Vista-21IP Programming Guide PDF
Vista-21IP Programming Guide PDF
VISTA-21iP / VISTA-21iPSIA
Security Systems
Programming Guide
–2–
PROGRAMMING FORM
Entries apply to the ADEMCO VISTA-21iP/VISTA-21iPSIA controls, except where noted, certain fields have special settings when used with the
VISTA-21iPSIA (indicated by V21iPSIA with heavy borders and reverse type throughout for easy identification).
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
SIA Guidelines: Notes in certain fields give instructions for programming the VISTA-21iP for False Alarm Reduction.
IMPORTANT! Make sure the Real-Time Clock is set before the end of the installation (see page 16 for procedure).
∗21 Quick Arm Enable [0,0] ∗37 Audible Exit Warning [1,1]
0 = no; 1 = yes Part. 1 Part.2 0 = no; 1 = yes (SIA Guidelines: must be enabled) Part. 1 Part. 2
∗22 RF Jam Option [0] V21iPSIA: Feature always enabled; field does not exist.
0 = unlimited sounding (bell output); 1 = one alarm sounding per zone ∗42 Secondary Phone No.
V21iPSIA: If “0” selected, “alarm sounding per zone” will be the same | | | | | | | | | | | | | | | | | | |
as the “number of reports in armed period” set in field *93 (1 if one
Enter up to 20 digits. To clear entries, press ✱41✱ or ✱42✱ respectively.
report, 2 if 2 reports, unlimited for zones in zone list 7).
NOTE: For fields *43 thru *46: Enter 0–9; #+11 for B; #+12 for C; #+13 for D;
#+14 for E; #+15 for F. Enter [✱] as the fourth digit if a 3-digit account number
∗32 Fire Alarm Sounder Timeout [0] (for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit
0 = sound stops at timeout; 1 = no timeout UL: must be “1” for fire install. account number for Nos. 0000-0999. Exit field by pressing ✱ if only 3 digits are
used. E.g., For Acct. B234, enter: #+11 + 2 + 3 + 4
∗33 Alarm Sounder (Bell) Timeout [1] ∗43 Partition 1 Primary Acct. No.
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min;
UL: For residential fire alarm installation, must be set for a | | | / | | | | | [FFFFFFFFFF] Enter 4 or 10 digits, as
minimum of 4 min (option 1); for UL Commercial Burglary chosen in *48 Report Format. See box above. To clear entries, press *43*.
installations, must be minimum 16 min (option 4)
∗44 Part. 1 Secondary Acct. No. (see field *43 for entries)
∗34 Exit Delay [60,60] | | | | | / | | | | | [FFFFFFFFFF] To clear, press *44*.
00 - 96 = 0 - 96 secs; 97 = 120 secs Part. 1 Part. 2
SIA Guidelines: minimum exit delay is 45 seconds ∗45 Partition 2 Primary Acct. No. (see field *43 for entries)
V21iPSIA: 45 - 96 = 45 - 96 secs; 97 = 120 secs | | | / | | | | | [FFFFFFFFFF] To clear, press *45*.
NOTE: Entries less than 45 will result in a 45-second delay.
∗46 Partition 2 Secondary Acct. No. (see field *43 for entries)
UL: see inst. instr. for requirements. Common zones use part. 1 delay.
| | | / | | | | | [FFFFFFFFFF] To clear, press *46*.
∗35 Entry Delay #1 [30,30] | |
Common zones use same delay as partition 1. Part. 1 Part. 2
∗47 Phone System Select [1]
00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs If Cent. Sta. is not on a WATS line: 0=Pulse Dial; 1=Tone Dial;
SIA Guidelines: minimum entry delay is 30 seconds if Cent. Sta. is on a WATS line: 2 = Pulse Dial ; 3 = Tone Dial
V21iPSIA: ∗48 Report Format [77]
30-96 = 30 - 96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
0 = 3+1, 4+1 ADEMCO L/S STANDARD primary secondary
NOTE: Entries less than 30 will result in a 30-second delay.
1 = 3+1, 4+1 RADIONICS STANDARD; 2 = 4+2 ADEMCO L/S STAND.
3 = 4+2 RADIONICS STANDARD
For UL Residential Burglary Alarm installations, must be set for a
5 = 10-digit ADEMCO CONTACT ID® REPORTING
maximum of 30 seconds; entry delay plus dial delay should not
6 = 4+2 ADEMCO EXPRESS
exceed 1 min. For UL Commercial Burglar Alarm, total entry delay
7 = 4-digit ADEMCO CONTACT ID® REPORTING
may not exceed 45 seconds.
8 = 3+1, 4+1 ADEMCO L/S EXP.; 9 = 3+1, 4+1 RADIONICS EXP.
–3–
∗49 Split/Dual Reporting [0] ∗66 Arm Away/Stay Rpt Code
0 = Standard/backup reporting only (all to primary) [0,0,0,0,0,0]
Primary Phone No. 2nd Phone No.
Away Stay Away Stay Away Stay
1 = Alarms, Restore, Cancel Others
2 = All except Open/Close, Test Open/Close, Test Part. 1 Part. 2 Common
3 = Alarms, Restore, Cancel All ∗67 RF Trans. Low Bat Report Code [00] |
4 = All except Open/Close, Test All
5 = All All UL: must be enabled if wireless devices are used
∗50 Burglary Dialer Delay [2,0] ∗68 Cancel Report Code [00] |
Delay Time: Delay Time V21iPSIA V21iPSIA: [10] Report enabled.
0 = no delay UL: must be “0” Delay Disable
1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds ∗69 Recent Closing Report Code [11] |
SIA Guidelines: delay must be minimum of 15 seconds
V21iPSIA: V21iPSIA:Always enabled.
Delay Time: 1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds Field does not apply to other controls.
Delay Disable:
RESTORE REPORT CODES (✱70 – ✱76)
0 = use delay set in entry 1
1 = dial delay disabled for zones listed in zone list 6 (use zone list 6
to enter those zones that require dial delay to be disabled;
these zones ignore the setting in entry 1)
∗70 Alarm Restore Rpt Code [0]
UL: Dial delay plus entry delay must not exceed one minute; use zone
list 6 to disable dial delay from appropriate zones, if necessary. ∗71 Trouble Restore Rpt Code [00] |
∗54 Dynamic Signaling Delay [0] ∗74 Low Bat Restore Rpt Code [00] |
Select delay from 0 to 225 secs, in 15-sec increments.
0 = no delay (both signals sent); 1 = 15 secs; 2 = 30 secs, etc. ∗75 RF Trans. Lo Bat Rst Rpt Code [00] |
NOTE: If ∗55 is set to “0,” use min. 30 sec to avoid redundant IP UL: must be enabled if wireless devices are used
report. However, this value may need to be adjusted (ex. 45 secs)
depending on the reporting environment. ∗76 Test Restore Rpt Code [00] |
For UL Burglar Alarm installations with Line Security, must be “0”
∗64 Test Report Code [00] | ∗87 Misc. Fault Delay Time [0]
Use Scheduling mode to set periodic test reports, or use the following (used with Configurable Zone Types “digit 6”)
key commands: 0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min
installer code +[#] + [0] + 0 = test report sent every 24 hours 1 = 30 seconds 7 = 3 min #+13 = 10 min
installer code +[#] + [0] + 1 = test report sent once per week 2 = 45 seconds 8 = 4 min #+14 = 12 min
installer code +[#] + [0] + 2 = test report sent every 28 day 3 = 60 seconds 9 = 5 min #+15 = 15 min
Each mode sets schedule 32 to the stated repeat option; first test report 4 = 90 seconds #+10 = 6 min
sent 12 hours after command. 5 = 2 minutes #+11 = 7 min
∗65 Open Report Code [0,0,0] UL: may only be used on non-burglar alarm/ non-fire alarm zones
when used in fire and/or UL burglar alarm installation
Part. 1 Part. 2 Common
–4–
∗88 Program Mode Lockout Options [0] ∗96, ∗97 Initialize/Reset Defaults
0 = standard *98 installer code lockout (reentry only by [∗] + [#] within This is a command, not a data field. See page 2.
50 seconds after power up)
1 = lockout [∗] + [#] reentry after *98 exit (reenter via installer code or ∗98, *99 Exit Commands
downloader only) This is a command, not a data field. See page 2.
2 = not used
3 = lockout local programming after *98 exit (reenter by downloader only) PAGER OPTIONS (✱160- ✱172)
∗89 Event Log Full Report Code [00] |
∗160 Pager 1 Phone No.
See box above field *59 for report code entries. | | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-sec pause
∗90 Event Log Enables [3]
NOTE: System messages are logged when any non-zero entry is made.
∗161 Pager 1 Characters
0 = None | | | | | | | | | | | | | | |
1 = Alarm/Alarm Restore
2 = Trouble/Trouble Restore Enter the optional prefix characters, up to 16 digits.
4 = Bypass/Bypass Restore 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
8 = Open/Close. Example: To select “Alarm/Alarm Restore”, and
“Open/Close”, enter 9 (1 + 8); To select all, enter #15. ∗162 Pager 1 Report Options [0,0,0]
–5–
∗172 Pager Delay Option For Alarms [3] KEYPAD OPTIONS *189-*196
0 = none; 1 = 1 minute; 2 = 2 minutes; 3 = 3 minutes KEYPAD NOTES:
This delay is for ALL pagers in the system. 1. Options for keypad 1, address 16 are set by the factory and cannot be
changed.
MISCELLANEOUS SYSTEM FIELDS (*174-*181) 2. Each keypad must be assigned a unique address. Keypads programmed
–6–
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182-
*185. Configurable zone types 92 and 93 can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for
zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields
*183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1 (See note 5 for RF zones) ENTRY 2 (See note 5 for RF zones) Entries for Fields *182 and *184
Response when system disarmed and zone is: Auto Entry Zone Type 90 Zone Type 91
Intact EOL Open Shorted Restore Vent Zone (field *182) (field *184)
RF zone normal RF zone N/A RF zn off-normal 1
0 = normal 0 = normal 0 = normal 0 = no 0 = no 2
1 = alarm 4 = alarm 1 = alarm 4 = yes 8 = yes 3
2 = trouble 8 = trouble 2 = trouble 4
3 = fault 12 = fault 3 = fault
see note 6 5
Entry 1 = EOL + Open Entry 2 = Short + auto restore + vent zone 6
7
ENTRY 3 (See note 5 for RF zones) ENTRY 4 (See note 5 for RF zones) 8
Response when armed STAY and zone is: Byp. when Byp. when 9
Intact EOL Open Shorted disarmed armed 10
RF zone normal RF zone N/A RF zn off-normal
0 = normal 0 = normal 0 = normal 0 = no 0 = no To calculate the value for each entry:
1 = alarm 4 = alarm 1 = alarm 4 = yes 8 = yes Simply add the values of the selected options
2 = trouble 8 = trouble 2 = trouble in each of the entry’s columns (one option per
3 = fault 12 = fault 3 = fault column). For example, to program Entry 2 for
see note 6 “alarm response to short,” “auto restore on,”
Entry 3 = EOL + Open Entry 4 = Short + byp. disarmed + byp. armed but not a “vent zone,” enter 5 (“1” for alarm
short + “4” for auto restore yes + “0” for vent
ENTRY 5 (See note 5 for RF zones) ENTRY 6 (See note 5 for RF zones) zone no).
Response when armed AWAY and zone is: Dial Delay Fault Delay
Intact EOL Open Shorted (see field *50) (see field *87)
RF zone normal RF zone N/A RF zn off-normal
0 = normal 0 = normal 0 = normal 0 = no 0 = no
1 = alarm 4 = alarm 1 = alarm 4 = use delay 8 = use delay
2 = trouble 8 = trouble 2 = trouble
3 = fault 12 = fault 3 = fault see note 1 INTACT OPEN SHORTED
EOL
see note 6 ZONE-003-V0
Entry 5 = EOL + Open Entry 6 = Short + dial delay + fault delay Zone Conditions Represented
in Entries 1-6
ENTRY 7 ENTRY 8
Display Faults Power Reset/ Use Entry Use Exit Respond as NOTES:
Verification Delay 1/2 Delay Interior Type 1. Do not use the “fault delay” option with a
0 = show alarms 0 = no 0 = no 0 = no 0 = no configurable zone type if it is set for an
when armed 4 = power reset 1 = delay 1 4 = use exit 8 = yes entry or exit delay, otherwise
& disarmed after fault 2 = delay 2 delay unpredictable results may occur.
1 = don’t show (by code + OFF) see note 2 2. To create an interior type zone, select
alarms when 12 = verification “respond as interior zone type” (entry 8,
armed (show (see zone interior type = yes), and set zone
alarms, trbles, type 16) response to “fault” in entries 3-4 to ensure
faults when fault displays; do not set as “normal,”
disarmed) “alarm,” or “trouble.”
3 = never show 3. Do not set fire zones to respond as a
any alarms, “fault” (entries 1-6), otherwise faults will
trbles, faults
not display unless the [∗] key is pressed.
Entry 7 = fault display + power Entry 8 = entry delay 1/entry delay 2 + exit delay +
reset/verification interior zone type 4. 4219/4229 modules must use EOLRs or
unpredictable results may occur.
ENTRY 9 ENTRY 10 5. RF Zones: The “open” option in entries 1,
Alarm Sounds Use Bell Respond as Trouble Chime when 3, and 5 is not applicable for RF zones.
Timeout Fire Zone Sounds Chime Mode On Use the “intact EOL” option for normal RF
0 = none 0 = no 0 = no 0 = none 0 = no zone conditions and “shorted” for off-
1 = steady 4 = yes 8 = yes 1 = periodic 4 = yes normal RF zone conditions.
keypad beep 6. a. Zone-Doubling/Double-Balanced: A
2 = steady bell see fields *32, see zone type 2 = trouble short on either zone of a zone-doubled
and keypad *33 09; see note 4 beeps pair or on a double-balanced zone
3 = pulsing bell causes a tamper condition.
and keypad b. For double-balanced zones, this entry
Entry 9 = alarm sounds + bell timeout + fire zone Entry 10 = trouble sounds + chime must be “0.”
c. For zone-doubled zones, both zones
of the doubled pair must be assigned
the same response to a short.
–7–
*56 Zone Programming Menu Mode
(press *56 while in Program mode)
The Zone Programming Worksheet is on page 18.
For each of the following prompts, make the desired entry, followed by the [∗] key to accept the entry.
Refer to the Installation and Setup Guide for detailed explanations for each prompt.
–8–
Wireless Key Programming Templates (press the [D] key from *58 Menu mode Summary Screen)
This procedure programs the wireless keys, but a key is not active for arming/disarming until it is assigned to a user number (see
System Operation section, Assigning Attributes Command in the Installation Instructions).
TEMPLATE ? ENTER START ZONE
Enter desired template number 1–6 (see chart below), then press [∗] to The system displays the lowest zone number of the highest available
continue. consecutive 4-zone group.
To exit the Template screen, press [#]. The system returns to the *58 Menu To start at a different zone number, enter the zone desired, and press [∗]. If
mode Summary Screen. the system has four consecutive zones beginning with that zone, the zone
number is displayed. If not, the system will again display a suggested zone
TEMPLATE SUMMARY that can be used.
If the required number of consecutive zones is not available at all, the
L 01 02 03 04 system will display “00”.
T 23 22 21 23
Press [∗] to accept.
The selected template is displayed. Continue to the INPUT S/N (serial number/loop number) and XMIT TO
The top line represents loop numbers, the bottom line represents each CONFIRM prompts described earlier in the *56 Menu Mode section.
loop’s zone type.
IMPORTANT: When confirmed, the key is not active for arming/disarming
Press [∗] to accept template and continue. until it is assigned to a user number (using the assigning attributes command,
PARTITION attribute “4”). See System Operation section in Installation Instructions.
Enter the partition (1, 2) in which the key is to be active. When done, the keypad beeps three times and the display returns to the
Press [∗] to continue. ENTER START ZONE prompt to let you enter the starting zone for the next
wireless key.
Wireless Key Predefined Default Templates
For 5804 Loop Function Zone Type For 5804BD Loop Function Zone Type
TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23
2 Disarm 22 2 No Response 23
3 Arm Away 21 3 Arm Away 21
4 No Response 23 4 Disarm 22
TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22
TEMPLATE 3 1 24-hour audible 7 TEMPLATE 6 1 24-hour audible 7
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22
*57 Function Key Programming (press ∗57 while in Data Programming mode)
The Function Key Worksheet is on page 19.
PRESS KEY TO PGM KEY "A" FUNC (continued)
Press the desired function key to be programmed, A-D, then press [∗] to 01 = Single-button paging (sends a 999-9999 message to pager)
continue. 02 = Display time
When done, press 0 to exit this mode and return to data field mode. 03 = Arm AWAY (reports as User 00 if closing reports are enabled)
NOTE: A key programmed as a function key is no longer available to be 04 = Arm STAY (reports as User 00 if closing reports are enabled)
used as an end-user macro key or panic key. 05 = Arm NIGHT-STAY (reports as User 00 if closing reports enabled)
06 = Step Arming (arms STAY, then NIGHT-STAY if enabled, then
PARTITION AWAY)
Enter the partition (1-3) in which this function key will be active. 07 = Output Device Command (for device programmed as system
KEY "A" FUNC operation type 66 in *80 Menu Mode)
Enter the desired function for this key: 08 = Communication Test (sends Contact ID code 601)
00 = For the Function key selected, the functions are pre-defined as 09 -12= Macro Keys 1-4 respectively (defined by [#] [6] [6] command)
follows (default):
If A selected = Zone 95 (emergency key, same as [1] [∗] pair) Press [∗] to continue; returns to key number prompt with the next function key letter
displayed.
If B selected = Zone 99 (emergency key, same as [∗] [#] pair)
If C selected = Zone 96 (emergency key, same as [3] [#] pair)
If D selected = Single-button paging (continued in next column)
–9–
∗79 Output Device Menu Mode ∗80 Menu Mode (continued)
(press ∗79 while in Programming mode)
The *79 Device Mapping Worksheet is on page 19. OUTPUT ACTION
0 = off; 1 = Close for 2 seconds; 2 = Close and Stay Closed; 3 = Continuous
ENTER OUTPUT NO. Pulse 1 sec on and 1 sec off
01-18 = relays/X-10 4 = Change Device State; 5 = Duration 1 (see data field *177); 6 = Duration
2 (see data field *177)
[∗] to continue
Press [∗] to continue.
OUT NORM LOW (appears only for triggers 17/18)
0 = no (standard default); sets the output level normally high
ENTER OUTPUT NO.
1 = yes; sets the output normally low (can be used for resetting 4-wire Enter the device output number (programmed in *79 Menu Mode) you want
smoke detectors) associated with this output.
01-16 = output no.; 17-18 = on-board triggers
[∗] to return to Output Number prompt
Press [∗] to continue.
OUTPUT TYPE
0 = delete; 1 = relay (skip to “B” prompt); 2 = Powerline Carrier device (skip
SUMMARY SCREEN
to “A” prompt) A summary screen appears showing the programmed settings.
[∗] to continue. Press [∗] to return to OUTPUT FUNCTION NUMBER prompt.
– 10 –
*82 Alpha Descriptor Programming (continued)
ADDING CUSTOM WORDS (up to 10 words)
For custom words, the keys have the following functions: 4. Repeat Step 3 to create the desired word(s). Each word can be a
maximum of 10 characters (except custom message/partition descriptor
[4] moves cursor one space to the left. word numbers 11, 12, and 13, which can be a maximum of 16 characters).
[6] moves cursor one space to the right. 5. When the word is complete, press the [8] key to save the custom word(s)
[8] saves the new word in the system's memory. in the vocabulary list and return to the “CUSTOM WORD ?” display.
6. Repeat Steps 1–5 for other custom words to be entered. To change a
1. Select Custom Word mode (enter 1) when the prompt “CUSTOM WORD ?”
custom word, just overwrite it. When all words have been programmed,
is displayed.
enter 0 at the “CUSTOM WORD ?” prompt to return to the Program
2. Enter the number (01–10, or 11, 12, 13 for partition descriptors– see Alpha prompt. Enter 0 again to exit Descriptor mode.
below) of the custom word or word string to be created, corresponding to
index numbers 245 - 254 respectively. A cursor appears at the beginning To Assign Partition/Custom Message Descriptors, use Adding Custom
of the second line. Words procedure, but: use the following word numbers in step 2:
NOTE: Custom words 8, 9, and 10 are “reminder words” that can be 11 = partition 1; 12 = partition 2; 13 = common lobby
programmed to display using Scheduling Mode.
3. Refer to the Character (ASCII) Chart on the next page.
Press [#], followed by the two-digit entry for the first letter you would like
to display (e.g., # 6 5 for “A”). The cursor moves to the right, in position
for the next character.
To delete a character, simply enter the SPACE character (#32) at the
unwanted character’s location.
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
000 (Word Space) • 057 DOOR ∗ –L– –R– –V–
–A– • 059 DOWN • 106 LAUNDRY ∗ 155 RADIO 209 VALVE
• 001 AIR • 060 DOWNSTAIRS • 107 LEFT • 156 REAR 210 VAULT
• 002 ALARM ∗ 061 DRAWER 108 LEVEL 157 RECREATION 212 VOLTAGE
004 ALLEY • 062 DRIVEWAY • 109 LIBRARY ∗ 159 REFRIGERATION –W–
005 AMBUSH • 064 DUCT • 110 LIGHT 160 RF 213 WALL
• 006 AREA –E– 111 LINE • 161 RIGHT 214 WAREHOUSE
• 007 APARTMENT • 065 EAST • 113 LIVING ∗ • 162 ROOM ∗ • 216 WEST
• 009 ATTIC ∗ 066 ELECTRIC • 114 LOADING 163 ROOF • 217 WINDOW ∗
010 AUDIO 067 EMERGENCY ∗ 115 LOCK –S– • 219 WING
–B– 068 ENTRY 116 LOOP 164 SAFE 220 WIRELESS
• 012 BABY ∗ • 069 EQUIPMENT 117 LOW 165 SCREEN –X–
• 013 BACK ∗ • 071 EXIT ∗ • 118 LOWER 166 SENSOR 222 XMITTER
• 014 BAR 072 EXTERIOR –M– • 167 SERVICE –Y–
• 016 BASEMENT ∗ –F– • 119 MACHINE • 168 SHED ∗ 223 YARD
• 017 BATHROOM ∗ • 073 FACTORY 121 MAIDS 169 SHOCK –Z–
• 018 BED 075 FAMILY 122 MAIN ∗ • 170 SHOP ∗ 224 ZONE (No.)
• 019 BEDROOM ∗ • 076 FATHERS • 123 MASTER ∗ 171 SHORT • 225 ZONE ∗
020 BELL • 077 FENCE • 125 MEDICAL ∗ • 173 SIDE ∗ • 226 0
• 021 BLOWER • 079 FIRE ∗ 126 MEDICINE 174 SKYLIGHT • 227 1
• 022 BOILER • 080 FLOOR ∗ 128 MONEY 175 SLIDING ∗ • 228 1ST ∗
023 BOTTOM 081 FLOW 129 MONITOR • 176 SMOKE ∗ • 229 2
025 BREAK 082 FOIL • 130 MOTHERS • 178 SONS • 230 2ND ∗
• 026 BUILDING • 083 FOYER • 131 MOTION ∗ • 179 SOUTH • 231 3
–C– 084 FREEZER 132 MOTOR 180 SPRINKLER • 232 3RD ∗
028 CABINET • 085 FRONT ∗ –N– • 182 STATION • 233 4
• 029 CALL –G– • 134 NORTH 184 STORE • 234 4TH
030 CAMERA • 089 GARAGE ∗ 135 NURSERY • 185 STORAGE ∗ • 235 5
031 CAR • 090 GAS –O– 186 STORY • 236 5TH
033 CASH 091 GATE • 136 OFFICE ∗ 190 SUPERVISED ∗ • 237 6
034 CCTV • 092 GLASS • 138 OPEN ∗ 191 SUPERVISION • 238 6TH
035 CEILING 093 GUEST 139 OPENING 192 SWIMMING • 239 7
036 CELLAR 094 GUN • 140 OUTSIDE 193 SWITCH • 240 7TH
• 037 CENTRAL –H– 142 OVERHEAD –T– • 241 8
038 CIRCUIT • 095 HALL ∗ –P– 194 TAMPER • 242 8TH
• 040 CLOSED ∗ • 096 HEAT 143 PAINTING 196 TELCO • 243 9
• 046 COMPUTER 098 HOLDUP • 144 PANIC ∗ 197 TELEPHONE • 244 9TH
047 CONTACT 099 HOUSE ∗ 145 PASSIVE • 199 TEMPERATURE
245 Custom Word #1
–D– 100 INFRARED • 146 PATIO ∗ 200 THERMOSTAT
246 Custom Word #2
• 048 DAUGHTERS • 101 INSIDE ∗ 147 PERIMETER • 201 TOOL
247 Custom Word #3
049 DELAYED 102 INTERIOR • 148 PHONE 202 TRANSMITTER
248 Custom Word #4
• 050 DEN ∗ 103 INTRUSION 150 POINT –U–
249 Custom Word #5
051 DESK –J– 151 POLICE ∗ • 205 UP
250 Custom Word #6
• 052 DETECTOR ∗ 104 JEWELRY 152 POOL ∗ • 206 UPPER
251 Custom Word #7
• 053 DINING ∗ –K– • 153 POWER • 207 UPSTAIRS ∗ 252 Custom Word #8
054 DISCRIMINATOR • 105 KITCHEN ∗ • 208 UTILITY ∗ 253 Custom Word #9
055 DISPLAY 254 Custom Word #10
Note: Bulleted (•) words in boldface type are those that are also available for use by the 4286 Phone Module. If using a Phone module,
and words other than these are selected for Alpha descriptors, the module will not provide annunciation of those words.
Italicized words followed by an asterisk indicate those words supported by the 6160V/6150V Voice Keypads
CHARACTER (ASCII) CHART (For Adding Custom Words)
32 (space) 41 ) 50 2 59 ; 68 D 77 M 86 V
33 ! 42 * 51 3 60 < 69 E 78 N 87 W
34 " 43 + 52 4 61 = 70 F 79 O 88 X
35 # 44 , 53 5 62 > 71 G 80 P 89 Y
36 $ 45 – 54 6 63 ? 72 H 81 Q 90 Z
37 % 46 . 55 7 64 @ 73 I 82 R
38 & 47 / 56 8 65 A 74 J 83 S
39 ' 48 0 57 9 66 B 75 K 84 T
40 ( 49 1 58 : 67 C 76 L 85 U
– 11 –
∗29 Internal Device Menu Mode
(for Programming IP and GSM Module Options) 7720P Emulation Template for Alpha Keypads
This mode is for programming the Internet connection (IP) and GSM Module
configuration, collectively referred to as the Internal Device.
NOTE: The Internal Device is automatically set to address 3 and cannot be
changed.
S T X
RJ45 Internet connection). Refer to the Registration with AlarmNet section
for procedures. SHIFT
(C) N/Y 7 INSTANT 8 CODE 9 CHIME
Normal functions: The numeric values labeled directly on the keys and
the left-hand functions shown in diagram on the ABC keys. To perform a
normal key function, simply press the desired key.
SHIFT functions: Those functions shown in diagram above the numerical
keys and the right-hand functions shown on the ABC keys. To perform a
SHIFT key function, press SHIFT key (D key), then press the desired
function key (shift function is indicated by the lit READY LED).
– 12 –
Using ∗29 Menu Mode to Program IP/GSM Options Keypad Address (for Remote Access)
This prompt appears if remote access is enabled.
Entering ∗29 Program Mode
For enhanced remote access features, choose an AUI address. If no AUI
Press ∗29 while in Data Field Programming mode. addresses are available (all four AUIs are being used), choose an available
The following prompts appear. standard keypad address (some remote access features will be unavailable).
Enable INT IP/GSM? 1, 2, 5, 6 = emulated AUI address
0 = No, not using either IP or GSM; 1 = Yes, using IP and/or GSM module 17-23 = emulated standard keypad address
[∗] to continue. NOTE: Default = 1 (IP and/or GSM) NOTE: An AUI or standard keypad address is required for remote access
purposes, but an actual AUI device or keypad is not used.
IMPORTANT: If using an external communication device, see the VISTA-GSM
Module Installation section of the Installation and Setup Guide (Inadequate Supervision
Signal Strength paragraph) for physical installation of an external The supervising station must hear from the IP/GSM at least once during the
communication device. When complete, enter 1 at this prompt and enter 1-Prog supervision period. AlarmNet transmits a communications failure alarm to the
at the next prompt. Then program and register the external device using the central station if the supervision message is not received within the period.
Installation and Setup Guide included with the external communication device. This selection sets the supervision timing for one of the following values:
Programming/Diagnostics Select if using IP and/or GSM if using IP only (not for GSM usage)
• 30 day • US UL Line (6 Min)
1= Prog (program the IP/GSM options)
• 24-hours • US UL Line (90 Sec)
2 = Diag (enter diagnostic mode)
0 = Quit; returns to data field programming mode • None (no supervision) • CN UL Line Lv1 3 (3 Min)
• CN UL Line Lv1 4 (90 Sec)
Internal Device Programming Prompts • CN UL Line Lv1 5 (75 Sec)
The keys used to select and enter options now follow 7720P keypad emulation. • 1 hour
Refer to the table on the previous page for detailed key functions. The following To scroll the choices: [∗] key scrolls forward; [backspace] key scrolls backward
is a summary: [#] to continue
[∗] = scroll the options of a particular prompt GSM Rollover Y/N
[#] = accept the entry and move to the next prompt
Appears only if IP&GSM is selected as Internal Device option.
[A] = backspace or shift-[A} for escape
[Y] = all messages (including AlarmNet network supervisory messages) are
[B] = scroll to next prompt or shift-[B] scroll to previous prompt
sent over the GSM network in the event of an Internet failure
[C] = answer No or shift-[C] answer Yes to prompt
[N] = all messages (except AlarmNet network supervisory messages) are sent
[D] = shift key
automatically over the GSM network in the event of an Internet failure
Internal Device Selection GSM 24Hr Tst Y/N
Select the type of IP and/or GSM module usage (press [∗] to scroll choices): Appears only if IP&GSM is selected as Internal Device option.
Disabled (none); IP only; GSM module only; IP & GSM [Y] = have a message sent once a day to verify GSM operation. A "secondary
[#] to continue communication path loss" message is generated if the message is not
NOTE IF USING GSM ONLY OPTION: For registration purposes, the internal successfully delivered.
device must first be set for IP & GSM (and the control must be connected to [N] = disable 24hr test
the Internet via the RJ45 connector). Follow the prompts to program
appropriate values and use the default settings for the IP specific prompts. Old Alarm Time
After the control is registered (see Registering the Control with AlarmNet The old alarm time sets how long an undeliverable alarm is retried for delivery
paragraph later in this section), return to this prompt and set for GSM only. to AlarmNet. If the message is not validated, it is retried until the old alarm time
is reached or the message is validated. The choices available are:
Multi-Mode (email reporting) • 10 Minutes • 4 Hours
This feature is available only after authorization for it is set via the web-based • 15 Minutes • 8 Hours
programming tool on the AlarmNet Direct website. • 30 Minutes • 12 Hours
Multi-mode emulates 4204 Relay Module outputs to send up to four (4204 • 1 Hour • 24 Hours
sourced) or up to eight (2-4204 sourced) reports of system events to the user via • 2 Hours
email (email address is entered at the AlarmNet Direct website). Use the To scroll the choices: [∗] key scrolls forward; [backspace] key scrolls backward
AlarmNet Direct website to customize event titles, if desired. If enabled, a multi- [#] to continue
mode address must be entered in the next prompt.
Use *79/*80 Menu modes to program each emulated output to trigger a desired IP Fault Time
system event that, upon occurrence, will be sent to the user’s email address. Appears only if IP or IP&GSM is selected as Internal Device option.
Select the desired multi mode option: 01-99 = time delay (in minutes) before the control notifies the central station that
Disabled = no email reporting of events there is a loss of contact with the network over the Ethernet (IP)
4204 Sourced = up to four types of events reported (relay numbers 1-4 report connection.
as events 1-4 respectively) 0 = no delay (valid only If using IP only)
2-4204 Sourced = up to eight types of events reported (first module’s relay Must be two (2) minutes for UL installations.
numbers 1-4 report as events 1-4 respectively; second GSM Flt Time
module’s relay numbers 1-4 report as events 5-8 respectively) Appears only if GSM or IP&GSM is selected as Internal Device option.
To scroll the choices: [∗] key scrolls forward; [backspace] key scrolls backward 01-99 = time delay (in minutes) before the control notifies the central station
[#] to continue that a loss of contact with AlarmNet network has occurred.
NOTES: 0 = no delay (valid only if using GSM only,
1. Multi-mode has not been evaluated by UL. Must be two (2) minutes for UL installations.
2. Multi-mode (email notification) is intended as a convenience for the user,
and does not replace Central Station reporting of critical events (alarms, Notify Panel Of _
troubles, etc.). Appears only if IP&GSM is selected as Internal Device option.
Select from the following choices:
Multi-Mode Address • Neither Fault
This prompt appears if Multi Mode is enabled. • Both IP and GSM must fail before fault code is sent (status code 4005
12-15 =emulated 4204 Relay Module address. displayed); panel receives primary and secondary path failure messages.
If using “2-4204-sourced,” the address of the second module is automatically No message sent if only one or the other path fails.
assigned an address one higher than the first module’s address. To scroll the choices: [∗] key scrolls forward; [backspace] key scrolls backward
NOTE: A 4204 Relay module address is required for multi-mode purposes, but [#] to continue
an actual 4204 Relay module is not used.
NOTE: IP failure will always be sent to the central station as Primary Path
Primary City ID Failure, and GSM failure will always be sent as Secondary Path Failure.
NOTE: Account information is provided by the central station administrator.
01-99 (decimal) = 2-digit primary city code IP address information prompts
The following prompts appear only if IP or IP&GSM is selected as Internal
Primary CS ID Device.
Enter the primary central station's system ID number, 01-FE (HEX) It is recommended to use dynamically allocated IP addresses, but if fixed IP
Primary Sub ID addresses are desired, contact your network administrator for the appropriate
Enter the 4-digit customer account number, 0001-9999 (decimal). information. Note that a valid IP address must be entered in each prompt before
the system continues to the next prompt. Entries cannot be left with the default
Remote Access values.
This feature is available only after authorization for it is set via the web-based
programming tool on the AlarmNet Direct website. Use DHCP
[Y] = have the IP addresses dynamically allocated (recommended), skip to
Remote Services allow the end user to access their security system from a
Review prompt.
computer via the remote services website. Most system functions can then be
[N] = use fixed IP addresses; continue with next prompt
performed.
[#] to continue
[Y] = use remote services
[N] = do not use remote services
[#] to continue
– 13 –
NIC IP Address [255.255.255.255] IP/GSM Diagnostic Commands (continued)
Enter the 4-part IP address for this device, separating each part with a space Key Prompt Function
([∗] key, displayed as periods). [#] to continue [C] Time
Mon 01 Jan 2006
Retrieves the current date and
Subnet Mask [255.255.255.255] 05:48:39 am time from the AlarmNet network
Enter the 32-bit address mask used to indicate the portion (bits) of the IP
in Greenwich Mean Time (GMT).
address that is being used for the subnet address, separating each part with a
This display confirms that the
space ([∗] key, displayed as periods). [#] to continue module is in sync with network.
Gateway IP Addr [255.255.255.255] Physical Link
Enter the 4-part IP address assigned to the Gateway, separating each part with [D] Physical Link
Only if IP or IP/GSM enabled.
a space ([∗] key, displayed as periods). If unused set to 0.0.0.0. Good/Bad Indicates whether the device has
[#] to continue detected a physical connection
DNS IP Addr [255.255.255.255] to the internet.
Enter the 4-part IP address assigned to the DNS (Domain Name System) [∗] to continue to NIC IP address.
server, separating each part with a space ([∗] key, displayed as periods). If IP Information Displays
unused set to 0.0.0.0. [#] to continue NIC IP Address
Displays the IP address
xxx.xxx.xxx.xxx assigned to this device.
Review? (and Exit ∗29 Menu mode or Reset Defaults)
[∗] to continue to subnet mask.
You can review the ∗29 Menu mode options to ensure that the correct entries
have been made. When satisfied, select [N] to exit ∗29 Menu mode. Displays the 32-bit address mask
Subnet Mask used to indicate the portion (bits)
To review prompts or exit ∗29 Menu mode: xxx.xxx.xxx.xxx
[Y] = review prompts and entries, starting with Internal Device. Use the of the IP Address that is being
up/down arrow keys to scroll through the program fields without changing used for the subnet address.
any of the values. If a value requires change, simply type in the correct [∗] to continue to gateway IP.
value. When the last field is displayed, the “REVIEW?” prompt appears. Displays the IP Address
[N] = Exit *29 menu mode and return to data field programming mode. The Gateway IP Addr assigned to the Gateway.
prompt briefly displays “DONE” before returning to data field mode xxx.xxx.xxx.xxx [∗] to continue to DNS server IP.
prompt “Enter ∗ or #.”
Displays the IP Address
[#] to accept Y or N selection (# alone exits same as N) DNS Serv IP assigned to the DNS (Domain
To reset ∗29 Menu mode defaults: xxx.xxx.xxx.xxx Name System) server.
Press [ESC] at the Review prompt to display the “Set Defaults” prompt. [∗] to continue to encryption test.
[Y] = reset ∗29 menu mode options to factory values; if selected, all
Performs a self-test of the AES
programmed ∗29 Menu mode options are reset to the factory settings Encryption Test encryption algorithm.
[N] = cancel reset defaults function AES Passed! [∗] to continue to DHCP.
Programming IP/GSM Options via AlarmNet Direct Website DHCP (Dynamic Host
To program the IP/GSM options via the AlarmNet Direct website (if you are
DHCP
OK Configuration Protocol)
already signed up for this service), go to: indicates server is performing
https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx satisfactorily.
If you are not signed up for this service, click on “Dealer Sign-Up. [∗] returns to Physical Link prompt.
Log in and follow the on-screen prompts.
Please have the following information available: PriRSSI GPRS REG GSM Status Displays
1. Primary City ID (two-digit number) [E] Only if GSM or IP/GSM enabled.
2. Primary Central Station ID (two-digit hexadecimal number)
-xxxdbm x x PriRSSI – Primary Site RSSI
3. Primary Subscriber ID (four-digit number) level in dbm
4. MAC ID and MAC CRC number (located on the outside of box and on label GPRS – GPRS Service
inside module) or MIN number of the device you are replacing availability where “x” can be:
5. Mode of operation of existing module if replacing a "C" series radio. “Y” if GPRS is available
After programming is complete, you must transfer the data to the module and the “N” if GPRS is Not available
module must be registered. Refer to the Registration section for details. REG – Registration status
from GSM module where
∗29 Menu Mode)
IP/GSM Diagnostic Commands (∗ “x” can be:
Diagnostic commands can be used to quickly view your Internet and GSM N – Not Registered
connectivity settings and options. For each command press the [shift] key and H – Registered Home
then the designated command key. For example, press [shift] then [1/A] to S – Searching
display the software revision screen. D – Registration Denied
To enter Diagnostic mode: R – Registered Roaming
1. Press ∗29 while in data field programming mode. ? – Unknown Reg. State
2. Enter “1” at the “Enable IP/GSM” prompt then press [∗]. [∗] to continue to next screen.
3. Select “2” (Diag) at the next prompt. Cntry – Country Code
4. Enter the desired command at the “Sel Key Command” prompt. Cntry Netw LAC Netw – Network Code
For subsequent commands, enter the next command at the current screen. xxx xxx xxxxx LAC – Reg. status from GSM.
To exit Diagnostic mode, press ESC (shift-[A]). [∗] to continue to next screen.
Key Prompt Function Cell – Base Station ID
Cell BaseSt Chan BaseSt – Base Station Antenna
[A] Software Revision
Internal IP/GSM "x.x.xx" indicates the installed
Xxxxx x xxx Sector
x.x.xx mm/dd/yy software Revision. Mm/dd/yy Chan – Control Channel in use
indicates month, day and year of [∗] to continue to next screen.
the revision. Secondary GSM Site RSSI level
Second Site RSSI in dbm.
[B] MAC Address
MAC xxxxxxxxxxxx “xxxxxxxxxxxx” indicates the -xxxdbm [∗] to continue to next screen.
MAC CRC yyyy IP/GSM’s unique identification
[F] Testing Gateway Network Diagnostic Test
number. Yyyy indicates the 4
Only if IP or IP/GSM enabled.
digit MAC CRC needed to enroll Redir 1 Performs a set of network
the device in dealer direct.
diagnostics that tests the
[∗] to continue to SCID. integrity of the links between the
SCID Display IP/GSM and the various
SCID xxxxx xxxxx Only if GSM or IP/GSM enabled. connection points (Redirs) to
xxxxx xxxxx Displays the identification AlarmNet.
number assigned to the SIM
[S] ECP FLT Status request
card (SCID) in this device.
OK = normal
[∗] to continue to IMEI. OK i = IP off line
IMEI Display I = IP fault reported
IMEI xxxxxxxx Only if GSM or IP/GSM enabled. g = GSM off line
Xxxxxx x Displays the identification G = GSM fault reported
number assigned to the GSM
module in this device.
[∗] returns to MAC Address.
– 14 –
IP/GSM Diagnostic Commands (continued) Registration with AlarmNet
Key Prompt Function
The control must be registered with AlarmNet before internet communication
[T] Test Msg Sent Test Alarm (via IP or GSM) can occur.
Sends a Test alarm to AlarmNet. To register, the control must be connected to the Internet.
Functional for a registered Register the control by using one of these methods:
IP/GSM only. If the device is not
Register by phone
registered, a message is
1. Call 1-800-222-6525
displayed indicating that the
You will need the following information:
command cannot be executed.
• MAC ID and MAC CRC number (found on the PCB label).
[X] Reset CPU Y/N Reset the IP/GSM. • Subscriber information (provided by the central station), including a
[N] = return to diagnostic mode city code, CSID, and a subscriber ID.
(blank screen = enter next 2. When instructed to do so, triple-click the Test switch to complete the
command or escape). registration.
[Y] = resets the module (blank
screen = when reset Register with Alpha Keypad using *29 Menu mode
complete, enter next 1. Enter *29 Menu mode, select Diagnostic mode, then press Shift then [↑]
command or escape). key (D key followed by the B key). The registration message is sent
(“Registering” displayed) and the control waits for the acknowledgment.
↑]
[↑ Registration (Shift-UP 2. “Registration SUCCESS” displayed, indicating successful registration.
Registering … arrow)
Registers a programmed Register with Test Switch on control’s PCB (triple-click)
IP/GSM with AlarmNet. If it is 1. Click the switch three times.
configured to report to AlarmNet, 2. Watch the GSM Status LEDs: The Message (yellow) LED and the
the IP/GSM will register with Status (green) LED will blink slowly in unison while registration is in
AlarmNet. progress.
3. When registration is complete, the Status (green) LED goes out.
↓]
[↓ Enter PIN# Registration with PIN for
Replacement Module (DN Register with AlarmNet Direct Website
To register via AlarmNet Direct Website, please go to:
arrow) https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx.
Registers a programmed
IP/GSM with AlarmNet if it is Log in and follow the on-screen prompts.
configured to report to AlarmNet. Please have the following information available:
[0] Force Upload of • Primary City ID (two-digit number provided by central station)
Force Server Update
Configuration File to Server • Primary Central Station ID (two-digit hexadecimal number provided by
Y/N central station)
[Y] = force the device to upload
its entire configuration file • Primary Subscriber ID (four-digit number provided by central station)
to the server. • MAC ID and MAC CRC number (located on outside of box and on label
[N] = cancel the operation. on control’s PC board).
NOTE: If the internet is not If you are not signed up for this service, click on “Dealer Signup” from the
available, and the module is not login screen to gain access to the Honeywell web-based programming.
initialized when you enter this Dealer Sign-Up Direct Link:
command, the following screen
https://services.alarmnet.com/AlarmNetDirectP_Sign-Up.
will be displayed:
Cannot Upload You will be instructed how to proceed upon completing the sign-up form.
Try Later! _ Only one sign-up per dealer is required. Once an initial user is established,
Wait for the RSSI LEDs to light, additional logins may be created by that user.
indicating initialization is Once the control is registered, you may log out of the AlarmNet Direct
complete, and try again. website.
– 15 –
Setting Schedules (Installer Code + [#] + [6] [4])
NOTES: GROUP NUMBER ( for event 2 user access)
• The master code can only access schedules 01-16 and events 00-07. 1-8; [∗] to continue.
• System clock must be set before schedules can be used. PARTITION ( for events 3-7,10,12)
• Programmed schedules do not take effect until the next scheduled “start” 0 = all partitions; 1 = partition 1; 2 = partition 2; 3 = common
time. (e.g., if programming a schedule time window for 8AM to 5PM, the [∗] to continue.
schedule does not take effect until 8AM after the schedule has been
programmed.) START
01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; to select days, position the
ENTER SCHED NO. cursor under the desired days using the [∗] key to move forward, then press
01-16 = end-user schedules; 17-32 = installer-only schedules “1” to select the day.
[∗] to continue. [∗] to continue.
To Quit, enter 00.
STOP (for events 1 relay on/off; 2 user access; 3 latch key report)
ENTER EVENT
See START for entries. [∗] to continue.
00 = clear event
01 = Relay On/Off REPEAT
02 = User Access 0 = do not repeat; 1 = repeat schedule weekly; 2 = repeat schedule biweekly
03 = Latch Key Report to Pager (sent to all pagers in the user’s partition; (every other week); 3 = repeat schedule every third week; 4 = repeat
message sent is 777-7777. User must be enabled for paging and schedule every fourth week (28 days)
system must be armed before reporting can occur.) [∗] to continue
04 = Forced Stay Arming (Forced bypass is automatically enabled
regardless of setting in field *23) RANDOMIZE (for events 01 and 11)
05 = Forced Away Arming (Forced bypass is automatically enabled 0 = no; 1 = yes
regardless of setting in field *23) If selected, the scheduled start and stop times will vary within 60 minutes of
06 = Auto Disarm the “hour” time. For example, if a schedule is set to start at 6:15pm, it will do
07 = Display “Reminder” so the first time 6:15pm arrives, but on subsequent days it will start anytime
10 = Display custom words (if selected, system displays custom words 8, 9, between 6:00 and 6:59 p.m.
and 10 at defined time. Can be used as installer’s reminder message NOTE: Do not use the random option if the start and stop times are within
to the end user); programmable by installer only the same “hour” setting, otherwise unpredictable results may occur (e.g., the
11 = Periodic Test Report (see key commands in Test Report Code, data randomized stop time may occur before the start time).
field *64, to quickly set periodic test reporting intervals); programmable [∗] to continue and return to ENTER SCHED NO. prompt to program the
by installer only next schedule.
[∗] to continue.
DEVICE NUMBER ( for event 1 relay on/off)
01-18; [∗] to continue.
– 16 –
SCHEDULES WORKSHEET(installer code + [#] + [6] [4]; master code can only access schedules 01-16 and events 00-07
No. Event Device No. Group No. Partition Start Time/ Stop Time/ Repeat Random
(see list below) for “01” events: for “02” events: for “04-06” events: Days Days (1-4) (yes/no)
enter 01-18 enter 1-8 enter 1, 2, or 3
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Events: Master/Installer Installer Only
00 = clear event 04 = forced STAY arm 10 = display custom words 8-10
01 = device on/off 05 = forced AWAY arm 11 = periodic test report
02 = user access 06 = auto disarm
03 = latch key report 07 = display “reminder”
Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourth week (28 days)
– 17 –
*56 ZONE PROGRAMMING WORKSHEET [default shown in brackets]
Zone Zn Type Part. Report Hardwire Rsp. Time Location
Type
1 [09] [1] [EOL] [1]
2 [01] [1] [EOL] [1]
3 [03] [1] [EOL] [1]
4 [03] [1] [EOL] [1]
5 [03] [1] [EOL] [1]
6 [03] [1] [EOL] [1]
7 [03] [1] [EOL] [1]
8 [03] [1] [EOL] [1]
Zone Zn Type Part. Report Input Type Loop Serial No. Location
9 [1] [RF]
10 [1] [RF]
11 [1] [RF]
12 [1] [RF]
13 [1] [RF]
14 [1] [RF]
15 [1] [RF]
16 [1] [RF]
17 [1] [RF]
18 [1] [RF]
19 [1] [RF]
20 [1] [RF]
21 [1] [RF]
22 [1] [RF]
NOTES: 23 [1] [RF]
Zone Type: see chart in 24 [1] [RF]
∗56 Zone Programming 25 [1] [RF]
Menu mode section. 26 [1] [RF]
Report Code: enabled if 27 [1] [RF]
any digit entered as 1st 28 [1] [RF]
digit; 29 [1] [RF]
Hardwire Type (zns 2-8): 30 [1] [RF]
0 = EOL 3 = ZD 31 [1] [RF]
1 = NC 4 = DB
32 [1] [RF]
2 = NO
33 [1] [RF]
Input Type: 34 [1] [RF]
2 = AW (zones 9-48)
3 = RF (zones 9-48) 35 [1] [RF]
4 = UR (zones 9-48) 36 [1] [RF]
5 = BR (zones 49-64) 37 [1] [RF]
NOTE: Zones 9-16 not 38 [1] [RF]
available if zone
doubling enabled. 39 [1] [RF]
40 [1] [RF]
Response Time:
41 [1] [RF]
0 = 10msec
1 = 350msec 42 [1] [RF]
2 = 700msec 43 [1] [RF]
3 = 1.2 sec 44 [1] [RF]
45 [1] [RF]
Reserved Zones 46 [1] [RF]
91 = addressable device 47 [1] [RF]
report enable/disable 48 [1] [RF]
default zone type = 49 [1] [BR]
[05].
50 [1] [BR]
92 = Duress report 51 [1] [BR]
enable/disable [1] [BR]
52
53 [1] [BR]
54 [1] [BR]
55 [1] [BR]
56 [1] [BR]
57 [1] [BR]
58 [1] [BR]
59 [1] [BR]
60 [1] [BR]
61 [1] [BR]
62 [1] [BR]
63 [1] [BR]
64 [1] [BR]
95 [00] N/A** N/A N/A N/A keypad [1] / [∗]
96 [00] N/A** N/A N/A N/A keypad [3] / [#]
99 [06] N/A** N/A N/A N/A keypad [∗] / [#]
** Emergency key zones 95, 96, and 99 report the partition of the keypad used to activate the emergency zones.
– 18 –
*57 FUNCTION KEY WORKSHEET
A B C D Comments
Option Function P1 P2 com P1 P2 com P1 P2 com P1 P2 com
01 Paging
02 Time Display
03 Arm AWAY
04 Arm STAY
05 Arm NIGHT-STAY
06 Step Arming
07 Device Activation Device:
08 Comm. Test
09 Macro Key 1 Assign each macro key to only a single partition. †
10 Macro Key 2 Assign each macro key to only a single partition. †
11 Macro Key 3 Assign each macro key to only a single partition. †
12 Macro Key 4 Assign each macro key to only a single partition. †
00 Emergency Keys: zone 95 zone 99 zone 96 paging
Personal Emergency n/a
Silent Alarm n/a
Audible Alarm n/a
Fire n/a
Emergency Keys: A = paired keys [1] / [∗] (zone 95); B = paired keys [∗] / [#] (zone 99); C = paired keys [3] / [#] (zone 96)
† There are only four macros system-wide.
OUTPUT RELAYS/POWERLINE CARRIER (X-10) DEVICES WORKSHEET FOR ∗79, ∗80 and ∗81.
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
∗79 RELAY/POWERLINE CARRIER (X-10) DEVICE MAPPING (Must program before using *80)
OUTPUT TYPE OUTPUT TYPE
Relay X10 Relay X10
Output Module Pos Unit Output Module Pos Unit
No. Addr. (1-4) No. Description No. Addr. (1-4) No. Description
01 09
02 10
03 11
04 12
05 13
06 14
07 15
08 16
17 On-Board Trigger 1 norm output =
18 On-Board Trigger 2 norm output =
– 19 –
✱80 OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
Notes: 1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
2. For Powerline Carrier devices (plcd), field ✱27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Output Activation Type and Detail Partition Event (for zone list/activated by) Action Output Device
Function Activated by Zone List Zone Type Zone No. Number By Zone List By Zone No. 0 = off Number Type
Number 0=delete (ZL) (ZT) (ZN) (P) 1 = close 2 secs
(1-48) 1=zn list 1-8 = list (see table 00=none (if using ZT trig) 0 = restore 0 = restore 2 = stay closed 1-18 R = relay
2=zn type below) 01-64 0 = any 1 = alarm 1 = alrm/flt/trbl 3 = pulse T = trigger
3=zn no. 1 = partition 1 2 = fault 4 = toggle X = X10
2 = partition 2 3 = trouble 5 = duration 1††
3 = common 6 = duration 2††
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
– 20 –
5800 Series Transmitter Input Loop Identification
All of the transmitters illustrated have one or more unique factory assigned input (loop) ID numbers. Each of the inputs requires its own
programming zone (e.g., a 5804's four inputs require four programming zones).
For information on any transmitter not shown, refer to the instructions accompanying that transmitter for details regarding loop numbers, etc.
UL NOTE: The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP,
5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.
LOOP 3
LOOP 4
YOU MUST
ENROLL LOOP 2
THIS LOOP 1
LOOP BUTTON
1 LOOP 1
LOOP 1
LOOP LOOP 1
1
LOOP 3
LOOP 2 SERIAL #1
LOOP 4 LOOP 3
YOU MUST ON LOOP 4 SERIAL #1
ENROLL
OFF
LOOP 2 YOU MUST ON
OF LOOP 2 LOOP 1 LOOP 1
F
THIS LOOP 1 ENROLL SERIAL #1 1
2
•• •
LOOP 3
•
••• ••••
••
• •• LOOP 1 SERIAL #2
LOOP 2
SERIAL #2 - LOOP 1 = ON + 4 BUTTONS
LOOP 4 = 3 + 4 BUTTONS
5802 MN2 5804/5804E 5 8 0 4 B D / 5 8 0 4 B DV 5805-6 5806/5806W3 5809
ENROLL AS ENROLL AS "BR" ENROLL AS "BR" ENROLL AS "BR" 5808/5808LST/5808W3 ENROLL AS "RF"
"UR" OR "RF" SET HOUSE ID ENROLL AS "RF"
LOOP 2
(REED) LOOP 1
LOOP 2 (PRIMARY)
LOOP 1 (REED) LOOP 1
LOOP 2 LOOP 2 LOOP 2
(TERMINALS) (REED)
(REED) LOOP 1 (AUX.
(TERMINALS) LOOP 1 CENTER)
LOOP 1
(TERMINALS)
ALTERNATE LOOP 3
POSITION FOR (AUX.
LOOP 2 RIGHT)
LOOP 2 LOOP 2
(REED) (REED) AR
ME
D
RE
AD
Y
SERIAL #1
LOOP 3
AW
AY SERIAL #1
SERIAL #1 ST
AY LOOP 2
LOOP 4 1
2
LOOP 1 LOOP 1
SERIAL #1 (MOTION) LOOP 1
SERIAL #2 3
4 LOOP 1
LOOP 3
SERIAL #2
LOOP 2
SERIAL #2 - LOOP 1 = ON + 4 BUTTONS
LOOP 4 = 3 + 4 BUTTONS
– 21 –
UL NOTICES
1. Entry Delay No. 1 and No. 2 (fields ∗35, ∗36) cannot be greater than 30 seconds for UL Residential Burglar Alarm
installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm
installations, total entry delay may not exceed 45 seconds.
2. For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line security, total exit delay
time must not exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit delay time
must not exceed 120 seconds.
3. The maximum number of reports per armed period (field ∗93) must be set to “0” (unlimited) for UL installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA
max.).
6. All partitions must be owned and managed by the same person(s).
7. All partitions must be part of one building at one street address.
8. If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9. For UL commercial burglar alarm installations the control unit must be protected from unauthorized access. The
tamper switch installed to protect the control unit enclosure door is suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended downloading) is not permissible
for UL installations.
11. Auto-disarming is not a UL Listed feature.
12. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential
applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote
monitoring location, or to delay the energizing of a local alarm sounding device to permit the alarm system user to
enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
13. This control is not intended for bank safe and vault applications.
– 22 –
– NOTES –
– 23 –
IP (WEB) GRN ETHERNET LINK/ACTIVITY (ON=YES; OFF=NO) FOR COMPLETE
TO INTERNET RJ45 GSM MODULE (OPTIONAL)
NETWORK GRN LINK SPEED (ON=100 MB/S; OFF=10 MB/S) INFORMATION,
CONNECTION CONNECTOR
LEDs YEL NETWORK COLLISION (BLINK=DETECTED; OFF= NORMAL) SEE INSTRUCTIONS
K14488 OR LATER. CAUTION: ESD SENSITIVE DEVICE
24-HR BATTERY STANDBY REQUIRED FOR IP/GSM STATUS LEDs To guard against static discharge damage while installing this module, briefly touch
FIRE INSTALLATIONS. USE 12V, 17.2AH ALL DEVICES AND
+12 AUX
GND
OUTPUT 18
(TRIG. 2)
OUTPUT 17
(TRIG. 1)
CHARGING CURRENT 650mA. 3A
USE SAME VALUE TEST STATUS RSSI YEL MODE 1
OFF = ECP MODE
SEALED LEAD-ACID TYPE. (e.g. ADEMCO No. 90-12) LED MINIMUM YEL MODE 2
BATTERY NORMALLY NEED NOT BE INDICATOR LIT GRN WEB OFF = NO WEB CONNECTION; ON = CONNECTED TO WEB
REPLACED FOR AT LEAST 3 YRS. RED JUMPER 12 3 4 5 6 7 8
BATTERY GRN GPRS OFF = NO GPRS SERVICE; FLASH = GPRS IN USE; ON = GPRS AVAILABLE
RED CUT FOR BELL SUPERVISION. 8-PIN CONNECTOR
12V, 4AH FOR 1361X10 TRANS. GRN GSM OFF = NOT REGISTERED w/CARRIER; BLINK/ON = REGISTERED w/NETWORK CARRIER
TO DETERMINE TOTAL STANDBY LOAD ALSO, CONNECT 2000 OHM
(FLYING LEADS FOR
ÊK14488PRV14Š
ON BATTERY, ADD 100mA TO TOTAL OF BLACK RESISTOR DIRECTLY ACROSS AND ON-BOARD TRIGGERS SIGNAL STRENGTH
BATTERY CONNECTION) AND STATUS LEDs
AUX. POWER OUTPUT AND REMOTE SOUNDER. SEE INSTRUCTIONS.
KEYPAD CURRENTS.
AC AC BELL GND AUX GRN YEL Z1+ Z1- GND Z2 Z3 GND Z4 Z5 GND Z6 Z7 GND Z8 TIP RING TIP RING GND
USE UL LISTED LIMITED ENERGY
CABLE FOR ALL CONNECTIONS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
USE 1361X10 TRANSFORMER INTERFACE
IN PLACE OF 1361 OR 1361CN WHEN POWER
LINE CARRIER DEVICES ARE BEING USED.
LO
HI
LO
LO
HI
HI
HI
HI
HI
LO
HI
HI
LO
LO
LO
LO
}
(e.g. ADEMCO No. 1361)
(USE No. 1361CN IN CANADA) AUX. POWER TELEPHONE WIRING GROUND
OUTPUT SEE
(VIA RJ31X* JACK AND DIRECT
10.5-13.8VDC INSTRUCTIONS
TO 110VAC CONNECT CORD)
600mA MAX. FOR PROPER
UNSWITCHED OUTLET (24HR) GROUNDING
(500mA MAX. *CA38A IN CANADA DOC LOAD NO.: 3
FOR UL
THIS EQUIPMENT SHOULD BE INSTALLED IN INSTALLATIONS) FOR CONNECTION OF OPTIONAL 4286 VIP MODULES
ACCORDANCE WITH THE NATIONAL FIRE TO PHONE TERMINALS, SEE INSTRUCTIONS.
ZONE 7
ZONE 8
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
BLK
RED: KEYPAD PWR ( + )
TESTING, MAINTENANCE, EVACUATION CURRENT (IN BOTH • MAX LOOP RESISTANCE: (EACH ZONE) 300 OHMS
www.honeywell.com/security
10.5–13.8VDC, 2A MAX. (600mA
4-WIRE SMOKE DETECTOR CONNECTIONS