Manual Micro Compressor Controller (MCC)
Manual Micro Compressor Controller (MCC)
Operation Manual
——Editor
January, 2008
TABLE OF CONTENTS
1. GENERAL INFORMATION
Warning:
DO NOT install, operate, maintain, adjust or service Micro Compressor Controllers
without thoroughly reading this manual.
Disclaimer:
The information in this document is subject to change without notice. While Sullair
assumes and believes the information contained herein to be accurate, the company
assumes no responsibility for any errors or omissions.
Copyright notice:
No part of this document may be reproduced in any form without prior written consent of
Sullair. The software described in this document is furnished under a license and may
only be used or copied in accordance with the terms of the license.
2. SAFETY INSTRUCTION
When using air compressors and compressed air accessories, basic safety rules and
precautions must always be followed including the following:
I) Read all instructions fully.
II) Electrical Safety Precautions.
When installing, commissioning, operating or carrying out maintenance on the MCC unit, the
respective persons must use safe working practices and observe all relevant local health and
safety requirements and regulations.
Use extreme cautions when carrying out electrical checks. Isolate the power supply before
starting any maintenance work.
Do not operate the MCC unit with damaged wiring/ parts after the controller unit have been
dropped or damaged in any manner. Notify authorized service facility for examination, repair
or other adjustments.
It is not possible to anticipate every circumstance, which might represent a potential hazard. If
the user employs an operating procedure, an item of equipment or a method of working which
is not specifically recommended, the user must ensure that unit will not be damaged or made
unsafe and that there is no risk to persons or property. Failure to observe safety precautions or
implement safe working practices may be considered dangerous practice or misuse of the
product.
Page 1 of 12
Micro Compressor Controller (MCC) Operation Manual
3. INTRODUCTION
Micro Compressor Controller (Abbr. MCC) displays temperature, pressure, operation time
and working status of the compressor through 2×8 liquid crystal display (LCD).
The information can be displayed in Chinese or English or other languages (The language
requirement should be stated in sales order).Compressor information can be uploaded via
RS485 Modbus protocol.
Operator can control the compressor, set parameters and display needed parameters through
the keypad on the control panel. Indicator lights on the panel reflect the basic status of the
device (refer to Fig.1).
4. SPECIFICATION
1. Digital Inputs: Digital input 4-channel
2. Digital Output: Digital switching output 5-channel.
3. Analog Inputs: Pt1000 temperature input 1-channel; 4~20mA transferred
input 1-channel;
4. USB port for program downloads in different languages.
5. Power supply: 90-130VAC, 50/60HZ, 40mA .
6. Display ranges
a) Temperature: -20~150℃; Accuracy: ±1℃
b) Run time: 0~999999H
7. Temperature Protection: When the actual temperature is higher than the rated
allowed temperature, the function will be activated in less than 2s.
8. Output relay contactor capacity: 250VAC/5A; 500000 switching times;
9. Ambient temperature: -20°C – 65°C
Page 2 of 12
Micro Compressor Controller (MCC) Operation Manual
5. OPERATORS' INTERFACE
Fig. 1
Stop Key: Press this key to stop the compressor (when pressing this key, the
compressor immediately turns to unload mode and stops after ** seconds (which can be set in
CUSTOMER SET). If the compressor has been unloaded for ** seconds (saved number)
before pressing the key, the unit will stop immediately.)
S Set key / Load / Unload: Press this key to save modified data. When compressor is
running, press this key to send load or unload command to the compressor.
▲ Up key: Press this key to move upward (add) in data modification or move upward
scroll in menu operation.
▼ Down key: Press this key to move downward (reduce) during data modification or
downward scroll in menu operation.
► Cursor/Confirm Key: This key is treated as cursor during data modification and as
confirm key during menu selection
Return / Reset Key: Press this key to return to upper menu during the menu operation
/ long held to reset the unit current state when the compressor is stopped due to a failure.
Press this key to stop buzzing.
Page 3 of 12
Micro Compressor Controller (MCC) Operation Manual
After power on, the MCC will display the following two interfaces. Each menu lasts up to 3
seconds before turn to main interface, e.g.:
STOP
180℉ 75PSI
Press “▼” key to read the running parameters directly. For example, if pressing “▼” key
for the first time, the overall operation time displayed as bellow.
Note: The customer and factory parameters are prevented from being modified
while the unit is running or in the stop delaying period.
Navigate to the last two menus: ‘CUSTOMER SET’ and ‘FACTORY SET’ by pressing
‘▼’,or by pressing ‘▲’ on the main interface to the ‘CUSTOMER SET’ and ‘FACTORY
SET’ immediately.
CUSTOMER SET
FACTORY SET
Ö From a menu, the various items within it can be viewed by scrolling with the “▼” or
Page 4 of 12
Micro Compressor Controller (MCC) Operation Manual
“▲” key.
Ö Menus are accessed with the “►”key, pressing this key will a sub-menu is displayed will
activated that particular sub-menu:
LOAD PRESS:
006.5BAR
If the entered password is correct the parameter to be modified will return to the display and
flash.
Ö The parameter now can be modified by pressing “▼” or “▲” key.
Ö To modify another parameter within the same menu,”►” is used to move the cursor to
the next number. Press “S” key as confirmation.
Ö To modify other parameters within the same menu, scroll to the new parameter and
depress “►”key.
Ö To end the parameters modification, press “ “key to return to the main interface.
All the customer parameters have been preset by SULLAIR according to SULLAIR product
requirements.
Page 5 of 12
Micro Compressor Controller (MCC) Operation Manual
CLEAR OIL FILT 0000H Reset time after oil filter changed
CLEAR A-O SEP 0000H Reset time after oil separator changed
CLEAR AIR FILT 0000H Reset time after air filter changed
CLEAR FLUID ALM 0000H Reset time after fluid changed
CLEAR GREASE AL 0000H Reset time after grease changed
OIL FILT CHANGE 1000H Set to ‘0000H’ to disable the oil filter alarm function
A-O SEP CHANGE 4000H Set to ‘0000H’ to disable the oil separator alarm function
AIR FILT CHANGE 1000H Set to ‘0000H’ to disable the air filter alarm function
FLUID CHANGE 8000H Set to ‘0000H’ to disable the fluid alarm function
GREASE REQ 2000H Set to ‘0000H’ to disable the grease alarm function
USER PASSWORD **** To modify the customer password
If DISABLE, communication cannot work. If SEQ, multiple
COM MODE: PC machines can work in sequence mode. If PC, communicate as
slave with external equipment according to MODBUS protocol
COM ADDRESS 0001 Communication address
Master or Slave mode when there are more than one
SEQUENCE STATE MASTER
compressors running in SEQUENCE mode
SEQUENCE NO. 0004 Total number of compressors in sequence network.
During sequence control, when master pressure is lower than
SEQ LOAD PRESS ***.*BAR SEQ LOAD PRESS, and SEQ DELAY is up, the master will
find a compressor in the net to load or start.
During sequence control, when master pressure is higher than
SEQ UNLOAD PR ***.*BAR SEQ UNLOAD PR, and SEQ DELAY is up, the master will
find a loading compressor in the net to unload or stop.
During sequence control, continuously send control interval
SEQ DELAY 0015S
time.
LANGUAGE SEL CHINESE Select display languages
7. INSTALLATION
7.1CONTROLLER INSTALLATION
The controller is installed with bolts’ size 72 x 122. Certain space should be left around controller
for wiring. The specific dimensions are as follows:
Page 6 of 12
Micro Compressor Controller (MCC) Operation Manual
MOTOR OVERLOAD
E-STOP
COM 1
RS485 A
RS485 B
P
FR1
T 28
E-STOP
s
p SW1 a
1 2 3 4 5 6 7 8 9 10 11 12
MCC
POWER
AC 110V
13 15 17 18 19 20 21 22 23 24 25 26
PE
KM3 KM2
a
33 35 E-STOP
E-STOP AC 110V
YV1 KM1 KM2 KM3
26
DRAIN/ LOAD/ Main Y △
REMOTE UNLOAD
PE
Controller terminals:
Page 7 of 12
Micro Compressor Controller (MCC) Operation Manual
4 and 5 are RTD signal input; 6 is remote controlled on/off signal input terminal; 7 is PR XDCR
signal input terminal; 8 is input terminal for overheat signal of fan motor; 9 is input terminal for
emergent stop signal; 10 is common terminal for input signals; 11 is RS485 A; 12 is RS485 B;
18 is electronic drain valve/remote control (optional) output; 19 loading valve; 20 controls main
contact switch; 21 star contactor; 22 delta contactor; 23 is common terminal COM1 of output relay;
24 is the analog grounding; 25 and 26 are the AC 110V power source input.
NOTE! The magnetic coils of valves and contactor must be connected to a surge
absorber.
8. CONTROL FUNCTIONS
8.1 AUTOMATIC CONTROL – LOCAL MODE
(Load mode: Automatic On/off, local start control mode)
① MOTOR STARTING:
The controllers perform a 6 seconds self-checking after power on during which the key can
not start the machine. Starting procedure of compressor is: KM1 (Main/Line contactor) power on
Æ, Motor in Y startingÆTransition time over(Y—△ transition time) ,KM2 power off(KM2 and
KM3 interlocked)ÆMotor running in △ mode, motor starting over.
Note: All the solenoid valves are power off during the motor starting to ensure the no-load starting.
If compressor is full voltage (not Y—△) starting, power on KM1.
③ NORMAL STOPPING:
By pressing the key the load solenoids valve powers off, after certain time (STOP DELAY
TIME), all controller relays will power off, main and fan motor stop running. The compressor can
be restarted only after the restart delay time decrease to “0”.
④ ANTI-FREQUENTLY-STARTING CONTROL
The motor can not be started immediately after stopping unless after (RESTART TIME), or if the
compressor stopped after (UNLOAD RUN TIME). Whatever the situation is, the controller will
display remain time of delay (such as 90s). The motor can only be started when the delay time is
0.
8.2 AUTOMATIC CONTROL – REMOTE MODE
(Load mode: Automatic On/off, Remote start control mode)
① MOTOR STARTING:
The controller performs a 6 second self-check prior to press the ‘ ’ key to start the machine. If
“DRAIN/REMOTE” is set as remote, the No.18 terminal serves as remote control enable signal
input. After key has been pressed, the compressor can be started or stopped by controller No.
Page 8 of 12
Micro Compressor Controller (MCC) Operation Manual
6 terminal. Start signal is to be received via the No.6 terminal, the motor starts as in the local
control mode.
③ REMOTE STOPPING:
To signal a remote stop, terminals 6 and 10 must be open circuit and then the load solenoid valve
will lose power, all controller relays will lose power after the stop delay time (STOP DELAY
TIME), the main and fan motor will stop running thus remotely stopped the compressor. Only
when the restart delay time counts to “0” can the compressor be restarted remotely by remote start
signal from terminals 6 and 10. Only when user presses the local key will the remote
start/stop enable signal clear off, the compressor can not be started by remote control.
Page 9 of 12
Micro Compressor Controller (MCC) Operation Manual
In this condition check the temperature sensor to see whether wire is broken or damaged.
The relevant warning information shall popup on the screen in case of other faults.
RTD FAULT Cable off, PT1000 failure, etc Check wiring, Replace PT1000
Main contactor failure Emergency stop key wiring loose Check wiring. Check Contactor
Page 10 of 12
Micro Compressor Controller (MCC) Operation Manual
1 Read Section 1—Safety in MCC Controller User Interface Manual. Follow all safety
guidelines.
2 Disconnect incoming power.
3 Open starter enclosure door and unplug connectors from existing controller.
4 Loosen screws on installation clips and remove controller.
5 Install new controller and gasket.
6 Plug connectors into controller, close enclosure door and turn on power to machine.
7 Modify setting accordingly
8 Confirm pressure setting as follows:
ٛ a. Slowly open the shut-off valve to the service line.
ٛ b. Press the START pad to start the compressor in default mode (AUTO).
ٛ c. Check for leaks in service air piping.
ٛ d. Slowly close the service line shut-off valves to verify nameplate pressure unload setting.
The compressor should unload when nameplate pressure is achieved.
9 Adjust other customer settings (maintenance intervals, units, operating mode) as desired.
Refer to the Micro Compressor Controller Operation Manual
Section 6.4— Customer setting
Page 11 of 12
Global Sales and Service
SULLAIR EUROPE
SULLAIR ASIA
SULLAIR AUSTRALIA