Office of The Secretary: Areas
Office of The Secretary: Areas
Republic of
Department of ‘Health
-
February 4, 2020
DEPARTMENT MEMORANDUM
No. 2020 - 0062
In response to the current or potential influx of Patients Under Investigation (PUI) for
2019 Novel Coronavirus (nCoV) in
our health facilities, all DOH Hospitals are hereby urged to
comply with the patient placement guidelines and isolation standards adopted from the CDC
Guidelines and Standards for Transmission-based Precautions. This shall facilitate the
management of PUIs and prevent the transmission of the virus within the health facility.
I. For health facilities with Airborne Infection Isolation Room (AIIR), the following
standards shall be followed:
Building 1, San Lazaro Compound, Rizal Avenue, Sta. Cruz, 1003 Manila e Trunk Line 651-7800 local 1113, 1108, 1135
Direct Line: 711-9502; 711-9503 Fax: 743-1829 e URL: http://www.doh.gov.ph; e-mail: [email protected]
Air exhaust should be directed away from people and air intakes. If this is not
possible, air must be filtered through a HEPA filter before recirculation.
Doors must be kept closed except when entering or leaving the room. Minimize
unnecessary entry and exit.
Air pressure must be monitored daily with visual indicators (e.g smoke tubes, flutter
strips), regardless of the presence of differential pressure sensing devices (e.g.
manometers).
6. For the standard floor plan for AIIR, refer to ANNEX B.
II. For facilities with limited Airborne Infection Isolation Rooms, private rooms may be
utilized for the management ofPUIs.
1. Use private roomsat the end of the hallway for conversion into a temporary isolation
room. It must be away from the stairs and nurses’ station.
2. Keep doors closed except when entering or leaving the room. Entry and exit should
be minimized.
. Keep the windows in the converted isolation rooms open regardless of use and non-
use of air conditioning. Windows connecting to hallways should not be opened.
The use of air conditioning in the isolation room is allowed provided
the general air conditioning system of the facility.
it is not part of
Medical supplies needed for patient care shall be made readily available at point of
care.
Ensure that the relatives or carers of minors and elderly patients are provided with
Personal Protective Equipment (PPEs). Instructions on the appropriate use and
disposal of PPEs must be provided.
10. Refer to ANNEX C for the Proposed Floor Plan for Converted Private Room. If
access to a lavatory in the ante room is not feasible, wall mounted alcohol-based
hand rubs are recommended.
B. Conversion of Ward
Wards may also be utilized for the management of PUIs. For the conversion of wards
into isolation rooms, the following guidelines must be followed:
1. Follow the same guidelines for conversion of private rooms.
2. Place cohorted PUIs in a converted ward room provided that they have the same test
results. Do not include patients with pending confirmatory test results in the cohort.
3. General ward rooms must have adequate ventilation with at least 60 L/s of air flow
per patient.
4. All patient beds should be placed at least three (3) feet apart with a curtain separator
for privacy.
Private rooms and wards converted into isolation rooms must not be used for the
management and treatment of patients other than PUIs until after appropriate
environmental cleaning and disinfection procedures are undertaken.
Additional reference materials on establishment and types of isolation rooms are listed
on ANNEX D.
Once in an Airborne Infection Isolation Room (AIIR), the patient’s facemask may be
removed. Transport and movement of the patient outside of the AIIR must be limited to
medically-essential purposes. When not in an AIJIR (e.g. during transport), patients must
wear a facemask to contain secretions.
Personnel entering the room must use PPEs, including respiratory protection (i.e. fit-tested
disposable N95 mask).
. Only essential personnel must enter the room. Staffing policies must be strictly observed to
minimize the number of healthcare professionals (HCP) who enter the room.
4. Facilities must take precautions to minimize the risk of transmission and exposure to other
patients and other HCP.
. Facilities must keep a log of all persons who provide care and enter the room care areas of
or
these patients.
6. Dedicated or disposable noncritical patient-care equipment must be used (e.g., blood
pressure cuffs). If equipment will be used for more than one patient, clean and disinfect such
equipment before use on another patient according to manufacturer’s instructions.
HCP entering the room after a patient vacates the room must use respiratory protection.
Standard practice for pathogens spread by the airborne route (e.g., measles, tuberculosis) is
to restrict unprotected individuals, including HCP, from entering a vacated room until
sufficient time has elapsed for enough air changes to remove potentially infectious particles.
Currently, there is no data on how long 2019-nCoV remains infectious in the air. In the
interim, apply a similar time period before entering the room without respiratory protection
as used for pathogens spread by the airborne route (e.g., measles, tuberculosis). In addition,
the room should undergo appropriate cleaning and surface disinfection before it is returned
to routine use.
. HCP must perform hand hygiene before and after contacts with patients, potentially
infectious material and PPE, including gloves.
Healthcare facilities must ensure that hand hygiene supplies are readily available in every
care location.
ANNEX B
Cabinet, PPE 1
Water closet 1
Lavatory 1
Outdoor air temperature (°C) ave, local station temp. reading {IGeneral iHumination (LUX) 250
Mechanical ventilation
fast illumination (LUX) 500
To
Humidity (9%RH) 50 Black aut essential:desirable: UNNECESSARY
SOUND SAFETY
Access limit
medical staff, relatives/watcher &
patient
risk LOW: medium: high
{fire
other risks NA
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3} HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
ee om
April 2016 NURSING WARDS
tical, 250B-NU-RDS-07C
TECHNICAL DESIGN DATA: LAYOUT OF ROOM AND SPACE COMPONENTS:
DIRECT SERVICES DESIGN DATA
oe
Medical Vacuum 40 ipm @ 450mm Hg % nd
Compressed Air
- ; NA
a
:
7
Steam NA
Loading NA
stretcher trolley access SPACE DEMANDS (Total Minimum Space Required in sq.m.) !
Windows clear, solar control, HSpace Components Minimum Space Required/Component (sq.m.)
privacy control
3000.00
KEY:
HOSPITAL BED, ADJUSTABLE; WITH
ADJUSTABLE SIDE RAILS
CHAIR, UPRIGHT; STACKING
AN
FOOTSTOOL
BENCH, CUSHIONED
AAP
TABLE, SIDE; WITH CABINET
3500.00
TABLE, OVERBED
ON
CLOSET, WARDROBE
CONSOLE, BEDHEAD, FOR NURSE CALL,
MEDICAL GAS OUTLETS, POWER OUTLETS,
6000.00 LAMP, ETC.
WASTE BIN; INFECTIOUS
10. WASTE BIN; GENERAL
PROVIDE:
ADDITIONAL
<
DOOR & WALL ANTE ROOM:
ll. LAVATORY; WALL-HUNG
12. CONCEALED FLOOR DRAIN
15. CABINET; PPE
> PROVIDE:
WASH SINK & PPE CABINET
1400.00
. Administrative Order No. 2012-0012, “Rules and Regulations Governing the New
Classification of Hospitals and Other Health Facilities in the Philippines,” as amended.
Refer to A.O. No. 2012-0012-A, “Amendment to Administrative Order (A.O.) No. 2012-
0012 entitled "Rules and Regulations Governing the New Classification of Hospitals and
Other Health Facilities in the Philippines”
. Centers for Disease Control and Prevention (2007). “2007 Guideline for Isolation
Precautions: Preventing Transmission of Infectious Agents in Healthcare Setting”, updated
July 2019. https://www.cdc.gov/infectioncontrol/guidelines/isolation/index.html]