrueAlert ES Appliance Self-Test Individual Appliance Report Example

Figure 12: TrueAlert ES Appliance Self-Test Individual Appliance Report Example

Page 13 S4100-0100 Rev. 21 5/2019


Addressable Fire Detection and Control Basic Panel Modules and Accessories

Additional Technical and Datasheet Reference


Table 17: Additional Technical Reference
Description Document
ES Installation Instructions 574-848
ES Operating Instructions 579-197
DCAI Module Installation Instructions 579-1029
IDNet 2 and 2+2 Module Installation Instructions 579-1169
EPS Installation Instructions 579-1015
Table 18: Additional 4100ES datasheet reference
Subject Data Sheet
Serial DACT (SDACT) for 4100ES, 4010ES, 4007ES S2080-0009
Battery and Battery Cabinet Reference for 4100ES S2081-0006
110 Ah Batteries and Cabinets for 4100ES S2081-0012
Seismic Battery Brackets Reference S2081-0019
4009 IDNet NAC Extender S4009-0002
4009 IDNAC Repeater S4009-0004
External 110 Ah Battery Charger for 4100ES, 4010ES S4081-0002
Graphic I/O Modules for 4100ES, 4010ES, 4007ES S4100-0005
Interface to VESDA Air Aspiration Detection Systems S4100-0026
4100ES Basic Panels with SPS Power Supplies S4100-0031
4100ES LED/Switch Modules & Printer S4100-0032
Master Clock Interface S4100-0033
4100ES Emergency Voice/Alarm Equipment S4100-0034
MINIPLEX Transponders with SPS Power Supplies S4100-0035
NDU with SPS Power Supplies for 4120 Network S4100-0036
4100ES Enclosures S4100-0037
4100ES Remote Annunciator Panels S4100-0038
4100ES Extinguishing Release Applications S4100-0040
TFX Interface Module S4100-0042
InfoAlarm Command Center with SPS Power Supplies S4100-0045
2120 BMUX Module S4100-0048
Multiple Signal Fiber Optic Modems for 4120 Networks S4100-0049
BACpac Ethernet Module S4100-0051
4120 Network Products and Specifications S4100-0056
Building Network Interface Card (BNIC) S4100-0061
SafeLINC Internet Interface S4100-0062
TrueInsight Remote Gateway S4100-0063
ES Net Network Products and Specifications S4100-0076
NDU with SPS Power Supplies for ES Net S4100-0077
InfoAlarm Command Center with EPS Power Supplies S4100-0101
NDU with EPS Power Supplies for 4120 Network S4100-0102
MINIPLEX Transponders with EPS Power Supplies S4100-0103
NDU with EPS Power Supplies for ES Net S4100-0104
120 VAC Remote Printer S4190-0011
PC Annunciator S4190-0013
TrueSite Workstation S4190-0016
Network System Integrator (NSI) for 4120 Networks S4190-0017
TrueSite Incident Commander S4190-0020
SCU/RCU Annunciators S4602-0001
LCD Annunciator for 4100ES S4603-0001

© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without
notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
S4100-0100 Rev. 21 5/2019

You might also like