Data sheet 3RW5235-6AC14

SIRIUS soft starter 200-480 V 143 A, 110-250 V AC Screw terminals


Analog output

Product brand name SIRIUS


Product category Hybrid switching devices
Product designation Soft starter
Manufacturer's article number
● of HMI module usable 3RW5980-0HS00

● of HMI-Modul high-feature usable 3RW5980-0HF00

● of communication module PROFINET standard 3RW5980-0CS00


usable
● of communication module PROFIBUS usable 3RW5980-0CP00

● of communication module Modbus TCP usable 3RW5980-0CT00

● of circuit breaker usable at 400 V 3VA2220-7MN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10

● of circuit breaker usable at 400 V at inside-delta 3VA2325-7MN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10
circuit
● of the gG fuse usable up to 690 V 3NA3244-6; Type of coordination 1, Iq = 65 kA

● of the gG fuse usable at inside-delta circuit up 3NA3244-6; Type of coordination 1, Iq = 65 kA


to 500 V
● of full range R fuse link for semiconductor 3NE1227-0; Type of coordination 2, Iq = 65 kA
protection usable up to 690 V

3RW5235-6AC14 Subject to change without notice


Page 1/8 06/29/2018 © Copyright Siemens
● of back-up R fuse link for semiconductor 3NE3334-0B; Type of coordination 2, Iq = 65 kA
protection usable up to 690 V

General technical data


Starting voltage [%] 30 ... 100 %
Start-up ramp time of soft starter 0 ... 20 s
Product component
● is supported HMI-Standard Yes
● is supported HMI-High Feature Yes
Product feature integrated bypass contact system Yes
Number of controlled phases 3
Trip class CLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Insulation voltage
● rated value 600 V
Degree of pollution 3
Impulse voltage rated value 6 kV
Blocking voltage of the thyristor maximum 1 400 V
Service factor 1
Surge voltage resistance rated value 6 kV
maximum permissible voltage for safe isolation
● between main and auxiliary circuit 600 V
Protection class IP IP00; IP20 with additional terminal covers for vertical touching
from the front
Usage category acc. to IEC 60947-4-2 AC 53a
Shock resistance 15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
Vibration resistance 15 mm to 6 Hz; 2g to 500 Hz
Reference code acc. to DIN EN 81346-2 Q
Product function
● ramp-up (soft starting) Yes
● ramp-down (soft stop) Yes
● Soft Torque Yes
● Adjustable current limitation Yes
● pump ramp down Yes
● Intrinsic device protection Yes
● motor overload protection Yes; Electronic motor overload protection
● Evaluation of thermistor motor protection No
● inside-delta circuit Yes
● Auto-reset Yes
● Manual RESET Yes
● remote reset Yes; By turning off the control supply voltage
● communication function Yes
● via software configurable Yes
● firmware update Yes

3RW5235-6AC14 Subject to change without notice


Page 2/8 06/29/2018 © Copyright Siemens
● removable terminal for control circuit Yes
● analog output Yes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High
Feature HMI)

Power Electronics
Operating current
● at 40 °C rated value 143 A
● at 50 °C rated value 128 A
● at 60 °C rated value 118 A
Operating current at inside-delta circuit
● at 40 °C rated value 248 A
● at 50 °C rated value 222 A
● at 60 °C rated value 204 A
Operating voltage
● rated value 200 ... 480 V
● at inside-delta circuit rated value 200 ... 480 V
Relative negative tolerance of the operating voltage -15 %
Relative positive tolerance of the operating voltage 10 %
Relative negative tolerance of the operating voltage -15 %
at inside-delta circuit
Relative positive tolerance of the operating voltage at 10 %
inside-delta circuit
Operating power for three-phase motors
● at 230 V at 40 °C rated value 37 kW
● at 230 V at inside-delta circuit at 40 °C rated 75 kW
value
● at 400 V at 40 °C rated value 75 kW
● at 400 V at inside-delta circuit at 40 °C rated 132 kW
value
Operating frequency 1 rated value 50 Hz
Operating frequency 2 rated value 60 Hz
Relative negative tolerance of the operating -10 %
frequency
Relative positive tolerance of the operating frequency 10 %
Adjustable motor current
● minimum 68 A
● at inside-delta circuit minimum 118 A
Minimum load [%] 15 %; Relative to smallest settable Ie
Power loss [W] for rated value of the current at AC
● at 40 °C to power-up 55 W
● at 50 °C to power-up 50 W
● at 60 °C to power-up 47 W

Control circuit/ Control

3RW5235-6AC14 Subject to change without notice


Page 3/8 06/29/2018 © Copyright Siemens
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz 110 ... 250 V
● at 60 Hz 110 ... 250 V
Relative negative tolerance of the control supply -15 %
voltage at AC at 50 Hz
Relative positive tolerance of the control supply 10 %
voltage at AC at 50 Hz
Relative negative tolerance of the control supply -15 %
voltage at AC at 60 Hz
Relative positive tolerance of the control supply 10 %
voltage at AC at 60 Hz
Control supply voltage frequency 50 ... 60 Hz
Relative negative tolerance of the control supply -10 %
voltage frequency
Relative positive tolerance of the control supply 10 %
voltage frequency
Control supply current in standby mode rated value 30 mA
Holding current in the by-pass mode operating rated 75 mA
value
Starting current at close of by-pass contact maximum 2.5 A
Inrush current peak at connect of control supply 12.2 A
voltage maximum
Duration of inrush current peak at connect of control 2.2 ms
supply voltage
Design of the overvoltage protection Varistor
Design of short-circuit protection for control circuit 4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1
miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker
(Icu= 300 A); Is not part of scope of supply

Inputs/ Outputs
Number of digital inputs 1
Number of digital outputs 3
● not parameterizable 2
Digital output version 2 normally-open contacts (NO) / 1 changeover contact (CO)
Number of inputs for thermistor connection 0
Number of analog outputs 1
Switching capacity current of the relay outputs
● at AC-15 at 250 V rated value 3 A
● at DC-13 at 24 V rated value 1 A

Installation/ mounting/ dimensions


Mounting position with vertical mounting surface +/-90° rotatable, with vertical
mounting surface +/- 22.5° tiltable to the front and back
Mounting type screw fixing
Height 306 mm

3RW5235-6AC14 Subject to change without notice


Page 4/8 06/29/2018 © Copyright Siemens
Width 185 mm
Depth 203 mm
Required spacing with side-by-side mounting
● forwards 10 mm
● Backwards 0 mm
● upwards 100 mm
● downwards 75 mm
● at the side 5 mm
Installation altitude at height above sea level 5 000 m; Derating as of 1000 m, see catalog
maximum
Weight without packaging 6.6 kg

Connections/Terminals
Type of electrical connection
● for main current circuit screw-type terminals
● for control circuit screw-type terminals
Type of connectable conductor cross-sections
● for DIN cable lug for main contacts stranded 2x (16 ... 95 mm²)
● for DIN cable lug for main contacts finely 2x (25 ... 120 mm²)
stranded
Type of connectable conductor cross-sections at
AWG conductors for control circuit
● solid 1x (20 ... 12), 2x (20 ... 14)
Wire length
● between soft starter and motor maximum 800 m
● at the digital inputs at AC maximum 100 m

Ambient conditions
Ambient temperature
● during operation -25 ... +60 °C
● during storage and transport -40 ... +80 °C
Environmental category
● during operation acc. to IEC 60721 3K6 (no ice formation, only occasional condensation), 3C3 (no
salt mist), 3S2 (sand must not get into the devices), 3M6
● during storage acc. to IEC 60721 1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand
must not get inside the devices), 1M4
● during transport acc. to IEC 60721 2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
EMC emitted interference acc. to IEC 60947-1 CISPR11, ambience A (industrial sector)

Communication/ Protocol
Communication module is supported
● PROFINET standard Yes
● Modbus TCP Yes
● PROFIBUS Yes

3RW5235-6AC14 Subject to change without notice


Page 5/8 06/29/2018 © Copyright Siemens
UL/CSA ratings
Manufacturer's article number
● of the fuse usable up to 575/600 V according to Standard fault, Iq = 10 kA
UL
Operating power [hp] for three-phase motors
● at 200/208 V at 50 °C rated value 40 hp
● at 220/230 V at 50 °C rated value 40 hp
● at 460/480 V at 50 °C rated value 100 hp
● at 200/208 V at inside-delta circuit at 50 °C 75 hp
rated value
● at 220/230 V at inside-delta circuit at 50 °C 75 hp
rated value
● at 460/480 V at inside-delta circuit at 50 °C 150 hp
rated value
Contact rating of auxiliary contacts according to UL R300-B300

General Product Approval Declaration of other


Conformity
Confirmation

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RW5235-6AC14
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RW5235-6AC14
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RW5235-6AC14
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RW5235-6AC14&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RW5235-6AC14/char
Characteristic: Installation altitude
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RW5235-6AC14&objecttype=14&gridview=view1

3RW5235-6AC14 Subject to change without notice


Page 6/8 06/29/2018 © Copyright Siemens
185

165 203

60 17 7 110

1 / L1 3 / L2 5 / L3

1
AQ I+

AQ U+

AQ-
NO

1
98
NC

96
305.6

305.6
255.6

95
289.1

225

23
BYPASSED
NO

14/
24
NO
ON/ RUN

13

2
IN

A2

A1
2

2 / T1 4 / T2 6 / T3

10

110

3RW5235-6AC14 Subject to change without notice


Page 7/8 06/29/2018 © Copyright Siemens
14/24
1/L1

3/L2

5/L3

A1

95
-Q IN

BYPASSED
ON/RUN
A2

AQ-
2/T1

4/T2

6/T3

AQ I+
96 NC
13 NO

23 NO

98 NO

AQ U+

last modified: 06/22/2018

3RW5235-6AC14 Subject to change without notice


Page 8/8 06/29/2018 © Copyright Siemens