Relay For OLTC Control & Transformer Monitoring: Technical Data
Relay For OLTC Control & Transformer Monitoring: Technical Data
Model REG-DA
1 Wall mounting housing
1 Panel mounting housing
1 Din-rail mounting
Issue 06/2020
g
We take care of it.
AC input (IE)
4. Technical specifications Overload capacity 10 A continuous
Regulations and standards 30 A for 10 s
100 A for 1 s
0 IEC 61010-1 / EN 61010-1
500 A for 5 ms
0 CAN/CSA C22.2 No. 1010.1-92
0 CISPR 22 Ed.6 (2009-09)
0 IEC 60255-11 / EN 60255-11 Analogue inputs (AI)
0 IEC 60255-21 / EN 60255-21 Quantity See order specifications
0 IEC 60255-22-1 / EN 60255-22-1 Input range
0 IEC 60255-25 / EN 60255-25 Y1...Y2 -20 mA...0...20 mA
0 IEC 60255-26 / EN 60255-26 points Y1 and Y2 are
0 IEC 60255-27 / EN 60255-27 programmable
0 IEC 61326-1 / EN 61326-1 Control limit ± 1.2 Y2
0 IEC 60529 / EN 60529
Voltage drop ≤ 1.5 V
0 IEC 60068-1 / EN 60068-1
0 IEC 60688 / EN 60688 Potential isolation Optocoupler
0 IEC 61000-6-2 / EN 61000-6-2 Common-mode > 80 dB
0 IEC 61000-6-4 / EN 61000-6-4 8 rejection
Series-mode rejection > 60 dB / Decade from 10 Hz
Overload capacity ≤ 50 mA continuous
UL Certificate Number 050505 - E242284 Error limit 0.5%
Limit-value monitoring
Limit values programmable
Response times programmable
Simplified diagram of a binary input Alarm indicators LEDs are programmable or are
programmable on an LCD
Mechanical dimensions, in mm
47 >I R11
6. Terminal configuration 48 >U R10
No. 49 <U R9
Option M1* M2* M9* 50 Local R8
51 Remote R7
2 Measuring U1a UL1 U1a
5 voltage U1b UL2 U1b 52 TC error** R6
Level I
8 Measuring
Measuring UL3 U2a 53 GND R6...R11
10 voltage
voltage - U2b
- 54 closes in the event of
Level I
1 Measuring
S1 fault
voltage Current input I1 55 Life contact (status)
3 S2
56 opens in the event of
4 S1 Current input I2 fault
6 S2 57 MANUAL
7 S1 58 MAN/AUTO
9 S2 Current input I3
59 AUTO
21 L/(+) UH = Auxiliary voltage
22 L/(-) 69 E-
63 mA input + A1 70 E+
E-LAN (L)
64 mA input - A1 71 EA-
72 EA+
61 mA input or output + A2
200 GND
Level III
62 mA input or output - A2 0
73 E-
65 mA input or output + A3 74 E+
66 mA input or output - A3 75 EA- E-LAN (R)
67 mA input or output + A4 ϑ 76 EA+
68 mA input or output - A4 201 GND
0
77 Tx+
11 Binary input 1 Freely programmable
12 Binary input 2 Freely programmable 78 Tx-
13 Binary input 3 Freely programmable 79 Rx+ COM3 (RS485)
14 Binary input 4 Freely programmable 80 Rx-
Level III
Module 2
and C99 with four Ethernet ports (Feature PB1…5). In this case 102 R14
the feature C90 can also use only one slot. 103 R15
Characteristic C10 – Standalone monitoring function 104 R16
No. 105 R17
100 lower command 106 GND R12 … R17
101 interlock 107 R18
102 raise command 108 R19
8
Module 2
103 interlock 109 R20
104 Overvoltage >U 110 R21
105 Root 111 R22
Module 6
Module 1
113 COM2 / TxD 102 Binary input E19
Characteristic C90 – (e.g. 2 x PT100, other combinations are possible) 103 Binary input E20
No. 104 Binary input E21
100 Ik+ 105 Binary input E22
Module 5
Module 3
COM1
90 RS232-RxD 141 RS232-TxD COM1
COM1
RS232
Fibre optic
COM1
RJ45
Ethernet 1
connector
Characteristic Z21–REG-LON communication interface
No.
Fibre optic cable In
Fibre optic
Fibre
Characteristics XW94..96,
Fibre optic cable GND module Fibre optic
cable Characteristics CS94..96 combined with PB0
Fibre optic cable VCC REG-PE🔒 TK 28-6A communication interface
Nr.
Characteristic Z99–Profibus-DP communication interface 130 RS232 Rx PARAM (acc. GND is terminal 134)
131 RS232 Tx PARAM (acc. GND is terminal 134)
No.
1 RS232-GND FO 132 Fibre optic Rx Fibre optic
133 Fibre optic Tx
PARAM
(RJ11)
137 PE
Profibus-
4 RTS
138 GND COM1
5 GND BUS
139 RS485-P (B) COM1
6 +5 V BUS
140 RS485-N (A) COM1
COM1
8 A-Line (Rx/Tx -)
141 RS232-TxD COM1
142 RS232-RxD COM1
Characteristics XW90..93+97+98 143 RS232-RTS COM1
REG-PE TK 860 communication interface (discontinued item, for 144 RS232-CTS COM1
replacement see REG-P(E)🔒 TK28-4/6 in the right column) 145 RS485-P (B) COM4
No. 146 RS485-N (A) COM4
147 RS232-TxD COM4
COM4
87 RS232-RxD
148 RS232-RxD COM4
PARAM1
88 RS232-TxD
149 RS232-RTS COM4
89 RS232-GND 150 RS232-CTS COM4
90 RS232-GND-SCR 151 GND COM4
91 RS232-RxD PARAM Micro USB
PARAM 2
92 RS232-TxD
RJ45
93 RS232-GND Ethernet 1 or
connector
94 RS232-GND-SCR Fibre optic (LC)
RJ45
Ethernet
Ethernet 2 or
RJ45 connector or connector
Fibre optic (LC)
Fibre optic cable (ST or LC)
Characteristics PB1..4
REG-PEDSV TK 102A communication interface
Nr.
87 RS485-P (B) COM1
88 RS485-N (A) COM1
89 RS232-TxD COM1
COM1
90 RS232-RxD COM1
91 RS232-RTS COM1
92 RS232-CTS COM1
93 GND COM1
94 PE
PE
95 PARAM-RxD
PARAM
96 PARAM-TxD
97 GND
5V ext.
RJ45
Ethernet 1 or
connector
Fibre optic (LC)
RJ45
Ethernet 2 or
connector
Fibre optic (LC)
RJ45
Ethernet 3 or
connector
Fibre optic (LC)
RJ45
Ethernet 4 or
connector
Fibre optic (LC)
*) The dual module comes as a dual mA input module or a dual mA output module. The position is occupied by a PT100 module
if the temperature is to be recorded directly.
*) The dual module comes as a dual mA input module or a dual mA output module. The position is occupied by a PT100 module
if the temperature is to be recorded directly.
Time factor 0.1 ... 30 To ensure that the REG-DA produces the same results during
the simulation as in a live environment, the transformers, the
Setpoint value 1..2 60.0 ... 140.0 V network and the load are accurately recreated
60.0 ... 140.0 V or mathematically.
Setpoint value 3..4 -500 … 500% for P/Q The authenticity of the simulation is guaranteed because
regulation REGSimTM uses the REG-DA regulator's original algorithm.
ΔU · t = const All of the settings match those of the real regulator and the
REG 5A/E simulation is run in real time.
Time behaviour
LINEAR REGSimTM enables parameters to be tested and set before
CONST using them in a live environment.
Trend memory 0 ... 60 s
Apparent current
Current influence Active current
(load-dependent setpoint) Reactive current
LDC
Apparent, active, reactive
current
0 ... 400 V/In
Increase (I) (pos.)
0 ... 400 V/In
Increase (I) (neg.)
-40 ... 40 V
Limit (I) (max.)
-40 ... 40 V
Limit (I) (min.)
R : 0 ... ± 100 Ω
LDC (Line drop compensation)
X : 0 ... ± 100 Ω
Undervoltage <U -25% ... +10 %
Overvoltage >U 0 ... 25 %
Overcurrent >I 0 ... 210% (1A / 5A)
Undercurrent >I 0 ... 100 % (1A / 5A)
Inhibit High 65 V ... 150 V
Fast switching forward 0 ... -35 %
Fast switching backward 0 ... 35 %
Inhibit low -75 % ... 0 %
Switching delay for <U, >U, <I,
inhibit high,
1 ... 999 s
Fast switching,
(Fast step-up 2...999 s)
Inhibit low can be set
separately
Parallel programs dI*sin(phi)
dI*sin(phi)[S]
dcos (phi)
Master-slave
MSI
MSI2
TC in operation - maximum
3 ... 40 s
time
8. Order specifications
0 Only one code of the same capital letter is possible
0 When the capital letter is followed by number 9, further details are necessary
0 The code can be omitted when the capital letter is followed by zero or one option is marked as standard
0 X characteristics such as XE91 cannot be combined with all of the other characteristics. Please read the notes and
explanations.
CHARACTERISTIC CODE
REG-DA relay for voltage control REG-DA
0 with dual ELAN interface COM2, COM3 and one mA input channel, for example, to measure the oil
temperature or get the tap position via mA signal
0 with 16 binary inputs and 12 relay outputs plus a status output, and includes the parameterisation
software WinREG to set parameters, program and view all regulator data and connection cables.
Note: COM2 is only freely accessible when operated without SCADA interface.
Model
0 Sheet steel housing (H x W x D) 307 x 250 x 102 mm including flange plate with cable glands, B0
brush sealing and mounting material for panel or wall mounting
0 Sheet steel housing (H x W x D) 307 x 250 x 102 mm including flange plate with cable glands, brush B1
sealing and mounting material for panel or wall mounting and standard DIN rail adapter
Serial interface COM1
0 Serial interface COM1 as RS232 with SUB-D connector (9-pin male), standard if charact. is not I0
specified
0 Serial interface COM1 as USB I1
Power supply
0 Power supply AC 85V ... 110V ... 264V / DC 88V ... 220V ... 280V H0
0 Power supply DC 18V ... 60V ... 72V H2
Input current (rated value)
0 Rated input current Ir 1A (subsequently modifiable) F1
0 Rated input current Ir 5A (subsequently modifiable) F2
Voltage and current measurement
0 Three-wire three-phase system balanced load (1x U, 1x I) M1
0 Three-wire three-phase system unbalanced load (2x U, 2x I, Aron connection) M2
0 Measured quantities: primary voltage U, secondary voltage U and current I (2x U, 1x I) M3
0 Other application with 2x CT's and 2x VT's; e.g. 3 windings transformer M9
Recorder function for network quantities incl. REGView evaluation software
0 Without Recorder function S0
0 With Recorder function with max. three channels S1
0 With Recorder function with max. 256 channels (4x 64), 108 MB internal memory and upgraded CPU, S2
including S1
Transformer monitoring
0 Without Transformer Monitoring T0
0 With Transformer Monitoring in accordance to IEC 60354 and IEC 60076 T1
0 With extended Transformer Monitoring: moisture in paper/oil, bubbling temperature (T1 incl.) T2
Note: The feature T2 is only available in combination with the features S2
Parallel operation
0 Without firmware for parallel operation K0
0 With firmware for parallel operation K1
Integrated SCADA connection for Ethernet based protocols (e.g. IEC 61850) without cyber security
option
0 without ethernet based protocols without cyber security option (continue with charact. group 'CS') XW00
0 IEC 61850 with 1x RJ 45 connection (continue with characteristic group 'G') XW91
0 IEC 61850 with 1x FO-ST connection (continue with characteristic group 'G') XW93
0 IEC 61850 with 1x FO-LC connection (continue with characteristic group 'G') XW93.1
0 IEC 61850 with 2x RJ45 connection (continue with characteristic group 'G') XW94
0 IEC 61850 with 2x FO-ST connection (continue with characteristic group 'G') XW95
0 IEC 61850 with 2x FO-LC connection (continue with characteristic group 'G') XW95.1
0 IEC 61850 with 1x RJ45 and 1x FO-ST connection (continue with characteristic group 'G') XW96
0 IEC 61850 with 1x RJ45 and 1x FO-LC connection (continue with characteristic group 'G') XW96.1
0 DNP 3.0 over Ethernet with 1x RJ45 connection (continue with characteristic group 'G') XW97
0 DNP 3.0 over Ethernet with 2x RJ45 connection (continue with characteristic group 'G') XW94.1
0 DNP 3.0 over Ethernet with 1x FO-ST connection (continue with characteristic group 'G') XW98
0 DNP 3.0 over Ethernet with 1x FO-LC connection (continue with characteristic group 'G') XW98.1
0 DNP 3.0 over Ethernet with 2x FO-ST connection (continue with characteristic group 'G') XW95.2
0 DNP 3.0 over Ethernet with 2x FO-LC connection (continue with characteristic group 'G') XW95.5
0 DNP 3.0 over Ethernet with 1x RJ45 and 1x FO-ST connection (continue with characteristic group 'G') XW96.4
0 DNP 3.0 over Ethernet with 1 x RJ45 and 1 x FO-LC connection (continue with characteristic group 'G') XW96.5
Note: Please specify the target SCADA system for connections in conformity with DNP 3.0.
0 DNP 3.0 over Ethernet with 1x RJ45 connection (continue with code "PB") CS97
0 DNP 3.0 over Ethernet with 2x RJ45 connection (continue with code "PB") CS94.1
0 DNP 3.0 over Ethernet with 1x FO-ST connection (continue with code "PB") CS98
0 DNP 3.0 over Ethernet with 1x FO-LC connection (continue with code "PB") CS98.1
0 DNP 3.0 over Ethernet with 2x FO-ST connection (continue with code "PB") CS95.2
Integrated SCADA connection for serial protocols like IEC 60870- 5-101/ ..-103, DNP3.0, …
0 without integrated protocol interface for serial protocol (continue with code "G") L0
0 with integrated SCADA interface for serial prot. for connection of one REG-DA (cont. with code "V") L1
0 with integrated SCADA interface for serial protocol for connection of more than one system (REG- L9
D/DA/DP etc.) (continue with code "V")
Note: L9 can only be combined with characteristics Z15 to Z19 and Z91.
Connection type
0 Copper
– RS232 V10
– RS485 2-wire operation only V11
0 Fibre optic cable with FSMA connection technology
– Fibreglass (Wave length 800...900 nm, range 2000 m) V13
– All-plastic (Wave length 620...680 nm, range 50 m) V15
0 Fibre optic cable with ST connection technology
V17
– Fibreglass (Wave length 800...900 nm, range 2000 m) V19
– All-plastic (Wave length 620...680 nm, range 50 m)
0 Fibre optic cable with VL connection technology V22
– All-plastic (Wave length 620...680 nm for SPABUS)
(continue with code "Z or CZ")
Protocol (without cyber security) Attention! Select only Z or CZ
0 IEC60870-5-103 for ABB Z10
0 IEC60870-5-103 for Areva Z11
0 IEC60870-5-103 for SAT Z12
0 IEC60870-5-103 for Siemens (LSA/SAS) Z13
Provided by:
_______________________________