Ijeev5n5 01 PDF
Ijeev5n5 01 PDF
Abstract
With the introduction of availability based tariff in the open access power
transfer regime, utilities may derive benefit by proper coordination of Loss of
Excitation (LOE) Relay with Generator Capability Curve (GCC) and Steady
State Stability Limit (SSSL). The co-ordinated operation of protection and
excitation may extend the time of availability of the generator during some of
the system disturbances, without jeopardizing the generator and system health.
In this work an algorithm has been developed which specifically ensures the
coordination of LOE relays with generator full load capability and machine
steady state stability limits during normal & abnormal conditions by adopting
specific calculation methods. Modeling has been done in PSCAD/EMTDC
software to check the required coordination of the relay on a large alternator.
Introduction
A protection scheme in a power system is designed to protect the power system and
its apparatus to ensure maximum continuity of electrical supply with minimum
damage to life and equipments. Stable operation of power system requires continuous
matching between energy supply to prime mover and the electrical load on the system
and an adequate reactive power support mechanism to maintain voltage within limit at
different buses. Performance of excitation system is very important during a
disturbance as it acts to maintain system stability. The excitation limit determines the
steady state stability characteristic of the generator. If the excitation is not sufficient to
provide the vast demand of the generator, then the stability limit is exceeded. Our
objective is to keep the generator online for an optimizing time without infringing on
the system stability limits and at the same time without compromising the health of
the generator.
Generator Capability
Synchronous generators have the capability of generating (overexcited generator) or
absorbing (under excited generator) power. The capability curve [1] establishes the
steady state (continuous) generator operating limits of generator. The generator
capability curve is normally published at generator rated voltage.The generator
capability is a composite of three different curves: the stator winding limit, the rotor
heating limit and the stator end iron limit. GCC depends upon Generator excitation
voltages, coolant pressure, turns in the armature & field windings.
There are varieties of controls like Automatic Voltage Regulator (AVR), which
may operate manually or automatics. All the automatic control modes may have
supplementary controls Minimum Excitation Limiter (MEL), over excitation limiter
(OEL) etc.
Coordination of Loss of Excitation with Capability Curve 503
This supplementary control may ensure that the generator is always operated
within capability limit. The main duty of the limiters is to keep the synchronous
machine operating within the safe and stable operation limits, avoiding the action of
protection devices that may trip the unit. Also the purpose of the work is to maximize
the time operation of the generator during Loss of excitation (LOE) within its
capability limit without infringes on the system stability.
Brief Background
Earlier work has been done in [1] to describe traditional protection function related to
the Capability curve, such as stator thermal, rotor thermal, motoring, over voltage,
under voltage and loss of field protection. The paper by Mozina [2] provided practical
guidance about proper coordination of generator protection and generator AVR
control to enhance security and system stability. The paper by Benmouyal [3] proved
the impact of the excitation system with an AVR or a power system stabilizer (PSS)
on the generator stability limits. The paper by ZHANPENG [4] analyzed the
generator loss of excitation fault and described an investigation on existing loss of
excitation protection schemes. The paper by Berube [5] presented a brief review of
the experience and perspective of a large Canadian utility with Under Excitation
Limiters (UELS). The paper by Hurley [6] presented Under Excitation Limiter (UEL)
models which can be applied to the excitation system models of synchronous
machines. The paper by Seba [7] provided UEL control effect on dynamic behavior of
synchronous generators in a Power System. Another work by an IEEE group [8]
presented Computer Models for representation of newer digital-based excitation
systems in transient stability programs.
A Theoretical Understanding
Generator Capability Curve
Synchronous generators have the capability of generating (overexcited generator) or
absorbing (under excited generator) power. The capability curve [1] establishes the
steady state (continuous) generator operating limits of generator. The generator
capability curve (GCC) is normally obtained at generator rated voltage. The generator
capability is a composite of three different curves (Fig.1): the armature current limit,
the rotor current limit and the stator end region heating limit. GCC depends upon
Generator excitation voltages, coolant pressure, turns in the armature & field
windings, altogether described in Fig.1 & Fig.2.
504 Madhurri Kanjilal et al
Fig.5 shows the SSSL L of both a salient pole and round rotor geneerators [3] with
the indicated characteristics. Difference between the two curves lies only
o in the area
close to the Q-axis where the point of intersection is at point 1/Xq for the salient pole
generator rather than 1/XXd for the round-rotor generator. Thereforee the difference
between the two SSSL curves
c should be considered as negligible forf all practical
purposes.
506 Madhurri Kanjilal et al
The increase in the exttent of shaded portion of the Relay operating zone highlights
the vulnerability of the sysstem with a weak Xs as shown in the fig.
As stated previously, three factors may limit the capability of a synchronous
generator to operate in thee under excited region.
In this region, core-ennd heating, power-system stability or allow wable operating
voltage limit to the generaator capability to absorb reactive power.
Figure 8: Loss of field eleement characteristics in the P-Q plane set to coordinate with
the Generator capability curve
c when the SSSL characteristics is outsidde the capability
curve
Figure 9: Loss of field eleement characteristics in the P-Q plane set to coordinate with
the SSSL when the SSSL characteristics is inside the capability curve
508 Madhurri Kanjilal et al
be properly coordinated with Generator capability curve (GCC) and Steady State
Stability Limit (SSSL) for a loss of excitation unit in a large alternator.
The field voltage fromm excitatory is made zero after 20th second of steady state
operation with the help off a timer circuit. The fig15.1 shows the field voltage
v becomes
th
zero instantly at 20 seccond. The fig15.2 shows that the field cuurrent decreases
exponentially according too field time constant.
When loss of excitattion occurs, the terminal voltage starts to decrease. The
terminal voltage is relateed to reactive power delivered which in tuurn depends on
excitation (Fig.15.4). As excitation
e is lost the reactive decreases to zeero and become
negative and hence it draw
ws huge reactive power from system or nearbyy generator (i.e.
the direction of reactive power
p reverses.) to maintain its excitation. If
I the system is
not able to supply sufficcient reactive, the voltage reduced to a veery small value
causing voltage collapse. Large amount of reactive power causes Higgh stator current
to flow which in turn heaats up the stator winding and stator end iron heating. In this
case voltage reduced fromm 19.75 kV to 8.75 kV as shown in Fig.15.3.
The active power outpput decreases to a very small value as the exciitations reduced
and there is no other generator to support the excitation instantly exccept the system
bus. The electrical output decreases from 434MW to 50 MW during looss of excitation
period as shown in Fig.115.5 and the load angle increases from 0.388 radian to 0.8
radian at rated load as shhown in Fig.15.6. If load is decreases to sm mall value both
active power output increaases to 458Mw and load angle increases to 0.77rad.
Fig.17 shows the P-Q Q operating point falls below the SSSL under u dynamic
condition of system voltagge and reactance when the unit losses excitaation because of
field supply reduced to zerro instantaneously.
Figure 18:: Dynamic threee Dimensional Views of Active and Reactiive Power with
Voltage and Time during Loss
L of Excitation.
Fig.18 shows Dynamicc three dimensional views of p-q locus with Voltage
V & Time
during Loss of Excitation through MATLAB simulation. The red curvve & blue curve
show dynamic three diimensional views of Active & Reactivee Power locus
respectively with Voltage & Time during Loss of Excitation.
Coordination of Loss of Exxcitation with Capability Curve 517
Figure 19: Three Dimensional Views of P-Q Operating Point and SSS
SL with varying
Voltage.
Conclusions
Major generator tripping events are not as rare as many people believve. Should they
occur, such events can bee very disruptive and costly to the utility pow wer production.
Delays in determining thee cause of the disruption and in assessing equuipment damage
can add hours to reenergizzing and returning to normal operations.
There are many advaantages of this Co-ordination [1] Process:-(ii) Reduction of
loss of revenue due to redduction in power transfer. (ii)Improve reliabillity of generator
VAR support to system. (iii)
( Reduction of transmission line overload.. (iv) Reduction
of unnecessary tripping off breaker and other equipments operation. (vv) Reduction of
likelihood of islanded syystem condition. (vi) Increased confidencee in results of
planning studies.
The LOE condition enntails a check for both the generator capabilitty as well as the
system network to whichh the generator is connected. The fullest uttilization of the
generator capability withinn the SSSL of the power system is targeted before
b going for
tripping.
Our work depicted thee method to establish an optimum utilization of o the generator
capability without infringging on the stability limit. With the development of this
intelligent system, on line monitoring of the SSSL points and GCC C may be made
possible with the integratioon of adaptive feature in the LOE relay.
518 Madhuri Kanjilal et al
References
[1] Ramon Sandoval, “Dynamic Simulations Help Improve Generator Protection”,
IEEE power system conference, march-2007, pp 16-38.
[2] C.J. Mozina, “Coordination of generator protection with generator excitation
control and generator capability”. Working Group J-5 of the Rotating
Machinery Subcommittee, Power System Relay Committee, vol-15.no.-3 IEEE
Power engineering society general meeting, 2007, PP1-17.
[3] Gabriel Benmouyal, “The Impact of Synchronous Generators Excitation
Supply on Protection and Relays”, Schweitzer Engineering Laboratories,
Inc.2007, pp1-16.
[4] ZHANPENG SHI. “Investigation on Generator Loss of Excitation Protection in
Generator Protection Coordination”, Master Thesis, School of Electrical
Engineering, Royal Institute of Technology Stockholm, Sweden 2010.
[5] G. Roger Berube, “A Utility Perspective on Under-Excitation Limiters”, Vol-
10, No-3, sep-1995, pp 532-537.
[6] J. D. Hurley, “Under excitation Limiter Models for Power System Stability
Studies”, IEEE Transaction on energy conversion, Vol-10, No. 3, sep. 1995, pp
524-531.
[7] Seba Stieo, “Impact of Under excitation limit control on power system dynamic
performance”, IEEE Transactions on power system, Vol.10, No. 4, Nov.1996.
[8] “Computer Models for Representation of Digital-Based Excitation Systems”, a
paper prepared by the Digital Excitation Task Force of the Equipment Working
Group. IEEE Transactions on Energy Conversion, Vol. 11, No. 3, September
1996, pp607-613.
Appendix A
Source of System
System data
Positive sequence impedance:
Zmin = 0.00105 + j0.016463 pu (138KV, 100 MVA)
Zmax = 0.000511 + j0.010033 pu (138KV, 100 MVA)
System voltage = 138 KV, (L, L)
System frequency = 60 HZ
Generator Data
Rated MVA = 492 MVA
Rated voltage = 20 KV
Xd = 1.18878 pu
Xq = 0.146 pu
Xd’= 0.20577 pu
Tdo’= 5.2 s
Transformer Data
Rated MVA = 425 MVA
Coordination of Loss of Excitation with Capability Curve 519
AC1A Exciter
Rated feedback Gain (KF) = 0.03 pu
Rated feedback Time constant (TF) = 1.0 s
Infinite Bus Data
Base voltage = 138KV
Base MVA = 100 MVA
Frequency = 60 HZ
Timer
Duration on = 20 s
Appendix B
Mathematical Models used in flowchart
The equation representing SSSL circle as shown in Fig.4
P2 + (Q – q (i)) 2 = B1 (i) 2 ….eqn. (B.1)
Where q (i) is the coordinate of the center A1 (i) on the Q-axis at ith instant,
where the centre
A1 (i) = (0, q (i))…eqn. (B.2)
Where f1 (i) represents a point on the SSSL when P=P (i) and Q=Q (i) and system
reactance = X (i).Vt (i) is the terminal voltage at the ith instant.
To test the points P(i) &Q(i) on the B(i) curve representing the SSSL curve at the
ith instant the following equation is used.
B1 (i) 2-f1 (i) < … eqn. (B.6)
A separate LOE locus is not maintained. It is the difference (Eta) with the SSSL
at respective instants that determines the LOE status. If the difference is negative, it
indicates the point f1 (i) is outside the stability limit, then instant tripping initiated.
This criterion checks whether the measured P-Q has crossed the SSSL point at
that instant.
Where is small margin which 3% of rated MVA of generator.
To determine a point on GCC the following equation are used
520 Madhuri Kanjilal et al
f2 (i) represents the value of armature current limit at ith instant when P=P (i) and
Q=Q (i)
To test the points P(i) &Q(i) on the B(i) curve representing the GCC curve at the
ith instant the following equation is used.
B22-f2 (i) < … eqn. (B.10)
Likewise as in the previous, a separate LOE locus is not maintained. The equation
(B.10) checks whether the measured P-Q falls on armature current limit.
Where K1=0.3 & Vt (i) is the terminal voltage at the ith instant. And the radius of
the curve CD as in fig.1
B3 (i) =K2* …. eqn. (B.12)
Where K2 =1.3
Here the constants K1and K2 are assumed for temperature rise in field and
armature winding.
Then f3 (i) represents stator end iron heating limit point at ith instant when P=P (i)
and Q=Q (i).To test the points P(i) &Q(i) on the B(i) curve representing the GCC
curve at the ith instant the following equation is used.
Coordination of Loss of Excitation with Capability Curve 521
Likewise as in the previous, a separate LOE locus is not maintained. The equation
(B.16) checks whether the P-Q operating point crosses the stator end iron heating
curve.
Then f4 (i) represents the operating point at ith instant of time when P=P (i) and
Q=Q (i). Vt (i) is the terminal voltage at the ith instant.
To test the points P(i) &Q(i) on the B(i) curve representing the GCC curve at the
ith instant the following equation is used.
B4 (i) 2-f4 (i) < …. eqn. (B.22)
Likewise as in the previous, a separate LOE locus is not maintained. The equation
(B.22) checks whether the P-Q operating point lies inside the rotor current heating
limit.
The equation used to calculate the system reactance on line is
…… eqn.(B.23)
For all decision blocks a delay subroutine is to be called to tide over transitory
system inconsistencies.