Ventilation Air For Indoor Pools: Technical Bulletin 5
Ventilation Air For Indoor Pools: Technical Bulletin 5
1978
Technical Bulletin 5
When planning natatoriums, designers are concerned about The standard exists to protect the health of pool users. Proper
preventing any unpleasant odors. Typically, they design a interpretation, however, can also enhance energy conservation
ventilation system which brings in an excess amount of by reducing the volume of outdoor air required to the mini-
outdoor air in order to control any potential odor problems. mum allowed by code.
While a complete analysis of pool water chemistry is beyond
the scope of this bulletin, a quick review is required to eliminate The interpretation is based on the following assumptions:
The control of outdoor air dampers can be accomplished in I NTRODUCTION OF OUTDOOR AIR
two ways: a manual switch or a timer.
The dynamics of a pool enclosure are unique because of the
For either of these two actuation methods, the system will need for humidity control. Most other applications can accept
establish three control points to automate the outdoor air outdoor air upstream of the air handler without affecting the
damper: closed for unoccupied conditions; minimum code system’s performance. This is not true in the case of a
ventilation for normal activity; and an event mode to handle dehumidifier. If outdoor air is introduced into the return air
spectator load requirements. duct, two problems can occur in cold weather (winter). The
first problem is condensation in the duct when cold air meets
Spectator occupancy is not constant in most facilities except the moist return air from the pool room. The second problem
during swim meets or shows. Spectator ventilation air can be is that the mixed air temperature will be lower than the pool
introduced by a dedicated outdoor air system (DOAS) that return air and will decrease the moisture removal capacity of
has its duct work flush spectators with clean, fresh air. The the dehumidifier.
DOAS can also produce temperatures that are a couple of
degrees lower than the pool space temperature to help keep To eliminate these problems, the outdoor air should be
fully clothed spectators cooler. To further reduce energy introduced downstream of the evaporator (see Figure 3.)
costs, the code ventilation for this area can be controlled via Then the dehumidifier has maximum moisture removal
a manually activated switch or a building management system capacity and the reheat and auxiliary heating coils can raise
with a scheduling program. In this way the facility can reduce the temperature of the outdoor air, avoiding cold drafts
its energy costs by conditioning the air only when spectators to the swimmers.
are present.
OUTSIDE AIR
A
U F
X R I
I L
SUPPLY L E
I H T RETURN
AIR
A E E AIR
R E R
Y A V
T A
H P F
E C
A I
T O C L
I O T
C L I E
O L
I R
L
WINTER SUMMER
An indoor pool enclosure has several sources of energy loss: During the summer months, heat gain - not loss - is a problem.
A higher volume of outdoor air increases the cooling demand
1) convection through the ceiling, windows, and walls
and introduces extra moisture. The increased load requires a
2) exhaust air larger sensible cooling capacity, and the increased moisture
requires a larger dehumidifier that must run longer. This
3) evaporation of the pool water
effect must be included in the dehumidifier sizing calculation.
The convection heat loss and the exhaust air heat loss in a
pool enclosure is a function of the coolness of the outdoor air
C ONCLUSION
temperature. The greater the temperature differential between
A dehumidification system in an indoor pool facility not only
indoor and outdoor, the greater the loss of energy.
protects the structure and recovers energy, but it also
Uncontrolled heat loss causes swimmer discomfort and also
allows a reduction of outdoor air, thereby increasing energy
increases the pool water evaporation rate. Heat loss through
savings. If your state has adopted ASHRAE 62 ventilation
ceilings, walls, and windows can be minimized by using
codes, then the following design specifications should be
adequate insulation and multipane windows. Heat loss
incorporated into your plans:
through exhaust air can be minimized by eliminating exhaust
during unoccupied times and by bringing in the minimum ◆ Dehumidification system - designed to provide four to
amount of outdoor air that code permits. eight air changes per hour while maintaining a relative
humidity of 50 percent for unoccupied space and not
The water’s heat loss can be minimized by maintaining the air greater than 60 percent for occupied (active) space.
temperature at several degrees above the water temperature.
A key factor is maintaining the room relative humidity at ◆ Automatic chemical feed system - designed to eliminate
50-60 percent. Should the relative humidity drop below 50 the need to introduce extra outdoor air to control the odor
Relative humidity below 50 percent can occur when extra ◆ Provide 0.5 CFM/square foot of pool and deck area
amounts of outdoor air are introduced in the wintertime. during normal usage, and 0.5 CFM plus 15 CFM per
spectator during swim meets or shows.
The simplest method to calculate the effects of ventilation is
the total enthalpy method. This method compares the difference ◆ Outdoor air introduced after the evaporator coil in the
in enthalpy (BTU/lb) of indoor versus outdoor air at different pool dehumidifier -maximizes the capacity of the unit.
ventilation rates. A direct energy cost can then be calculated. A DOAS can be used for the spectator outdoor air volume.
105 2019/01