3.-Modulo IDNET S4100-0100 - SIMPLEX
3.-Modulo IDNET S4100-0100 - SIMPLEX
UL, ULC, CSFM Listed; FM, NYC Addressable Fire Detection and Control Basic Panel Modules and Accessories
Fire Dept Approved*
Features current draw and voltage drop margin under both primary power and
secondary battery standby
• Efficiencies include lower strobe currents, wiring distances up to 2 to
3 times farther than with conventional notification, support for more
appliances per IDNAC SLC, and the ability to use smaller gauge wiring –
all providing installation and maintenance savings with high assurance
that appliances that operate during normal system testing will also
operate during worst case alarm conditions
• IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert
addressable notification appliances, and remote 4009 IDNAC
Repeaters to extend power and wiring distance even farther
This product has been listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0251 for allowable values
and/or conditions concerning material presented in this document. NYC Fire Dept COA #6151. At the time of publication only UL and ULC listings are applicable to ES Net network products. Additional
listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Introduction
4100ES fire panels provide extensive installation, operator, and service
features with point and module capacities suitable for a wide range of
system applications. An on-board Ethernet port provides fast external
system communications to expedite installation and service activity.
Dedicated compact flash memory archiving provides secure on-site
system information storage of electronic job configuration files to meet
NFPA 72 (National Fire Alarm and Signaling Code) requirements.
Modular design
A wide variety of functional modules are available to meet specific
system requirements. Selections allow panels to be configured for either
Figure 2: 4100ES Module Placement
stand-alone or networked fire control operation.
Reference in 3-Bay Cabinet
Programmable sensitivity
Programmable sensitivity of each sensor can be selected at the control
panel for different levels of smoke obscuration (shown directly in
percent) or for specific heat detection levels. To evaluate whether the
sensitivity should be revised, the peak value is stored in memory and can
be easily read (or downloaded as a report) and compared to the alarm
threshold directly in percent.
Figure 3: Operator interface
CO sensor bases
CO sensor bases combine an electrolytic CO sensing module with a
IDNet Addressable Device and IDNAC Addressable TrueAlarm analog sensor to provide a single multiple sensing assembly
Notification Appliance Control using one system address. The CO sensor can be enabled/disabled,
Overview.The 4100ES EPS power supply with IDNet 2 Module provides used in LED/Switch modes and custom control, and can be made public
addressable initiating device and IDNAC addressable notification for communication across a fire alarm Network. (refer to data sheet
appliance Signaling Line Circuits (SLCs) that supervise wiring connections S4098-0052 for details)
and the individual device/appliance communications status on their
SLC. With these 2-wire SLCs, initiation, monitoring, and control devices TrueAlarm heat sensors
such as manual fire alarm stations, TrueAlarm sensors, control relays, TrueAlarm heat sensors can be selected for fixed temperature detection,
and sprinkler waterflow switches; and notification appliances such with or without rate-of-rise detection. Utility temperature sensing is also
as strobes and horns can communicate their identity and status and available, typically to provide freeze warnings or alert to HVAC system
receive fire alarm system control. Additional interface modules include problems. Readings can selected as either Fahrenheit or Celsius.
circuit isolators, conventional IDC zone adapters, and interface to other
TrueSense Early Fire Detection
system circuits such as fans, dampers, and elevator controls.
Multi-sensor 4098-9754 provides photoelectric and heat sensor data
using a single 4100ES IDNet address. The panel evaluates smoke
IDNet Addressable Device Operation activity, heat activity, and their combination, to provide TrueSense
Each addressable device on an IDNet communication channel early detection. For more details on this operation, refer to data sheet
is continuously interrogated for status condition such as: normal, S4098-0024 .
off-normal, alarm, supervisory, or trouble. Both Class B and Class A
operation is available. Sophisticated poll and response communication
techniques ensure supervision integrity and allow for "T-tapping" of
Diagnostics and Default Device Type
the circuits for Class B operation. Devices with LEDs pulse the LED Sensor Status
to indicate receipt of a communications poll and can be turned on TrueAlarm operation allows the control panel to automatically indicate
steady from the panel. With addressable devices, the location and when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72
status of the connected device is monitored and logged, and displayed requirement for a test of the sensitivity range of the sensors is fulfilled
on the operator interface LCD and on remote system annunciators by the ability of TrueAlarm operation to maintain the sensitivity level of
with each device having its own 40 character custom label for precise each sensor. CO Sensors track their 10 year active life status providing
identification. indicators to assist with service planning. Indicators occur at: 1 year, 6
months, and end of life.
TrueAlarm Addressable Sensor Operation
Modular TrueAlarm sensors
Addressable initiating device communications include operation of
TrueAlarm smoke and temperature sensors. Smoke sensors transmit Modular TrueAlarm sensors use the same base and different sensor
an output value based on their smoke chamber condition and the CPU types (smoke or heat sensor) and can be easily interchanged to
maintains a current value, peak value, and an average value for each meet specific location requirements. This allows intentional sensor
sensor. Status is determined by comparing the current sensor value to substitution during building construction when conditions are
its average value. Tracking this average value as a continuously shifting temporarily dusty. Instead of covering smoke sensors (causing them to
reference point filters out environmental factors that cause shifts in be disabled), heat sensors may be installed without reprogramming the
sensitivity. control panel. The control panel will indicate an incorrect sensor type,
but the heat sensor will operate at a default sensitivity to provide heat
detection for building protection at that location.
of wires. IDNet 2 and IDNet 2+2 Module SLCs are isolated from other Virtual NACs Provide Control Convenience
system reference voltages to reduce common mode noise interaction For control convenience, IDNAC notification appliances can be grouped
with adjacent system wiring. Additional 250 address IDNet 2 or IDNet into Virtual NACS (VNACs) for group control, grouping that can be made
2+2 Modules are available. across SLCs, not defined by their wiring connection.
Table 2: IDNet 2 and IDNet 2+2 SLC Wiring Specifications Panel Control Convenience
Specification Rating Applicable operation settings for each appliance can be programmed
4000 ft (1219 m); 50 without having to replace appliances or remove them from the wall or
Maximum Distance 1 - 125
ohms ceiling. An appliance's VNAC notification zone can be easily changed
from Control Panel per
2500 feet (762 m); 35 through programming without having to add additional circuits, conduit,
Device Load 126 - 250
ohms and wiring. Audible and visible appliances for non-Fire Emergency
Up to 12,500 ft (3.8 Communications notification can be programmed to operate separately
Total Wire Length Allowed With “T” Taps for on the same pair of wires as the fire alarm notification appliances. The
km);
Class B Wiring result is lower installation, retrofit, and overall life-cycle cost of ownership
0.60 µF
compared with traditional conventional notification systems.
Maximum Capacitance Between IDNet 2
1 µF
Channels Installation, Retrofit, and Life-Cycle Cost Benefits
0.8 mA supv., 1 mA With each addressable appliance capable of being controlled separately
alarm; on the same two-wire IDNAC SLC, installation time and expense for
Loading per device
2 mA per activated both retrofit and new construction can be significantly reduced. When
device LED Class B wiring is used, wiring can be "T-tapped" allowing more savings
Shielded or unshielded, in distance, wire, conduit (size and utilization), and overall installation
Wire Type and Connections twisted or untwisted efficiency.
wire*
Location Information, Diagnostics and Troubleshooting
Terminals for 18 to 12
2 Each addressable notification appliance has its own 40 character
Connections AWG (0.82 mm to 3.31 custom label to identify the location of the appliance and to aid in
2
mm ) troubleshooting fault conditions. In conventional notification systems,
IDNet 2 and IDNet 2+2 Module Compatibility: IDNet conventional appliances are not capable of communicating with the
communicating devices and TrueAlarm sensors including QuickConnect control panel. Fault reporting on a conventional system is limited to
and QuickConnect2 sensors the circuit wiring and the entire area (zone) covered by appliances on
Note: * Some applications may require shielded wiring. Review your the notification appliance circuit (NAC) making it much more difficult
system with your local Simplex product supplier. and costly to locate and correct the source of a problem. Using the
TrueAlert magnet test allows each appliance to individually identify
IDNAC SLC Control of TrueAlert and TrueAlert ES its candela setting and address and to briefly operate if desired, and
using the TrueAlert ES Appliance Self-Test feature provides detailed
Addressable Notification
performance verification per appliance.
Addressable notification appliance communications include
operation of TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible
only (A/O, horn), Audible/Visible (A/V, horn/strobe), and strobes of TrueAlert ES Appliance Self-Test Operation
Speaker/Visible (S/V) notification appliances. (S/V appliances require On-Board Test Sensors
separate speaker wiring.) IDNAC SLC addressable communications
TrueAlert ES appliances are equipped with on-board sensors to detect
allow each horn and strobe to be individually controlled using a single
strobe and/or horn output allowing efficient and unobtrusive Self-
two-wire circuit, confirms the wiring connections to the individual
Testing. When Automatic Self-Test is initiated from the control panel,
notification appliance's electronic circuit, and confirms communications
each appliance within the selected VNAC group will briefly operate and
between each appliance and the fire alarm control panel. Addressable
then report its Self-Test status to the control panel, all within several
communications increases supervision integrity versus conventional
seconds. Silent Self-Test can be selected to test only visible appliance
notification systems by providing supervision beyond the circuit wiring to
if desired. The control panel is in a trouble condition during testing
each individual appliance and by constantly verifying the ability of each
and in the event of an alarm, Self-Test is automatically terminated.
appliance to communicate with the control panel.
Additionally, Automatic Self-Test can be scheduled to occur at a
Individual Appliance Status and Settings convenient time on a regular basis (Requires version 2.03.01 or higher
The fire alarm control panel monitors and records each addressable software).
notification appliance status, type of appliance, and its configured Automatic Self-Test
appliance settings. A fault in any individual appliance automatically
Automatic Self-Test results are communicated to the control panel with
reports a trouble condition to the control panel.
a time and date stamp and are stored in memory. Results are viewable
at the front panel display and printed reports can be generated from the
panel service port.
Individual Self-Test
Individual Self-Test is selected from the control panel when individual
appliances need to be observed to operate. Each appliance in the
selected VNAC group will turn on its LED until individually activated by
applying a magnet. After performing the individual test, the appliance
LED turns off to indicate completion. Results are recorded the same as
during the automatic test.
IDNAC SLC Hardware Reference 4100-6032, without disconnect switches) can be selected for
conventional dual circuit city connections
EPS Power Supplies
• Alarm Relay Module (4100-6033) provides three Form C relays that are
EPS Power Supplies provide three, 3 A IDNAC SLCs for control and used for Alarm, Trouble, and Supervisory, rated 2 A resistive @ 32 VDC
power to TrueAlert ES and TrueAlert addressable notification appliances.
Both power supplies incorporate an efficient switching design that EPS (Enhanced Power Supply) with IDNet 2 Module Details
provides a regulated output of 29 VDC, even during battery operation. • Rating is 9 A output with "Special Application" appliances
With 29 VDC minimum output at the panel, addressable notification • Outputs are power-limited, except for the battery charger
SLCs can support wiring distances 2 to 3 times farther than available
• Provides system power, battery charging, auxiliary power, earth
with conventional notification, or support more appliances per SLC, or
detection, on-board electrically isolated IDNet 2 Module with 250
work with smaller gauge wiring, or combinations of these benefits, all
point SLC, three on-board 3 A IDNAC SLCs, and provisions for either
resulting in installation and maintenance savings with high assurance
an optional City Connect Module or an optional Alarm/Supv/Tbl Relay
that appliances that operate during normal system testing will operate
Module
during worst case alarm conditions.
• IDNet 2 Module SLC Output provides Class B or Class A
communications for up to 250 addressable devices with dual short
IDNAC SLC Appliance Wiring Reference circuit isolating loop outputs
IDNAC SLC Capacity
Note: The "IDNet 2 Module" replaced the "IDNet 1+ Module" and the
Up to 127 addresses and up to 139 unit loads (appliances are typically
term "EPS with IDNet 2 Module" replaces the term "EPS+"
one unit load, devices such as Isolators may require more than one load,
• Note: The “IDNet 2 Module” replaced the “IDNet 1+ Module” and the
refer to individual device data sheet for specific information)
term “EPS with IDNet 2 Module” replaces the term “EPS+”. DCAI (Dual
Table 3: IDNAC SLC Appliance Wiring Reference Class A IDNAC Isolator) Module creates two Class A outputs from
Specification Rating one IDNAC SLC Class B Input; up to two can be connected to one
IDNAC SLC, with up to 6 total per EPS; total Class A output loop current
Recommended wire type UTP, unshielded twisted pair
is limited to the 3 A rating of the IDNAC SLC
Maximum wire length allowed
with "T-Taps" for Class B wiring, 10,000 ft (3048 m) • Battery Charger is dual rate, temperature compensated, and
per SLC charges up to 50 Ah sealed lead-acid batteries mounted in the battery
Maximum wire length per SLC compartment (33 Ah for single bay cabinets). UL listed for charging up
4000 ft (1219 m) to 110 Ah batteries mounted in an external cabinet (see data sheet
to any appliance
S2081-0012 for details)
Appliance Supervisory Current 1 unit load = 0.8 mA per appliance
2 • Battery and Charger Monitoring includes battery charger status
Terminals for 18 to 12 AWG (0.82 mm and low or depleted battery conditions; status information provided
Wiring connections 2
to 3.31 mm ) to the master controller includes analog values for: battery voltage,
Installation Instructions (see for charger voltage and current, actual system voltage and current, and
579-1015
more information) individual IDNAC SLC currents
• Low Battery Cutout is selectable for each EPS power supply,
Standard CPU Bay Module Details Canadian models are shipped selected, other models are shipped
unselected
Master Controller and Motherboard
• Mounts in Slot 2 of a two slot motherboard and provides one Class B 2 A Programmable Output
or Class A, RUI+ communications channel configurable for isolated or • Select for conventional non-synchronous NAC operation to provide
un-isolated operation supervised reverse polarity for sounder base power, Suppression
• Slot 1 of the motherboard is primarily for an optional network Release Peripheral (SRP) power, or other coded NAC operation
interface card or secondarily for the 4100-6038 dual RS-232 board requirements
communications • Select for Auxiliary (AUX) operation for sounder base power, 4-wire
• RUI+ and RUI communications controls up to 31 remote devices per detector power, or door holder; supervised AUX operation does not
master controller at up to 2500 ft (762 m) for single run, or 10,000 require an end-of-line relay to provide power-limited operation
ft (3048 m) total if wiring is Class B and T tapped; if more distance is 8-Point Zone/Relay Module Details
required, up to four total RUI channels are supported; add up to three
• Select as IDC or Relay; configure up to 8, Class B IDCs, or up to
4100-1291 RUI Expansion Modules (4100-1291 provides unisolated
4, Class A IDCs; or up to 8, Relay outputs rated 2 A resistive @ 30
RUI communications)
VDC (N.O. or N.C.); or combinations of IDCs and Relays; each zone is
• Compatible RUI+ and RUI remote equipment includes: MINIPLEX separately configurable as an IDC or Relay output
transponders, 4603-9101 LCD Annunciators, 4602-9101 Status
• IDC Support: each IDC supports up to 30, two-wire devices. Zone relay
Command Units (SCU), 4602-9102 Remote Command Units (RCU),
modules may be powered directly from the control unit power supply
4602 Series LED Annunciator Panels, 4100 Series 24 I/O and LED/
or through the optional 25 VDC regulator module where required for
Switch modules, (4602 series annunciators require un-isolated
2- wire detector compatibility (refer to 2-Wire Detector Compatibility
communications).
document 579-832 for additional details).
• Up to 4 RUI channels (combination of built-in RUI+ and optional RUI
• IDC EOL resistor values are selectable as: 3.3 kΩ, 2 kΩ, 2.2 kΩ, 3.4
modules) are supported
kΩ, 3.9 kΩ, 4.7 kΩ, 5.1 kΩ, 5.6 kΩ, 6.34/6.8 kΩ, and 3.6 kΩ + 1.1 kΩ; see
• Open slot space on the left of the CPU motherboard is available for instructions for more details
either another dual slot motherboard, or for one or two block modules
(refer to Figure 2)
Note: for additional non-addressable Power Supplies, refer to data sheet S4100-0031.
Table 7: 8 Zone Initiating Device Circuits
Model Type Supv. Alarm
4100-5005 Class B 75 mA 195 mA
4100-5015 Class A 75 mA 195 mA
Note: Modules are for use with all 4100U systems and 4100ES systems version 3.03.05 or earlier. IDC Modules are 1 slot size.
Loading per IDNet device (no LEDs on) = 0.8 mA supervisory and 1 mA alarm.
Each IDNet 2 and IDNet 2+2 Short Circuit Isolating Loop Output can be individually controlled for system diagnostics and can be assigned a public
point for Fire Alarm Network annunciation.
Table 11: Relay Modules; Non power-limited (for mounting in expansion bay only)
Resistive Inductive
Model Description Size Supv. Alarm
Ratings Ratings
4100-3202 4 DPDT w/feedback 10 A @ 250 VAC 10 A @ 250 VAC 2 Slots 15 mA 175 mA
2 A @ 30 VDC/ 1/2 A @ 30
4100-3204 4 DPDT w/feedback 1 Block 15 mA 60 mA
VAC VDC/120 VAC
3 A @ 30 1-1/2 A @ 30
4100-3206 8 SPDT 1 Block 15 mA 190 mA
VDC/120 VAC VDC/120 VAC
Current Calculation Notes:
To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered by panel power
supplies.
To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel SLC and NAC loads and all
external loads powered from panel power supplies.
Table 12: End User Programming Software (requires 4100-8802)
Model Description
4100-8802 Programming Software (select)
Table 13: End User Programming Software Selection (select maximum of one each from below)
Model Description
4100-0292 Custom Labels Editing; allows editing of 40 Character Custom Labels for non-system user points
Access Level/Passcode Editing; allows user to re-assign Access Levels and Passcodes for each display function;
4100-0296 Acknowledge, Alarm Silence, System Reset, Point Enable/Disable, WALKTEST Enable/Disable, Clear History Logs, Change
Time & Date, etc.
4100-0295 Port Vectoring Setup and Control; Allows vectoring of events to PC Annunciator, Printers, LCD Annunciators, etc.
WALKTEST Configuration Setup and Control; Allows user to create or edit WALKTEST groups used to test system
initiating devices and signals by a single person, these groups allow an inspector to conduct a one-person WALKTEST in
4100-0298
a specific area of a building (or different buildings), and limit the activation of the building signals to only the intended
area; up to 8 WALKTEST groups are supported
Table 14: Miscellaneous Accessories
Model Description
4100-1279 Single blank 2” display cover; 4100-2302 provides a single plate for a full bay
4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules
4100-9856 4100ES Canadian French Appliqué Kit; Simplex, 4100ES, Contrôle Incendie
4100-9868 Special Purpose Appliqué Kit: Simplex, Elevator Recall Control and Supervisory Control Unit, 4100ES
4100-9869 Special Purpose Appliqué Kit: Simplex, Sprinkler Waterflow and Supervisory Station, 4100ES
4100-6029 Smoke Management Application Guide; required for UUKL listing
Tamper Switch, one per cabinet assembly if required; monitors solid door for panels with solid door; monitors the
4100-6034
internal retainer panel for panels with glass door (not the glass door); has a built-in addressable IDNet IAM
Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper)
2081-9031
470 Ω, 1 W, encapsulated, two 18 AWG leads (0.82 mm2 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)
General Specifications
Table 15: General Specifications
Specification Description
120 VAC Models 4.6 A maximum @ 102 to 132 VAC, 50/60 Hz
2.3 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for
Enhanced Power Supplies (EPS) 220-240 VAC Models
220/230/240 VAC
Input Power Battery Input Rating 12 A maximum @ 24 VDC (during battery operation)
120 VAC Models 4 A maximum @ 102 to 132 VAC, 60 Hz
Expansion Power Supplies (XPS) 2 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for
220-240 VAC Models
220/230/240 VAC
9 A output for "Special Application" appliances
Note:
Total Power Supply
Output Rating The 9 A output rating of the EPS was determined such that optional
module currents, and external device and appliance currents can be Output switches to
Power Supply Output directly added together, not to exceed 9 A total. battery backup during
Ratings for EPS 3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit loads; mains AC failure or
IDNAC SLC Ratings
DC-DC converter circuit is >92% efficient over operating range brownout conditions
Output terminals are rated for 18 to 12 AWG with duplicate output
terminals rated for two wires each, allowing up to four (4) Class B
IDNAC SLC Wiring
branch circuit T-taps to be made in the cabinet; additional T-taps
may be made in external wiring junction cabinets or boxes
Auxiliary Power Tap 2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC)
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex
Compatible Special Application Appliances
product representative for compatible appliances
UL listed for battery charging of 6.2 Ah up to 115 Ah (batteries larger than 50 Ah require a
Battery Charger Ratings Battery capacity range
remote battery cabinet); ULC listed for charging up to 50 Ah batteries
for EPS (sealed lead-
Charger characteristics and Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL
acid batteries)
performance Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Including module currents and auxiliary power outputs; NAC outputs
Power Supply Output Total Power Supply Output are rated 9 A output for "Special Application" non-addressable
Output switches to
Ratings for XPS Rating appliances; 4 A output for "Regulated 24 DC" power (see details
(nominal 28 VDC on below); 6 A output with each NAC selected as auxiliary power output battery backup during
mains AC failure or
AC; 24 VDC on battery Auxiliary Power Tap 2 A maximum
brownout conditions
backup) NACs Programmed for 2 A maximum per NAC; 5 A Rated 19.1 to 31.1 VDC
Auxiliary Power maximum total
Special Application Simplex horns, strobes, and combination horn/strobes and speaker/strobes (contact your Simplex product representative
Appliances for compatible appliances)
Regulated 24 DC
Power for other UL listed appliances; use associated external synchronization modules where required
Appliances
Operating Temperature 32° to 120°F (0° to 49° C)
Environmental
Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Size Definitions:
• 1 Block = 4" W x 5.65" H (102 mm x 144 mm); (often called 4 x 5 modules)
• 1 Slot = 2" W x 11.3" H (51 mm x 287 mm), typically a motherboard with daughter card
Operator Interface
Convenient Status Information
With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. Features include a two-line
by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in Figure 8.
LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door
provides access to the control switches and allows further inquiry by scrolling the display for additional detail.
Figure 9: Mounting and CPU Bay Module Reference (* indicates supplied modules)
Note:
1. Side View dimensions are shown with minimal cabinet and door protrusion from the exterior wall. For 6 inch stud construction with minimum pro-
trusion shown, the door will open 90 degrees. To allow the door to open 180 degrees, the exposed cabinet dimension from the exterior wall must be a
minimum of 3 inches (76 mm) for both 4 inch and 6 inch stud construction.
2. A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved, dedicated
Earth connection per NFPA 70, Article 250, and NFPA 780.
Table 16: Reference Notes
Note PID
Note 1 4100-6052
Note 2 4100-6101
Note 3 4100-6102
Note 4 4100-6048
Note 5 4100-5005 or 4100-5015
Note 6
4100-6038
Note 7
Note 8 4100-6031
Note 9 4100-6032
Note 10 4100-6033
Note: Additional TrueAlert ES Self-Test information is detailed in ES Operating Instructions 579-197 shipped with the panel.
© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without
notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
S4100-0100 Rev. 21 5/2019