Cerberus® PRO FC922 / FC924

Programming Guide

Fan Restart Configuration

Siemens Industry, Inc. Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Objective:
The Following steps are designed to activate a Fan Shutdown relay on any
alarm, hold the relay active thru a panel reset, activate a status LED
indicating FAN RESTART and pressing a PMI button to restart the fans

Programming:
•Add the relay module HTRI-R / 8704 or FDCIO422 to the hardware tree. Page #3
•Create the hold thru reset Fire Control. Page #5
•Configure a PMI button to re-start the fan. Page #9
•Configure a PMI Status LED to indicate Fan re-start . Page #10

Siemens Industry, Inc. 2 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Adding the HTRI-R / 8704 / FDCIO422 Relay Module


To add the HTRI-R/8704/FDCIO422 relay module, proceed as follows:
(Repeat the following steps for additional relays as needed)

1. Select the ‘Hardware’ task card.

2. Open the ‘C-NET card’ element in the tree view.


3. Select the desired loop Circuit.

Siemens Industry, Inc. 3 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Adding the HTRI-R / 8704 / FDCIO422 Relay Module


4. Right-Click and select ‘New’ from the drop down menu.
5. Select the desire relay module ‘HTRI-R / 8704/FDCIO422’ from the drop
down list.

‘HTRI-R / 8704/FDCIO422’ added to the Loop circuit

Siemens Industry, Inc. 4 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Creating the Fire Control to activate the output


1. Select the ‘Control’ task card.

2. Open the ‘Panel’ element in the tree view.


3. Select the ‘Fire control group’ element in the tree view.

4. Right-Click and select ‘New’ -> ‘Fire control’ -> ’Standard Fire control’
from the drop down list.

Fire Control Created


*Optional: enter ‘Fan Shutdown’ in the Customer text window

Siemens Industry, Inc. 5 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Creating the Fire Control to activate the output


5. Open the ‘Fire control’ element in the tree view.
6. Select the ‘Effect’ property of the fire control in the tree view.

7. Right-Click and select ‘Assign’ from the drop down menu.

Siemens Industry, Inc. 6 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Creating the Fire Control to activate the output


8. Select the desired ‘Output’ and click ‘Assign’.
9. Close the dialog window when it re-appears.

The Output is assigned to the effect of the fire control

Siemens Industry, Inc. 7 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Configuring the Fire Control to activate on any


ALARM
1. Select the ‘Causes’ property of the fire control in the tree view.
2. Right-Click and select ‘Assign’ from the drop down menu.
3. Select the ALL ALARM command from the Event alarm category
4. Select detection tree and navigate to the panel element and assign it

Any Alarm from the Panel has been assigned to the Cause of the Fire
control, and will activate the relay in the Effects

Siemens Industry, Inc. 8 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Configuring the Fire Control to HOLD THRU


RESET
1. Select the ‘Fire Control Element in the tree view.

2. Select the Overview tab


3. Select ‘Undefined (no autom. deactivation) for the STOP mode
property – this will hold thru reset as it tells the formula not to stop
once activated .

Siemens Industry, Inc. 9 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Assigning a PMI button (Standard Keys) to stop the


fire control

To assign a standard key to stop the control function, proceed as follows:


1. Select the ‘Operation’ task card.

2. Open ‘Panel’ -> ‘PMI’ -> ‘Standard Keys’ in the tree view.
3. Highlight the appropriate ‘Standard Key’

Siemens Industry, Inc. 10 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Assigning a PMI button (Standard Keys) to stop the


fire control
4. Right-Click on the highlighted standard key
5. Select Assign from the drop down menu

6. Select the Deactivate command from the Activate/Deactivate


command category
7. Select Control and select the Fan shutdown Fire control – assign it

Siemens Industry, Inc. 11 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Assigning a PMI Status LED to indicate FAN RESTART


To assign the FAN RESTART status LED, proceed as follows:
1. Select the ‘Operation’ task card.

2. Open ‘Panel’ -> ‘PMI’ -> ‘LEDs’ in the tree view.


3. Select the required ‘LED’
should be the LED next to the PMI Button for FAN RESTART

Siemens Industry, Inc. 12 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

Assigning a PMI button (Standard Keys) to stop the


fire control
4. Right-Click on the highlighted standard key
5. Select Assign from the drop down menu

6. Select the All activation command from the Activate/Deactivate


command category
7. Select Control and select the Fan shutdown Fire control – assign it

Siemens Industry, Inc. 13 Cerberus® PRO


Building Technologies Division Rev. 1.0 A6V10437947
Cerberus® PRO FC922 / FC924 Configuring Fan Restart

You may now download the configuration to the


panel and test the Fan Restart functionality…

Siemens Industry, Inc. 14 Cerberus® PRO