B.9 - Data Sheet of The Inverter PDF
B.9 - Data Sheet of The Inverter PDF
100%
98%
L1 96%
Efficiency
DC EMI AC AC AC EMI
DC Filter Filter Relays Filter L2
94% Vdc=860 V
L3
Vdc=1050 V
92%
Vdc=1250 V
Output (AC)
AC output power 125000 VA @ 50 ℃
Max. AC output current 120 A
Nominal AC voltage 3 / PE, 600 V
AC voltage range 480 – 690 V
Nominal grid frequency / Grid frequency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD < 3 % (at nominal power)
DC current injection < 0.5 % In
Power factor at nominal power / Adjustable power factor > 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases 3/3
Efficiency
Max. efficiency / Euro. efficiency / CEC effciency 98.9 % / 98.7 % / 98.5 %
Protection
DC reverse connection protection Yes
AC short-circuit protection Yes
Leakage current protection Yes
Grid monitoring Yes
DC switch / AC switch Yes / Yes
Night SVG function Optional
Anti-PID function Optional
Overvoltage protection DC Type II / AC Type II
General Data
Dimensions (W*H*D) 670*902*296 mm 26.4''*35.5''*11.7''
Weight 76 kg 167.5 lb
Isolation method Transformerless
Degree of protection IP 65 NEMA 4X
Night power consumption <4W
Operating ambient temperature range -25 to 60 ℃ (> 50 ℃ derating) -13 to 140 ℉ (> 122 ℉ derating)
Allowable relative humidity range (non-condensing) 0 – 100 %
Cooling method Smart forced air cooling
Max. operating altitude 4000 m (> 3000 m derating) 13123 ft (> 9843 ft derating)
Display / Communication LED, Bluetooth+APP / RS485
DC connection type OT or DT terminal (Max. 185 mm² 350 Kcmil)
AC connection type OT or DT terminal (Max. 185 mm² 350 Kcmil)
Compliance CE, IEC 62109-1/-2, IEC 61000-6-2/-4, IEC 61727, IEC 62116, IEC 61000-
3-11/-12, UL 1741, UL 1741 SA, IEEE 1547, IEEE 1547.1, CSA
C22.2 107.1-01 and California Rule 21
Grid support SVG, LVRT, HVRT, active & reactive power control and
power ramp rate control
Type designation SG125HV-10