Service Manual: Controller Sigma Control 2
Service Manual: Controller Sigma Control 2
Controller
Manufacturer:
KAESER KOMPRESSOREN SE
96410 Coburg • PO Box 2143 • GERMANY • Tel. +49-(0)9561-6400 • Fax +49-(0)9561-640130
www.kaeser.com
/KKW/SSC 2.11 en IBA-SIGMA CONTROL BLOWER
/KKW/SSC 2.11
20200824 081558
Contents
Settings can be made after log-in with the RFID Equipment Card and access level 2.
2.2 Copyright
This operating manual is protected by copyright. Any queries regarding the use or duplication of
this documentation should be referred to KAESER. Correct use of information will be fully suppor‐
ted.
2.2.1 Software
The software used in SIGMA CONTROL 2 contains copyright-protected software packages which
are licensed as Open Source.
A copy of these licenses is contained in SIGMA CONTROL 2.
Display the licenses by pointing your browser to the "COPYING" file in the root directory of
SIGMA CONTROL 2.
URL:
http:// <Hostname>/COPYING
The licenses can be also found under these addresses:
http://www.gnu.org/licenses
http://code.google.com/p/curve25519-donna/
Within three years from receipt of SIGMA CONTROL 2, you may obtain the complete source code
of the copyright-protected software packages by sending a corresponding order to the following ad‐
dress:
Technical Office Electrical Design
KAESER KOMPRESSOREN SE
96450 Coburg, Postfach 2143
Germany
This offer is valid for anybody having this information.
2.3 Certification
This product has the following approvals:
■ This equipment has been tested and found to comply with the limits for a Class B digital de‐
vice, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
─ Reorient or relocate the receiving antenna.
─ Increase the separation between the equipment and receiver.
─ Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
─ Consult the dealer or an experienced radio/TV technician for help.
■ This device complies with part 15 of the FCC rules. The operation is subject to the following
two conditions:
─ this device may not cause harmful interference, and
─ this device must accept any interference received, including interference that may cause
undesired operation.
■ This device fulfils the provisions of the Industry Canada Licence, with the exception of the RSS
rules. The operation is subject to the following two conditions:
─ this device may not cause harmful interference, and
─ this device must accept any interference received, including interference that may cause
undesired operation.
In order to ensure permanent compliance with the FCC rules, unless explicitly approved by
the authority responsible for compliance with the provisions, no changes must be carried out
(for example: when connecting to computers or peripheral equipment use shielded cables on‐
ly).
2.5.1 Warnings
Warnings indicate danger potentially resulting in personal injury, if the measures specified are not
taken.
Warning notices indicate three levels of danger identified by the corresponding signal word:
Signal term Meaning Consequences of non-compliance
DANGER Warns of imminent danger Will very likely result in death or severe injury
WARNING Warns of potentially imminent danger May result in death or severe injury
CAUTION Warns of a potentially dangerous situa‐ May result in moderate physical injury
tion
Warning notices preceding a chapter apply to the entire chapter, including all sub-sections.
Example:
DANGER
The type and source of the imminent danger is shown here!
The possible consequences of ignoring a warning are shown here.
The word "DANGER" indicates that death or severe injury can very likely result from ignoring
the warning.
➤ The measures required to protect yourself from danger are shown here.
Warning notes referring to a sub-section or the subsequent step are integrated into the procedure
and numbered as a step.
Example:
1. WARNING!
The type and source of the imminent danger is shown here!
The possible consequences of ignoring a warning are shown here.
The word "WARNING" indicates that death or severe injury may result from ignoring the warn‐
ing.
➤ The measures required to protect yourself from danger are shown here.
2. Always read and comply with warning instructions.
Example:
NOTICE
The type and source of the imminent danger is shown here!
Potential effects when ignoring the warning are indicated here.
➤ The protective measures against the damages are shown here.
Material Here you will find details on special tools, operating materials or spare parts.
Precondition Here you will find conditional requirements necessary to carry out the task.
The conditions relevant to safety shown here will help you to avoid dangerous situations.
3 Technical Specifications
3.1 Controller SIGMA CONTROL 2
Industrial PC
■ Internal temperature monitoring
■ Internal undervoltage monitoring
■ Battery-buffered real-time clock
─ Battery service life: more than 10 years
─ Battery replaceable
Characteristic Value
Material Plastics
Width [mm] 190
Height [mm] 130
Depth [mm] 45
Number of membrane keys 13
Number of LEDs 9
Degree of protection, control cabinet exterior IP 54
Degree of protection, control cabinet interior IP 20
Voltage [V DC] 24
Current [A] 0.3
Voltage source Input/output module
Display
Characteristic Value
Graphical display [px] 255 x 128
Width [mm] 82
Height [mm] 41
Maximum number of lines/characters 8/30
Colours Black/white with grey scale
Lighting LED backlit
px ≙ pixel
Characteristic Value
Hardware on the SIGMA CONTROL 2 controller RFID reader
Hardware (external) RFID Equipment Card
Recognition distance [m] Max. 0.05
Frequency [MHz] 13.56
Emitted maximum transmitting power at 10 m dis‐ 11
tance [dB(µA/m)]
Tab. 11 RFID
The RFID read/write device transmits at a frequency of 13.56 MHz and is permitted for use in
EU member states.
IOM 1
Input/Output Input/output module 1
Internal, in available in External, into
the control parallel on the machine
cabinet both sides interior
Digital input (DI), 24 VDC 4 10 2
Analogue input current (AII), 0–20 mA – 1 2
Analogue input resistor (AIR), PT100 – 1 3
Digital output relay (DOR), 250 VAC, 8 A 8 – –
Digital output transistor (DOT), 24 VDC, 0.5 A – 2 1
Analogue output current (AOI), 0–20 mA – – –
Tab. 12 IOM 1
Characteristic Value
Degree of protection within the machine IP 54
Degree of protection within the control cabinet IP 20
Characteristic Value
Width [mm] 125
Height [mm] 250
Depth [mm] 44
3.1.3 Sensors
Pressure transducer
Characteristic Value
Output signal [mA] 0/4–20
Connection Two-core
Resistance thermometer
Characteristic Value
Sensing resistance (to DIN IEC 751) PT100
Connection Two-core
Feature Value
Controller SIGMA CONTROL 2 SIGMA AIR MANAGER 4.0
Bus PROFIBUS DP-V0 Slave, RS485
GSD file KAES0CEC.gsd KAKO0EFB.gsd
Baud rate Automatic recognition, possible baud rates:
[kbps]: 9.6/19.2/45.45/93.75/187.5/ 500
[Mbps]: 1.5/3/6/12
Input data 64 byte
Output data 128 byte
Diagnostic data 31 byte —
Data content, "Technical description "Technical description
see SIGMA CONTROL 2 process im‐ SIGMA AIR MANAGER 4.0 process im‐
age", document number age", document number 7_9696_PA.
7_7601_PA.
Feature Value
Controller SIGMA CONTROL 2 SIGMA AIR MANAGER 4.0
Bus SIGMA CONTROL 2 or ASCII, RS485 or RS232, galvanically isolated
Baud rate Adjustable, possible baud rates:
[bps] 1200 / 2400 / 4800 / 9600 / 19200 / 38400 / 57600 / 76800 / 115200
Stop bits Possible settings 1 / 2
Parity Possible settings None / Even / Odd
Bold elements: Factory setting
Feature Value
Time-out [ms] Possible settings 0...2000 ... 99999
Data bits: RTU: 8, ASCII: 7
Mode Possible settings RTU / ASCII
Input data 64
[byte]
Output data 128 (process data) and 42 (diagnos‐ 128 (prozess data)
[byte] tic data)
Data content "Technical description "Technical description
SIGMA CONTROL 2 process image", SIGMA AIR MANAGER 4.0 process im‐
document number 7_7601xPA. age", document number 7_9696_PA.
Bold elements: Factory setting
The Modbus interface is galvanically isolated and features RS485 and RS2232 signals. To use the
RS232 interface, connect Pin 2 with Pin 3.
Pin Direction Signal Description
1 — GND Data reference potential (isolated),
C/C’ RS485: Bus polarisation, for terminating resistor (pull-down)
2 Output VP +5V DC (isolated, max. 10mA) RS485: Bus polarisation,
+5V for terminating resistor (pull-up)
3 Input PMC To use RS232, connect with Pin 2.
To use RS485, keep open.
5 Bi-directional B/B’ RS485 B (RxD/TxD positive)
7 Input RxD RS232 Receive data
8 Output TxD RS232 Send data
9 Bi-directional A/A’ RS485 A (RxD/TxD negative)
Housing — — Internally connected to functional earthing (FE)
Feature Value
Controller SIGMA CONTROL 2 SIGMA AIR MANAGER 4.0
Bus Modbus TCP server (Slave)
Connection 2x RJ45 ports (Cat5e, shielded), integrated 2-port switch, potential isolation
Baud 10/100, full duplex or half duplex
rate [Mbit/s]
Input data [byte] 64
Feature Value
Output data 128 (process data) and 42 (diagnos‐ 194 (process data)
[byte] tic data)
Data content "Technical description "Technical description
SIGMA CONTROL 2 process im‐ SIGMA AIR MANAGER 4.0 process im‐
age", document number 7_7601xPA. age", document number 7_9696_PA.
Recommended conduit
Feature Value
Conductor Network conductor, CAT5 shielded, CU, for example: 7.7629.0
Plug Bus plug RJ45, IP20, for example: 7.7628.0
Maximum cable length [m] 100
Feature Value
Bus DeviceNet adapter (Slave), galvanically isolated
EDS file 324-8172-EDS_ABCC_DEV_V_2_3_1.eds
Functions Implicit and explicit messaging, UCMM, change-of-state, cyclic IO, polled IO
Baud rate [kbps] Automatic recognition, possible baud rates: 125–500
Input data [byte] 64
Output data [byte] 128
Data content "Technical description SIGMA CONTROL 2 process image", document number
7_7601xPA.
Feature Value
Controller SIGMA CONTROL 2 SIGMA AIR MANAGER 4.0
Bus SIGMA CONTROL 2 device (Slave) with RT classification, conformity class B,
topology detection (LLDP), network management (SNMP), redundancy, MRP
protocol
Connection 2x RJ45 ports (Cat5e), 2-port switch, potential isolation
Baud 100, full duplex
rate [Mbit/s]
GSD file GSDML-V2.25-Kaeser- GSDML-V2.3-Kaeser-SAM2-20150112
SC2-20120203.xml
Input data 64
[byte]
Output data 128 (process data)
[byte]
Data content, "Technical description "Technical description
see Document SIGMA CONTROL 2 process im‐ SIGMA AIR MANAGER 4.0 process im‐
No. age", document number age", document number 7_9696_PA.
7_7601xPA.
Recommended conduit
Feature Value
Conductor PROFINET conductor, CAT5 shielded, CU, for example: 7.7629.0
Plug Bus plug RJ45, IP20, for example: 7.7628.0 or 7.7628.1
Maximum cable length [m] 100
3.2.6 EtherNet/IP-Module
EtherNet/IP-Interface
Feature Value
Controller SIGMA CONTROL 2 SIGMA AIR MANAGER 4.0
Bus EtherNet/IP-Server (Slave)
Connection 2x RJ45 ports (Cat5e, shielded), integrated 2-port switch, potential isolation
Baud 10/100, full duplex or half duplex
rate [Mbit/s]
Input data [byte] 64
Output data 128 (process data) and 42 (diagnos‐ 194 (process data)
[byte] tic data)
Data content "Technical description "Technical description
SIGMA CONTROL 2 process image", SIGMA AIR MANAGER 4.0 process im‐
document number 7_7601xPA. age", document number 7_9696_PA.
Recommended conduit
Feature Value
Conductor Network conductor, CAT5 shielded, CU, for example: 7.7629.0
Plug Bus plug RJ45, IP20, for example: 7.7628.1
Maximum cable length [m] 100
Machines with star-delta start operate at mains frequency with a speed determined by the belt
drive translation. The flow rate depends on the working pressure and, possibly, the options of the
specific machine.
Machines with frequency converters (FC) operate with variable speeds, regardless of the mains
frequency applied. The flow rate depends on the respective speed, the working pressure and, pos‐
sibly, the options of the specific machine.
STC: Sections of this manual with this symbol apply solely to machines with star-delta start.
OFC/SFC: Sections of this manual with this symbol apply solely to machines with frequency-
converter (FC).
All other sections apply to both machine types.
Components
Function
A suitable transponder is the RFID Equipment Card. Two of them have been provided with the ma‐
chine.
Typical application:
■ Operators log on at the machine.
(Manual input of the password not required)
5.4 Display
Use the display to read information and to check entered data. The display comprises 8 lines, each
of 30 characters.
During operation, the operation mode is displayed as a pipe and instrument diagram.
Press «Enter» or one of the arrow keys to open the main menu. Here, you can set the language to
be used for the display of texts or open the various submenus.
Header
The header 8 is the topmost line on the display. It is always shown as white text on a black back‐
ground.
Display lines 2 to 7 display the current machine state as a pipe and instrument diagram (see Fig. 8)
or a menu text.
The following parameters with their current values are displayed in line 8:
■ The hours during which the machine was activated
■ Remaining desiccant service life of the machine until the next maintenance.
Representation
The main menu is the top menu level. You open the individual submenus in the main menu.
A scrollbar appears at the right side of the display if you open a menu with more than 6 lines. It
represents the currently visible portion of the menu. A short scrollbar thus indicates that the opened
menu is very long as only a small portion can be displayed.
The image above provides an example for the appearance of the main menu (without scrollbar).
Numbering
Active line
The active line (2–8) is always shown as white text on a dark background. In deviation of this, the
header is also shown as white text on a dark background, but cannot be selected.
Press «Enter» to open a menu in the active line. This opens the selected menu.
You change parameters in Setting mode.
Setting parameters
Press «Enter». The value of the parameter will flash indicating that it can be changed.
The «Enter» key affects only the active line.
In some lines, you can change more than one parameter.
In this case, you must first select the specific parameter with the «Left» or «Right» keys.
In order to reset current parameters to Zero, activate the check box for Reset in the active line of
the display.
First, press «Enter» to switch into setting mode. The check box Reset flashes.
You then press «Up». The check box is activated and flashes.
Press «Enter» to save the settings.
The display no longer flashes and the parameters are reset. The check box for Reset is again de‐
activated.
Further information For opening KAESER CONNECT, login and other procedures, please see chapter 8.3.
Subsequently, the software is loaded and the current operating mode is displayed as a pipe and
instrument diagram. Example:
The operating display provides the most important parameters during the machine's operation.
Main menu
Key remote
For details of the Communication menu, please
see table 43.
10 Components ■ Motor
■ Block
■ Sound enclosure cooling
■ AFxM-valve
■ Aftercooler
current Alarms
current Warnings
1.2 Statistics Load (hours)
since/Reset
Load (FAD)
since/Reset
Motor starts total
since/Reset
Motor starts /h
Motor starts /d
1.3 DI/DO display 1st I/O module
DI/DO display
3)
only visible in the event of parametrisation error
Model:
Date/Time
Time zone
■ Time server
─ active:
─ IP address
Date format
Time format
Pressure unit
Temperature unit
Display illumination
1)
Power switching with frequency converter (OFC/SFC)
■ Fixed speed 1)
─ n_min/n_max
─ Set speed
─ Actual speed
■ Pressure control 1)
─ Source actual pressure
─ Source set pressure
─ Local set pressure
─ KP
─ KI
─ Set pressure rise time
─ Ignore bus actual pressure
■ External values control 1)
─ Controller settings
─ Load control
xA
Load on/Load off
xB
Load on/Load off
─ xA/xB Clock
xA/xB RC
dt maintenance hours
Ramp up time
Ramp down time:
1)
Power switching with frequency converter (OFC/SFC)
Load signal
Idle signal
Acknowledge messages
Key remote
5.6 Save data Language:
Save data
Eject SD card
Status
Format SD card
5.9 Pulse generator Activate
on
off
Function
5.10 I/O periphery ■ DO-functions
─ On load
─ Controller on
─ Collective error
─ Collective warning
─ Remote mode
─ Time control active
■ External messages
─ External message 1
─ External message 2
─ External message 3
■ Switch
─ p1
─ p2
─ T1
─ T2
─ T3
─ T_S
─ block speed
1)
Power switching with frequency converter (OFC/SFC)
Restart
Timeout
Cycle time
For details of the Connections menu, please see
table 44.
■ E-mail
─ active:
Blower number:
Language:
─ Sender address:
Sender name:
Contact telephone:
Receiver address:
─ SMTP server:
User name:
Password
─ Port/Timeout
Repeat cut-off time:
MAC: MAC address
8.2 Com-Module The content of the menu depends on the type of
the communication module identified.
Motor type
1)
Power switching with frequency converter (OFC/SFC)
2)
Screw blower
n_ref, p
■ Speed monitoring
■ Vibration monitoring
─ VSE Status
─ AII
─ ↑ V1
1)
Power switching with frequency converter (OFC/SFC)
2)
Screw blower
Collection
AIR
⇞
↑
↓
⇞ DI
10.4 AFxM-valve AFxM-valve
Control type
Type
Idle time
10.5 Aftercooler Aftercooler
10.6 Transmission venting Oil return/DOT
vacuum pump/DOT
Interval
Target/Actual
Trigger time
Target/Actual
1)
Power switching with frequency converter (OFC/SFC)
2)
Screw blower
When the operating voltage is applied to the SIGMA CONTROL 2 controller, the operating control
is in OFF mode.
If all faults are inactive, pressing «ON» produces the ON ready mode.
If remote control is active, the remote load demand and remote idle demand signals are evaluated.
When the remote control is deactivated, the system switches to Local mode. The load signal is
generated by the «ON» key or the two-point controller.
Pressing the «OFF» key produces the SWITCH OFF ready mode. The machine is shut down un‐
der control. The sound enclosure's fan will run on to prevent a heating up of the interior caused by
pent up heat. If «ON» is pressed during the control shut-down process, the ready control returns to
ON mode.
You can interrupt the controlled machine shut-down by pressing «OFF» a second time. The ready
control changes to OFF ready mode. The sound enclosure's fan stops.
If the ready control is in ON or SWITCH OFF ready mode and a fault occurs, the ready control
switches to OFF ready mode.
If the Remote acknowledgement function is inactive, the machine cannot be operated until the fault
is corrected. When all fault causes have been corrected and all faults have been acknowledged,
you must again press «ON».
If the ready control is in ON ready mode and a fault occurs or is active, the ready control switches
to ON/FAULT ready mode but not OFF ready mode. In the ON/FAULT ready mode, the machine
behaves similar to the OFF ready mode.
When all fault causes have been corrected and all faults are acknowledged, the ready control re‐
turns to ON ready mode and the drive motor starts. You don't need to press «ON» a second time.
If the ready control is in ON/FAULT ready mode, you must expect at any time that a remote
acknowledgement may switch the machine to ON ready mode and the drive motor is started.
Objective of the venting period: Preventing undesirable switching processes of the motor due to
signal faults. Reducing the response time for load demand when the blower is still in idle mode.
The following operational states are identified:
STOP
READY
In addition, timing and/or remote control may affect the start of the drive motor.
MOTOR START
IDLE 1)
No air is transported.
1)
Only in combination with the optional idle valve.
LOAD
Air is transported.
SHUT-DOWN
When the operating voltage is applied to SIGMA CONTROL 2, the operation control is in STOP
operating mode and then switches to READY mode.
Triggered by the Load run command, the drive motor starts via the MOTOR START operating
mode and switches to LOAD operating mode. When the Load run command is no longer present,
the READY operating state is assumed and the drive motor is stopped.
If the operating control is in READY, MOTOR START or LOAD mode and the shut-down command
is present, the operation control switches to the SHUT-DOWN operating state.
As soon as the shut-down process is completed or the stop command is issued, the operating con‐
trol switches to the STOP operating state after the venting period has elapsed (menu 10.4 -> max.
1 s).
If the Load or Idle run command is present, the drive motor starts via the MOTOR START operat‐
ing state.
If the Load run command is present, the machine will switch to LOAD after the motor start is com‐
pleted.
If the Idle command is present, the operation control remains in IDLE.
If there is no Load run nor Idle command present, the operating control switches to the SHUT-
DOWN state. This state is only left after the venting period has elapsed and the minimum run time
has been reached.
If the Shut-down command is present, the control switches to the SHUT-DOWN state. This state is
only left when the run-on time has elapsed and the minimum run time has been reached.
The Stop command or the end of the shut-down switches the control to the STOP state.
NOTICE
UV radiation!
Direct sunlight (UV radiation) can destroy the display screen.
➤ Do not allow the display screen to be subjected to direct sunlight.
7 Installation
7.1 Reporting Transport Damage
1. Check the machine for visible and hidden transport damage.
2. Inform the carrier and the manufacturer in writing of any damage without delay.
➤ Label the starting device in the remote control centre as follows (suggestions):
➤ Attach the following notice to indicate the ON/OFF timer program machine operation (sugges‐
tion):
8 Initial Start-up
8.1 Outline
SIGMA CONTROL 2 was designed and developed for a number of applications. The settings that
can be made are correspondingly varied.
It is possible that only a few of these settings are needed for the initial start-up. This depends on
the application.
8.2: Setting the controller (display format, units, languages, etc.)
8.3: KAESER CONNECT benefits
8.4: Displaying and setting the blower properties
8.5: Machine start and stop
8.6: Operating modes in frequency-controlled machines
8.7: Setting the machine for master control operation
8.8: Setting the external input signal
8.9: Activating remote acknowledgement
8.10: Error behaviour
8.11: Commissioning the machine
2. Press «Enter».
The Main menu is displayed.
400mbar 08:15AM 80° C Header
Main menu
----------------English GB---------------- Current language
▶1 Status Sub-menu
▶2 Performance data Sub-menu
▶3 Operating data Sub-menu
▶4 Maintenance Sub-menu
▶5 Configuration Active line
7. Use «Up» or «Down» to select a menu item in the General sub-menu such as System
information.
8. Press «Escape» repeatedly to leave this menu.
Depending on the selected language, the system automatically sets the units and the time
and date formats. You can manually change these settings (see chapter 8.2.10).
1. Press «Enter».
The Main menu is displayed.
400mbar 08:15AM 80° C Header
Main menu
----------------English GB---------------- Current language
▶1 Status active line
▶2 Performance data Sub-menu
▶3 Operating data Sub-menu
▶4 Maintenance Sub-menu
▶5 Configuration Sub-menu
3. Press «Enter».
The currently set language flashes.
4. Use «Up» or «Down» to select the desired language.
5. Press «Enter».
Name: E00019895
Level: 2
2. Press «Enter».
The access right is confirmed.
The RFID Equipment Card is damaged or lost?
➤ Manually enter the user name and password, see chapter 8.2.6.
You have noted your user name and stored it at a suitable location (see chapter 8.2.3). You now
generate a password at the SIGMA CONTROL 2. Note this generated password as well, and store
it a suitable location. If your RFID Equipment Card is damaged or lost, the card won't be necessary
to manually log on to SIGMA CONTROL 2 when you have these two pieces of information.
Name: E00019895
Level: 2
Precondition The user name (see chapter 8.2.3) and password (see chapter 8.2.5) are known.
The operating mode is displayed.
Result You are now logged on to SIGMA CONTROL 2 with access level 2, having manually input your
user name and the password.
Precondition The RFID Equipment Card delivered with the machine and at least one additional teachable RFID
Equipment Card are available.
The operating mode is displayed.
1. Hold the RFID Equipment Card delivered with the machine in front of the RFID reader.
Users are always logged on with access level 2.
400mbar 08:15AM 80° C Header
Log-in successful Menu
Button to change password Prompt, whether the password is to be changed
------------------------------
Name: E00019895
Level: 2
2. Within 10 minutes, hold the master RFID Equipment Card to be taught in front of the RFID
reader.
The master RFID Equipment Card is not registered at the machine.
400mbar 08:15AM 80° C Header
Registration successful The master RFID Equipment Card has been regis‐
tered
------------------------------
Name: E00017326
Level: 2
3. Repeat the above steps at the next machine if the master RFID Equipment Card is to be regis‐
tered at other machines.
Result You have registered a master RFID Equipment Cards at the machine.
➤ When operating the machine with a timer program, check the time settings at least once
a year.
➤ You can automatically synchronise date and time using a time server. Manual setting of
the time is no longer required in this case. See chapter 8.2.16.
1. Open the 5.1 <Configuration – General> menu.
2. Use «Up» or «Down» to select the Date/Time line.
4. Press «Enter».
The display for days 00.00.00 flashes.
5. Use «Up» or «Down» to set the day.
6. Press the «Right» arrow.
The display for months 00.00.00 flashes.
4. Press «Enter».
The time zone display flashes.
5. Use «Up» or «Down» to set the time zone.
6. Press «Enter».
The setting is applied.
7. Press «Escape» repeatedly to leave this menu.
3. Press «Enter».
The MM/DD/YY display flashes.
4. Use «Up» or «Down» to set the date format.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
3. Press «Enter».
The hh:mm:ssAM/PM indication flashes.
3. Press «Enter».
The display for the set unit flashes.
4. Use «Up» or «Down» to set the unit.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
Format Example
°F 114°F
3. Press «Enter».
The display for the set unit flashes.
4. Use «Up» or «Down» to set the unit.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
Mode 1 2 3
Indication automatic on off
Function The illumination extin‐ Permanent setting Permanent setting
guishes after the time- Illumination "on" Illumination "off"
out has elapsed.
4. Press «Enter».
The display for the set mode flashes.
5. Use the «Up» or «Down» keys to set the auto. mode.
6. Press «Enter».
The setting is applied.
7. Press the «Right» key.
8. Set the value for the Timeout in the same manner: 1 min, for example.
9. Press «Enter».
10. Press «Escape» repeatedly to leave this menu.
Result The display illumination is set for automatic operation with deactivation after one minute without
user intervention.
3. Press «Enter».
The check box Key remote will flash.
400mbar 08:15AM 80° C Header
8 Communication Menu
▶1 Ethernet/SIGMA NETWORK
▶2 Com-Module
Key remote ☐ Active line with deactivated check box
8.2.14 IP configuration
For the SIGMA CONTROL 2 to be connected to the network, you must set the IP configuration (for
KAESER CONNECT for example).
If you use SIGMA CONTROL 2 as the master control of two machines, you set other network
parameters in the IP configuration menu (see chapter 8.7.4).
The network parameters for the IP configuration must be specified manually. You cannot use
DHCP for an automatic IP configuration.
4. Press «Enter».
The first group of numbers of the IP address flashes 169.254.100.101.
5. Use «Up» or «Down» to set the first group of numbers of the IP address.
6. Press the «Right» key.
The SECOND group of numbers of the IP address flashes 192.168.100.101.
7. Use «Up» or «Down» to set the second, third and fourth group of numbers of the IP address.
The IP address is correctly set.
8. Press «Enter».
The setting is applied.
9. Press «Down».
The Subnet mask line is displayed.
10. Set the remaining network parameters as described above:
3. Press «Enter».
The check box active: will flash.
4. Press «Up».
The check box is deactivated.
5. Press «Enter».
The e-mail function is deactivated.
7. Activating the e-mail function: Activate the active: check box as described above.
8. Press «Escape» repeatedly to leave this menu.
Result The e-mail parameters are set and the e-mail function is activated.
To suppress messages repeating at short intervals, a period of 0–999 minutes can be set during
which a repeat of the same message is suppressed, i.e. is not sent. This prevents the sending of
identical messages.
4. Use «Up» or «Down» to set the value for Repeat cut-off time:.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
3. Press «Enter».
The first group of numbers of the IP address flashes 192.053.103.103.
4. Use «Up» or «Down» to set the first group of numbers of the IP address.
■ System status
■ Graphs
■ Messages
■ I/O display
■ User management
■ Settings
■ Backup
■ Data recording
Thus, KAESER CONNECT provides an excellent option for an easy and quick check of the econo‐
my and energy efficiency of your machines.
For KAESER CONNECT to be able to use the Internet-capable device, it must be registered
in the same network as SIGMA CONTROL 2.
To be able to use KAESER CONNECT, the browser installed on the Internet-capable device
must be able to display HTML5 content. For security reasons, we strongly recommend to use
only up-to-date browser versions.
1. Use an Ethernet cable to connect SIGMA CONTROL 2 to the Internet-capable device or net‐
work.
2. In the web browser, enter the IP address of the controller.
The log-in mask is displayed.
You can display the automatically-recorded machine data for any time in the past.
Precondition An SD card with sufficient free memory is inserted in the X5 SD card slot
The SD card was inserted for the entire operating time of the machine.
The SIGMA CONTROL 2 data recorder function is activated.
1. Enter the date and time for the start time in the required time period in Start:.
2. Enter the date and time for the end time in the required time period in End:.
3. Click 6 .
The machine data for the specified time interval are loaded and displayed.
3. Press «Enter».
The setting mode is active.
4. Use «UP» or «DOWN» to set the value for installation elevation.
400mbar 08:15AM 80° C Header
5.2 Blower properties Menu
Altitude 00m Active line with set installation elevation
Air pressure 1.006bar
Pressure version Pressure
Maximum pressure 0.40bar
Design pressure 0.30bar
Minimum pressure 0.20bar
You can select either Time control or Pulse generator operating mode. The operating modes
cannot be used simultaneously.
When setting a clock programme for the first time, note first the switching times on the "User-
defined clock programme" table for example.
Example
■ Machine ON: On weekdays 06:30AM – 05:00PM, Fridays 06:30AM – 03:00PM
■ Machine OFF: Sat – Sun and during midday break 12:00PM – 01:00PM
3. Press «Enter».
The n.a. indication flashes.
4. Use «Up» or «Down» to set the weekdays.
5. Press the «Enter» key.
The setting is applied.
6. Press the «Right» key.
7. Press «Enter».
The display for hours, 00:00 flashes.
8. Use «Up» or «Down» to set the hours.
9. Press the «Right» arrow.
10. The display for minutes, 00:00 flashes.
11. Use «Up» or «Down» to set the minutes.
12. Press the «Enter» key.
The setting is applied.
400mbar 08:15AM 80° C Header
6 Time control Menu
······························
01 Mon-Fri 06:30AM on Switching point 01 is set
02 Mon-Fri 12:00PM off Switching point 02 is set
03 Mon-Fri 01:00PM on Switching point 03 is set
04 Mon-Thu 05:00PM off Switching point 04 is set
05 Fri 03:00PM off Switching point 05 is set
Result Weekdays, time and the actions on / off are set for all switching points of the user-defined clock
program.
4. Press «Enter».
The setting is applied.
5. Press «Escape» repeatedly to leave this menu.
➤ Press the «Time control» key on the SIGMA CONTROL 2 operating panel to activate the time
control.
Result The Time control LED on the operating panel of the SIGMA CONTROL 2 signalises with green
continuous light that the machine is operated with activated time control.
The time control of SIGMA CONTROL 2 switches the machine according to the defined switching
points of the time program.
Result You have adjusted the delay tome for the restart after a power supply failure from 1 s to 10 s.
3. Press «Enter».
The setting mode is active.
4. Press the «Up» key.
The check box is activated.
400mbar 08:15AM 80° C Header
5.3 Restart Menu
Automatic restart ☑ Active line with deactivated check box
Delay 10 s Set/expiring delay time
Overview
■ Setting the load signal to remote mode
■ Setting the idle signal to remote mode
■ If necessary, activate the «Time control» key and configure the clock program (see chap‐
ter 8.5.1.2).
■ Activating the remote control
■ Press the «ON »key. The On LED lights green.
Two methods are available to start the machine remotely from a control centre:
■ Variant A: Starting the machine with the input signal from the remote control centre.
■ Variant B: Starting the machine from the remote control centre in addition to a configured
ON/OFF clock program.
The machine can be started from the remote control centre even though the time control is ac‐
tivated and the ON/OFF program has selected OFF at this point in time.
Result The idle signal is set to remote operation. The conveyed air escapes through the Load/Idle run
valve.
The Fixed speed and Pressure control operating modes can always be selected, regardless of the
setting of the AII1.02 current signal.
The External speed control and External values control operating modes are only available if the
AII1.02 current signal has been correspondingly defined.
■ Pressure control
─ Target value:
→ Via bus, if the activation bit is set
→ Via parameters in the 5.4.2 Pressure control
menu→ Via AII1.02, if set in the 5.5.1 Current signal AII1.02 menu
─ Actual value:
→ Via bus, if the activation bit is set
→ Via AII1.02 if Current signal AII1.02 is set in the 5.5.1 menu
and Pressure control is selected in the 5.4.2 menu
→ p1, p2 gauge or vacuum pressure version, if Pressure control is selected in the 5.4.2
menu
→ dp, if Pressure control is selected in the 5.4.2 menu
■ External speed control
─ Target value:
→ Via bus, if the activation bit is set
→ Via AII1.02 if Current signal AII1.02 is set in the 5.5.1 menu
■ External values control
─ Target value:
→ Via bus, if the activation bit is set
→ Via parameters in the 5.4.3 External values control menu
─ Actual value:
→ Via AII1.02 if Current signal AII1.02 is set in the 5.5.1 menu
1. Open the 5.5.1 <Configuration – External DI / AII signal – Current signal AII1.02 > menu.
2. Use «Up» or «Down» to select the AII1.02 line.
400mbar 08:15AM 80° C Header
5.5.1 Current signal AII1.02 Menu
AII1.02 ☐ Active line
Value type Other
Decimal places 1
Unit bar
4mA 0.40bar
20mA 1.0bar
3. Press «Enter».
The check box AII1.02 will flash.
4. Press the «Up» key.
The check box is activated.
5. Press «Enter».
The setting is applied.
6. If necessary, specify settings for Value type, Decimal places, Unit, Scaling 4mA / 20mA.
7. Press «Escape» repeatedly to leave this menu.
Result The function Current signal AII1.02 is activated. The machine can be controlled by an analogue
current signal at the AII1.02 input.
6. Use «Up» or «Down» to configure the details for the set operating mode. Open the required
sub-menus 1–3.
7. Press «Enter».
The setting mode is active.
8. Enter settings.
9. Press «Escape» repeatedly to leave this menu.
Result The currently selected operating mode is displayed in the 5.4 <Configuration – Operating modes>
menu.
8. Press «Enter».
The setting mode is active.
9. Use «Up» or «Down» to set the Set speed value.
10. Press «Enter».
The setting is applied.
In the 5.4.2 Pressure control menu, select the signal for the Source actual pressure parameter that
the system uses to regulate:
■ p1 (inlet pressure)/p2 (discharge pressure)
■ dp (differential pressure)
■ AII1.02 (Current signal AII1.02)
3. Press «Enter».
The setting mode is active.
400mbar 08:15AM 80° C Header
5.4.2 Pressure control Menu
Source actual pressure p1,p2 Active line
Source set pressure p1,p2
Local set pressure 1.0bar
KP 1.0rpm / mbar
KI 1.00rpm / (mbar *s)
Set pressure rise time 0s
A PI controller with anti-wind-up reset and upstream target value delay is used for controlling the
pressure.
The speed calculated by the PI controller is limited to the minimum and maximum speeds permissi‐
ble for the specific blower block. The difference of the speed upstream or downstream of the speed
limitation is used for the correction of the I-portion (anti-wind-up reset).
If the operation control is in STOP, READY, SHUT-DOWN or MOTOR START operating mode, the
effective target pressure is: 0 bar. At the end of the motor start, the effective target pressure of 0
bar starts to rise to the target pressure set in the menu. The effective target pressure rises linearly.
The target pressure is limited by the maximum working pressure of the machine.
4. Use «Up» or «Down» to set the value for Local set pressure.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
The target pressure is increased linear to prevent the controller output from immediately reaching
the full speed. This gives the system time to build up the actual pressure. If the full target pressure
would be instantly used, the system and hence the actual pressure could overcompensate.
To avoid an over-compensation of the actual pressure during machine start, you can set a delay
beyond the target pressure rise time (0 s to 99 s). The target pressure delay is inactive if 0 s is set
as target pressure rise time.
4. Use «Up» or «Down» to set the value for Set pressure rise time.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
Setting the KP (proportional amplification) and KI (integral amplification) values is used to activate
the PI controller and is performed empirically.
4. Press «Up» to incrementally increase the value for KP and to slightly change the actual pres‐
sure until the system (pressure) continuously compensates.
5. Use «Down» to reduce the KP value to approximately 40 - 50 % of the currently set value.
6. Press «Enter».
The setting is applied.
7. Use «Up» or «Down» to select the KI line.
8. Press «Enter».
The setting mode is active.
400mbar 08:15AM 80° C Header
5.4.2 Pressure control Menu
Source actual pressure p1,p2
Source set pressure p1,p2
Local set pressure 1.0bar
KP 1.0rpm / mbar
KI 1.00rpm / (mbar *s) Active line
Set pressure rise time 0s
9. Press «Up» to incrementally increase the value for KI until the system (pressure) continuously
compensates.
10. Use «Down» to reduce the KI value to approximately 70 - 80 % of the currently set value.
11. Press «Enter».
The setting is applied.
12. Press «Escape» repeatedly to leave this menu.
1. Open the 5.5.1 <Configuration – External DI / AII signal – Current signal AII1.02> menu.
2. Use «Up» or «Down» to select the 4mA line.
400mbar 08:15AM 80° C Header
5.5.1 Current signal AII1.02 Menu
AII1.02 ☑
Value type Speed
Decimal places 0
Unit 1/min
4mA 1500/min Active line
20mA 2000/min
3. Press «Enter».
The setting mode is active.
4. Use «Up» or «Down» to set the speed.
5. Press the «Enter» key.
The setting is applied.
6. Adjust the switching differential for the 20mA parameter in the same manner.
■ xA/xB Clock
■ xA/xB SC2
■ xA/xB RC
■ xA/xB Load balancing
In operating mode xA/xB Clock the target value is switched via a separate timer with 20 switching
points. You set the timer in the 5.4.3.2xA/xB Clock menu.
Please note the minimum run time for limiting the starting frequency (see chapter 9.1.1).
Operating mode xA/xB SC2 is a master/slave operating mode. First of all, the master/slave com‐
munication (see chapter 8.7.4), and the remote control operating mode (see chapter 8.2.13) must
be activated. This operating mode is intended for the slave. The slave uses xA, if the master uses
xB and vice versa.
In the xA/xB RC operating mode, it switches between xA and xB with a signal to the digital input.
Set the digital input in the 5.4.3External values control menu. Also, the remote control operating
mode is activated.
In the xA/xB Load balancing operating mode, the master/slave communication and the remote con‐
trol operating mode is activated. This operating mode is only used for the master. The master pur‐
sues the set target. Set a maintenance hour offset for this purpose. Depending on the number of
hours until the next maintenance, the target value is switched between xA/xB. The blower with the
higher number of hours until the next maintenance, runs at xA.
All operating modes have in common that the target value pair xA is used in the event of an error
(faulty I/O parametrisation or communication malfunction). For the master/slave operating modes,
xA is used if the partner is currently not operational.
In addition, the target value pair can be switched by means of the bus. Use the activation bit
“xBS30” and the selection bit “xBS31“ (0 = xA, 1 = xB) for this purpose.
3. Use «Up» or «Down» to set the External values control operating mode.
4. Press «Enter».
The setting is applied.
7. Use the «Up» or «Down» keys to select the Load control line.
8. Press the «Down» key.
9. Press «Enter».
The currently active operating mode flashes.
10. Use «Up» or «Down» to set the required operating mode for the Load control.
11. Press «Enter».
The setting is applied.
12. Use the «Up» or «Down» keys to select the Load on line.
13. Press «Enter».
The setting mode is active.
14. Use «Up» or «Down» to set the percentage value for the cut-in threshold.
15. Press «Enter».
The setting is applied.
16. Set the percentage value for Load off in the same manner.
17. Press «Escape» repeatedly to leave this menu.
Result The load control of the machine is controlled by the measured value of the external variable.
1. Open the 5.4.3.1 <Configuration – Operating modes – External values control – Controller
settings> menu.
400mbar 08:15AM 80° C Header
5.4.3.1 Controller settings Menu
KP 1rpm/% active line
KI 10rpm/s/%
Set value 0%
Actual value 0%
Set value ramp-up time 0s
2. Set the control parameters for the PI controller. See chapter 8.6.4 Pressure control for the set‐
ting.
Precondition SIGMA CONTROL 2 is connected to SAM 4.0 via SIGMA NETWORK and ready for operation (see
the SAM 4.0 operating manual in the chapter “Installation”)
Network pressure pB is set as the pressure for the “SAM 4.0 manual mode".
Access level 2 is activated.
The remote control is activated (see chapter 8.2.13)
3. Set the IP address for SIGMA CONTROL 2 using the following pattern:
169.254.100.(SAM 4.0 machine number +102)
(for the setting see chapter 8.2.14).
The IP address for SAM 4.0 has been set on SIGMA CONTROL 2 at the factory:
169.254.100.100 and must not be changed. The same applies to Port 2000.
3. Press «Enter».
The SAM 4.0 active: check box flashes.
4. Press «UP».
The check box is activated.
5. Press «Enter».
The setting is applied.
6. Press the «DOWN» key.
7. Press «Enter».
The currently active operating mode flashes.
8. Use «Up» or «Down» to set the Send/Receive value.
400mbar 08:15AM 80° C Header
8.1.2.2 SAM 4.0 Menu
Status Counter 0
No error
------------------------------
SAM 4.0 active: ☑
Send/Receive Active line
IP address : 169.254.100.100
Result SIGMA CONTROL 2 communicates with SAM 4.0 via SIGMA NETWORK.
The communication is working smoothly when neither SIGMA CONTROL 2 nor SAM 4.0 report any
communication fault.
After switching on the power supply, monitoring for communication malfunctions is suppressed for
a period of time which can be defined by means of the Start td parameter. The setting depends on
the time passing at the bus master between return of voltage and start of communication via the
bus.
For the communication with SAM 4.0, the value of Start td must be set to 30 s.
SIGMA CONTROL 2 can monitor the bus communication at user level. For this purpose, the bus
master reads a value ("toggle bit") that changes with every bus cycle and returns it without change.
SIGMA CONTROL 2 returns a communication malfunction if the value does not change for a time
longer than set (Timeout).
Monitoring for communication malfunction can be activated if needed. For this purpose, the
Send/Receive option must be set for the data exchange. Activate the Communication error
check box to enable monitoring for communication malfunctions.
Start td 30 s
Timeout 5s
Check box Timeout Check box ☑ activated
1)
Prerequisite: The Send/Receive option has been set
SIGMA CONTROL 2 can use an optional communication module to communicate with a master
controller or a control centre. Depending on the selected machine type, this communication module
has been factory-installed or can be added with a retrofit kit. In both cases, the communication
module must be set for the actual application in the menu of SIGMA CONTROL 2.
The following requirements must be met before commissioning the communication module:
■ The communication module is correctly installed and connected
■ The bus wiring to the bus master is ready
■ The machine is parametrised as a slave in the bus master
■ The bus master is operational
■ The machine's voltage supply is activated
■ The machine has been activated with «ON»
■ OFC/SFC: The Constant pressure control operating mode is set
When all requirements are met, perform the commissioning process for each communication
module as shown below.
The following description concerning the parametrisation refers to current
SIGMA CONTROL 2 software versions. Please contact KAESER SERVICE if the settings in
the machine deviate.
Machine
1. Open the 8.2 <Communication – Com-Module> menu.
2. Activate the Com-Module Start check box.
The communication module is activated. The system detects the communication module type
and displays it in the Type line.
3. Select the data exchange direction:
► SIGMA CONTROL 2 ⇆ Bus master (SIGMA CONTROL 2 sends process data and receives
control data): Send/Receive or Master: Set Com-Module.
► SIGMA CONTROL 2 → Bus master (SIGMA CONTROL 2 sends process data): Send or
Master: Setting SAM/JSON-RPC.
For connection to a SIGMA AIR MANAGER: Send/Receive or Master: Set Com-Module.
4. Set the slave address (Slave No.:). The permissible address length is between 3 and 126. For
connection to a SIGMA AIR MANAGER: Slave address = compressor number + 102.
5. Set the required reaction in the event of a bus fault (see next chapter, “Reaction in a PROFI‐
BUS bus fault”).
6. Start the communication module with the set parameters. Activate the Reset check box.
The communication module is started with the set parameters.
7. Time-out at bus fault is activated.
Bus communication is now monitored.
The number behind Status Counter (Run) continuously changes during communication.
After switching on the power supply, the bus alarm can be suppressed for a definable period of
time. The setting depends on the time passing at the bus master between return of voltage and
start of communication via the bus.
SIGMA CONTROL 2 monitors the bus communication at log level (PROFIBUS). If there is a check
box behind Communication error, this monitoring in the Send mode can be switched off by deacti‐
vating the check box.
In Send/Receive or Master modes, SIGMA CONTROL 2 can monitor: Com-Module the bus com‐
munication at user level. For this purpose, the bus master reads a value ("toggle bit") that changes
with every bus cycle and returns it without change. SIGMA CONTROL 2 returns a bus alarm if the
bit does not change for a time longer than set (Timeout). Activate monitoring by setting a check
mark ☑.
For the connection to a SIGMA AIR MANAGER, set the following:
Machine
Precondition Access level 2 is activated.
The network parameters are known. Request the required information from your IT department.
After switching on the power supply, the bus alarm can be suppressed for a definable period of
time. The setting depends on the time passing at the bus master between return of voltage and
start of communication via the bus.
SIGMA CONTROL 2 monitors the bus communication at log level (Modbus). If there is a check box
behind Communication error, this monitoring in the Send mode can be switched off by deactivating
the check box.
In Send/Receive or Master modes, SIGMA CONTROL 2 can monitor: Com-Module the bus com‐
munication at user level. For this purpose, the bus master reads a value ("toggle bit") that changes
with every bus cycle and returns it without change. SIGMA CONTROL 2 returns a bus alarm if the
bit does not change for a time longer than set (Timeout). Activate the check box to enable monitor‐
ing.
Machine
Precondition Access level 2 is activated.
The network parameters are known. Request the required information from your IT department
After switching on the power supply, the bus alarm can be suppressed for a definable period of
time. The setting depends on the time passing at the bus master between return of voltage and
start of communication via the bus.
SIGMA CONTROL 2 monitors the bus communication at log level (Modbus TCP). If there is a
check box behind Communication error, this monitoring in the Send mode can be switched off by
deactivating the check box.
In Send/Receive or Master modes, SIGMA CONTROL 2 can monitor: Com-Module the bus com‐
munication at user level. For this purpose, the bus master reads a value ("toggle bit") that changes
with every bus cycle and returns it without change. SIGMA CONTROL 2 returns a bus alarm if the
bit does not change for a time longer than set (Timeout). Activate the check box to enable monitor‐
ing.
Machine
Precondition Access level 2 is activated.
The network parameters are known. Request the required information from your IT department.
After switching on the power supply, the bus alarm can be suppressed for a definable period of
time. The setting depends on the time passing at the bus master between return of voltage and
start of communication via the bus.
SIGMA CONTROL 2 monitors the bus communication at log level (SIGMA CONTROL 2). If there is
a check box behind Communication error, this monitoring in the Send mode can be switched off by
deactivating the check box.
In Send/Receive or Master modes, SIGMA CONTROL 2 can monitor: Com-Module the bus com‐
munication at user level. For this purpose, the bus master reads a value ("toggle bit") that changes
with every bus cycle and returns it without change. SIGMA CONTROL 2 returns a bus alarm if the
bit does not change for a time longer than set (Timeout). Activate the check box to enable monitor‐
ing.
Machine
Precondition Access level 2 is activated.
The network parameters are known. Request the required information from your IT department.
After switching on the power supply, the bus alarm can be suppressed for a definable period of
time. The setting depends on the time passing at the bus master between return of voltage and
start of communication via the bus.
SIGMA CONTROL 2 monitors the bus communication at log level (PROFINET). If there is a check
box behind Communication error, this monitoring in the Send mode can be switched off by deacti‐
vating the check box.
In Send/Receive or Master modes, SIGMA CONTROL 2 can monitor: Com-Module the bus com‐
munication at user level. For this purpose, the bus master reads a value ("toggle bit") that changes
with every bus cycle and returns it without change. SIGMA CONTROL 2 returns a bus alarm if the
bit does not change for a time longer than set (Timeout). Activate the check box to enable monitor‐
ing.
Machine
Precondition Access level 2 is activated.
The network parameters are known. Request the required information from your IT department
After switching on the power supply, the bus alarm can be suppressed for a definable period of
time. The setting depends on the time passing at the bus master between return of voltage and
start of communication via the bus.
SIGMA CONTROL 2 monitors the bus communication at log level (SIGMA CONTROL 2). If there is
a check box behind Communication error, this monitoring in the Send mode can be switched off by
deactivating the check box.
In Send/Receive or Master modes, SIGMA CONTROL 2 can monitor: Com-Module the bus com‐
munication at user level. For this purpose, the bus master reads a value ("toggle bit") that changes
with every bus cycle and returns it without change. SIGMA CONTROL 2 returns a bus alarm if the
bit does not change for a time longer than set (Timeout). Activate the check box to enable monitor‐
ing.
You need the following accessories to create the network connection with SIGMA NETWORK or
Ethernet:
■ SIGMA NETWORK cable (7.9679.0) or Ethernet cable with a maximum connection length of
100 m each
■ For each machine with SIGMA CONTROL 2:
─ Retrofit kit LAN RJ45 (7.5250.01870)
■ For connecting the machines to a network (LAN) or switch:
─ 2x RJ45 plug (7.7628.1)
➤ Create the electrical connection according to the local condition. For more information, see the
installation manual for the retrofit kit LAN RJ45 (7.5250.01870)
Use a cross-linked Ethernet cable for the direct connection of two machines.
Connect the Ethernet cable for each machine to the LAN connection or switch.
1. Attach the RJ45-plug to the cable end.
2. Plug the RJ45plug into the network socket until it latches.
Master IP configuration
If the controllers of both machines are linked directly, they must be given different IP addresses.
Example:
■ IP addressController machine 1 (Master mode): 169.254.100.101
■ IP address Controller machine 2 (Slave): 169.254.100.102
1. Set IP address for the master see chapter 8.2.14,IP address see above example.
The IP address of machine 1 (master) is set correctly.
2. Open the 8.1.2.1 <Communication – Ethernet/SIGMA NETWORK – Connections – SIGMA
CONTROL 2> menu.
3. Use «Up» or «Down» to select the Mode line.
4. Press «Enter».
The setting mode is active.
5. Use «Up» or «Down» to set Machine 1 Master operating mode.
400mbar 08:15AM 80° C Header
8.1.2.1 SIGMA CONTROL 2 Menu
Status Run 1¦Error 0
------------------------------
Mode : Master Active line
Port : 2.001
······························
Communication partner
Slave IP configuration
If the controllers of both machines are linked directly, they must be given different IP addresses.
Example:
■ IP addressController machine 1 (Master mode): 169.254.100.101
■ IP address Controller machine 2 (Slave): 169.254.100.102
You can optionally set load balancing for both machines. Without load balancing being active, the
machines will operate in fault-actuated changeover mode (redundancy operation).
Load balancing is activated only on machine 1 (master).
3. Press «Enter».
The setting mode is active.
400mbar 08:15AM 80° C Header
4.1 Load balancing
Load balancing ☑ Active line with activated check box
dt maintenance hours 5h
Maintenance Master 1h
Maintenance Slave 1h
Master state ready
Slave state ready
The requested message can be assigned to a free digital output (DOR orDOT).
Result A message about the operational state is now sent via the assigned digital output.
Overview
Use the External messages menu for specifying the settings.
■ Enter the message text
■ Assign and activate the input
3. Press «Enter».
The cursor is located at the first character of the message text.
A column with alphanumeric characters is displayed.
The selected character flashes.
4. Select the required character with the «Up» or «Down» keys.
5. Press the «Right» arrow.
The cursor jumps to the next position of the message text.
6. Enter the remaining characters of the message text in the same manner.
7. Press «Enter».
The message text has been entered.
8. Press «Enter».
The setting is applied.
8. Press «Enter».
ok is displayed.
The input is assigned and activated.
The delay can be set between 0 and 600 seconds. The delay is counted down from 600 in 1
second increments with the «DOWN» key and counted upwards from 0 (zero) in 1 second
increments with the «UP» key.
1. Use «Up» or «Down» to select the td line.
2. Press «Enter».
The td delay time flashes.
400mbar 08:15AM 80° C Header
5.10.2.1 External message 1 Menu
External message 1 Message text
DI1.07 ok ☑ Input selected
td: 0s ¦ Logic : + set time delay td
DOR1.04 ☐
Warning ☑ Message type (operational, alarm, warning)
5. Press «Enter».
1. Select the message type line with the «Up» and «Down» keys.
2. Press «Enter».
The display for the message type flashes.
3. Use «Up» or «Down» to set the message type.
400mbar 08:15AM 80° C Header
5.10.2.1 External message 1 Menu
External message 1 Message text
DI1.07 ok ☑ Input selected
td: 0s ¦ Logic : +
DOR1.04 ☐
Warning ☑ Example: Warning message type
4. Press «Enter».
The message type is set.
Result The signal at the DI digital input is available as External message 1 and as output signal at the
selected DOR output.
3. Press «Enter».
The menu for the selected measured value (in the example p1) is displayed.
400mbar 08:15AM 80° C Header
5.10.3.1 p1 Menu
active: ☐ active line with check box
······························
SP: 0.40bar ¦ SD: 0.0bar Switching point (SP) and switching differential (SD)
td 0s ¦ Logic + Delay (td) and logic
DOR1.01 ☐ Output DOR
DOT1.01 ☐ Output DOT
2. Press «Enter».
The display for the current threshold of the switching point flashes.
3. Use the «Up» or «Down» keys to set the SP threshold.
4. Press «Enter».
The setting is applied.
5. If necessary, adjust the value for the SD switching differential in the same way.
Result The threshold for the SP switching point and the SD switching differential are set.
The delay can be set between 0 and 600 seconds. The delay is counted down from 600 in 1
second increments with the «DOWN» key and counted upwards from 0 (zero) in 1 second
increments with the «UP» key.
1. Use «Up» or «Down» to select the td line.
2. Press «Enter».
The td delay time flashes.
400mbar 08:15AM 80° C Header
5.10.3.1 p1 Menu
active: ☐
······························
SP: 0.40bar ¦ SD: −0.2bar Switching point (SP) and switching differential (SD)
td 120s ¦ Logic + Delay (td) and logic
DOR1.01 ☐ Output DOR
DOT1.01 ☐ Output DOT
Once the threshold has been reached you can switch a digital output DOR.
1. Use «Up» or «Down» to select the DOR line.
2. Press «Enter».
The DOR output display flashes.
3. Select the output with the «Up» and «Down» keys.
4. Press «Enter».
The setting is applied.
400mbar 08:15AM 80° C Header
5.10.3.1 p1 Menu
active: ☐
······························
SP: 0.40bar ¦ SD: −0.2bar Switching point (SP) and switching differential (SD)
td 120s ¦ Logic + Delay (td) and logic
DOR1.03 ok ☑ Output DOR
DOT1.01 ☐ Output DOT
1. Select the message type line with the «Up» and «Down» keys.
2. Press «Enter».
The display for the message type flashes.
3. Use «Up» or «Down» to set the message type.
400mbar 08:15AM 80° C Header
5.10.3.1 p1 Menu
······························
SP: 0.40bar ¦ SD: −0.2bar Switching point (SP) and switching differential (SD)
td 120s ¦ Logic + Delay (td) and logic
DOR1.03 ok ☑ Output DOR
DOT1.01 ☐ Output DOT
Warning ☑ Type of message
4. Press «Enter».
5. Press the «Right» arrow.
6. Press «Enter».
The check box assigned to the message type flashes.
7. Press «Up» key.
The message is activated.
8. Press «Enter».
Result In the above example the switching point for p1 has been set and is active. If the pressure is
reached or exceeded and remains longer than the set time delay td, the message is triggered with
the set message type and the set output DOR is switched. If the pressure falls below the threshold
SP + switching differential SD, the message and output are reset. The switching behaviour is inver‐
ted by setting "-" of Logic parameter.
The settings for the other measured values are carried out in the same manner.
CAUTION
Machine damage can result from acknowledging a fault message without remedying its
cause!
➤ Find the failure cause.
DANGER
Risk of injury due to sudden machine start.
➤ If the controller is in ON/FAULT operating mode when Remote acknowledgement is ac‐
tive, it must be assumed that, an any time, a remote acknowledgement may switch the
machine to ON and the blower motor is started. See chapter 5.8.
Result Should a message occur, it can now be acknowledged from a control centre.
In the following example, the behaviour in master control mode is set with SAM 4.0.
Result If a communication fault occurs during the master control mode and no external load signal has
been parametrised, the blower switches to the operating state that has been set in this menu.
➤ The settings for Com-Module are carried out in the same manner.
1. Check and confirm all the items in the check list before first start-up of the machine.
When power is applied to the machine the controller boots and carries out a self test.
The display and the Controller on LED illuminate.
The actual working pressure, the time and the airend discharge temperature are displayed in
the first line of the display.
The operating mode is mapped as a pipe and instrument diagram on the display.
9 Operation
9.1 Switching the machine on and off
Always switch the machine on with the «ON» key and off with the «OFF» key.
Precondition A power supply isolating device has been installed by the user.
9.1.1 Switching on
Precondition No personnel are working on the machine.
All maintenance doors and removable panels are in place and secured.
The ambient conditions as described in Chapter "Installation and Operating Conditions" are met
The minimum run time for limiting the starting frequency is active in the Remote control and Local
operating modes. The starting frequency is used only by star-delta machines.
Star period Motor starts per hour
<10 s 6
≥10 s 4
In screw blowers plus 2 minutes pause between OFF and ON
Automatic restart
If a power failure occurs, the machine is not prevented from automatically re-starting when power is
resumed.
It can automatically re-start as soon as power is restored.
➤ The "Automatic restart" function is deactivated by default.
See chapter 8.5.3 for setting this function.
Result The Voltage applied to controller LED extinguishes. The machine is switched off and disconnected
from the power supply.
In rare cases, you may want to shut down the machine immediately and cannot wait until the
automatic shut-down process is finished?
➤ Press the «OFF» key a second time.
The compressor drive and the sound enclosure fan are immediately switched off.
Switching off
Result The EMERGENCY STOP command device remains latched after actuation.
The machine is secured against an automatic restart.
Switching on
1. Turn the EMERGENCY STOP command device in the direction of the arrow to unlatch it.
2. Acknowledge any existing alarm messages.
Fault message
Further information A list of possible fault messages occurring during operation are shown in chapter 10.2.
Warning message
If maintenance work is to be carried out or if the warning is displayed before a fault, the yel‐
low warning LED flashes.
Further information A list of possible warning messages occurring during operation are shown in chapter 10.3.
Line Submenu/Segment/Text
3 Text:
■ Message text
■ –
2. Press «Enter».
The 1.1.2.1 Blower messages menu is displayed.
The third line displays the last fault or warning message.
400mbar 08:15AM 80° C Header
1.1.2.1 Blower messages Menu
0002 A c 04/16/20 01:32:49PM Last message
Overload blower motor Message text for message 0002
0015 W a 04/16/20 01:06:43PM
Bus alarm Message text for message 0015
0005 W c 04/16/20 08:15:37AM
T1 ↑ Message text for message 0005
3. Press «Enter».
The analogue data for pressures are displayed.
400mbar 08:15AM 80° C Header
2.1 Pressures Menu
p1 0.0bar Active line with inlet pressure
p2 0.0bar
dp 0.0bar
π = p2_a / p1_a 0.0
------------------------------
Drag indicator
You can adjust the running times of the drive motor (Motor) and the compressor. This may be re‐
quired after a replacement, for example.
4. Use «Down» or «Up» key to set the value for operating hours to zero.
5. Press the «Enter» key.
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
Result The operating hours for the new drive motor are set to 0 h.
3. Press «Enter».
The maintenance interval display flashes.
4. Use «Up» or «Down» to set the new value for the maintenance interval.
Keep the «Up» or «Down» key pressed to quickly change the maintenance interval in incre‐
ments of 10, 100 or 1000.
5. Press «Enter».
The setting is applied.
6. Press the «Right» arrow twice.
7. Press «Enter».
The check box will flash.
8. Press the «Up» key.
The check box is activated.
9. Press the «Enter» key.
The counter for the maintenance interval is reset.
10. Press «Escape» repeatedly to leave this menu.
The communication module features LEDs providing information about the module status.
The communication module features LEDs providing information about the module status.
The communication module features LEDs providing information about the module status.
The communication module features LEDs providing information about the module status.
The communication module features LEDs providing information about the module status.
Precondition An SD card with compatible file system (FAT32) and minimum 50 MB free memory is plugged into
the SD card slot X5 of SIGMA CONTROL 2
The write protection of the SD card has been deactivated.
Access level 2 is activated.
3. Press «Enter».
The display for the set language flashes.
4. Use «Up» or «Down» to select the desired language.
5. Press «Enter».
The setting is applied.
6. Use «Up» or «Down» to select the Save data line.
400mbar 08:15AM 80° C Header
5.6 Save data Menu
Language: en_GB English
······························
Save data :☑ Active line
······························
Eject SD card :☐
Status recognised
7. Press «Enter».
The check box Save data will flash.
8. Press «Up».
The check box is activated.
9. Press «Enter».
A security query is displayed.
10. Press «Enter».
3. Press «Up».
The check box is activated.
400mbar 08:15AM 80° C Header
5.6 Save data Menu
Language: en_GB English
······························
Save data :☑
······························
Eject SD card :☑ Active line
Status recognised
Result The SD card is securely logged off from the electronic control and can be removed without the risk
of data loss.
The messages valid for your machine are dependent on the controller and individual equipment.
1. Do not attempt fault rectification measures other than those given in this manual!
2. In all other cases:
Have the fault rectified by an authorised KAESER SERVICE technician.
Consequences:
■ The red LED flashes:
■ The controller switches the machine off.
Fault messages are identified with the letter A.
The message numbers are not numbered consecutively.
In this table, you will see "%d" for a variable value, e.g. a number, duration or I/O address.
1)
Messages 0021, 0074–0075 and 0092-0096 are customer-specific.
Complete possible causes and remedies for your defined message text (see chapter 8.8).
External message 1
0022 A Current draw of the fan Check fan
Aftercooler motor too high. Check operating conditions.
Temperature too high. Clean the aftercooler.
Aftercooler clogged.
0023 A A fault occurred in the data Call KAESER SERVICE.
USS bus transmission between con‐
communication error troller and the FC of the
compressor drive.
0024 A A diagnostic message has For more details, see the text of the diag‐
Diagnostics group alarm occurred. nostic message.
Call KAESER SERVICE.
0025 A Oil temperature is very Check the ambient and operating condi‐
T3 ⇞ high. tions.
0026 A Pressure ratio across the Inlet conditions (pressure) or back pressure
π=p2_a/p1_a ⇞ block is too high - fault. is too high.
Check filter.
Check the position of the process valves.
0027 A Inlet temperature is too Check the inlet conditions (pipe, space) -
T1 ⇟ low – Fault T1 very low. Check the ambient and operating condi‐
tions.
0028 A Blower USS bus fault Check connection and line path.
Error USS handler %d
0029 A USS Communication fault Check connection and line path.
PKW requests
failed %d %d
0030 A Error while activating the Call KAESER SERVICE.
Error FC ramp up FC.
0031 A Frequency converter fault Call KAESER SERVICE.
Motor: n min not
reached
0032 A Frequency converter fault Call KAESER SERVICE.
Heavy load monitoring
triggered
External message 2
0075 A 1)
External message 3
0080 A Alarm from vibration moni‐ Call KAESER SERVICE.
Vibration monitoring toring
VSE ⇞
0092 A 1)
Switch p1
0093 A 1)
Switch p2
0094 A 1)
Switch T1
0095 A 1)
Switch T2
0096 A 1)
Switch T3
Switch T_S
0100 A Fault of frequency convert‐ Check the manual of frequency converter
Frequency converter er provided by the custom‐ provided by the customer
group alarm er
0101 A Fault when switching on Check parametrisation of frequency convert‐
Error FC ramp up frequency converter provi‐ er provided by the customer
ded by the customer
0102 A The blower motor has not Check parametrisation of frequency convert‐
Motor: n min not reached the minimum er provided by the customer
reached speed
0103 A Difference between the Check parametrisation of frequency convert‐
Target / Actual speed target and actual speed of er provided by the customer or speed meas‐
deviation ⇞ the blower motor is too urement
much
0104 A Difference between the Check parametrisation of frequency convert‐
block speed measured and calculated er provided by the customer or speed meas‐
speed of the block is too urement
much
0140 A AFxM- valve actuator Check the actuator of the AFxM valve.
AFxM-valve actuator fault.. Check the wiring between IOM and the
error AFxM valve actuator
0141 A Control cabinet fan actua‐ Check the control cabinet fan for jamming.
Enclosure fan actuator tor fault. Check the wiring to the drive of the control
alarm cabinet fan.
Check the drive of the control cabinet fan.
0142 A AFxM- valve actuator Check the actuator of the AFxM valve.
AFxM-valve actuator fault.. Check the wiring between IOM and the
error AFxM valve actuator.
0500 A An I/O address has been Have the menu with the incorrect parametri‐
I/O parameterisation assigned more than once. sation displayed in the 1.1.3Address error
incorrect in module %d! menu and correct the parameter in there
Consequences:
■ The yellow LED flashes.
■ The controller does not switch off the machine.
Warning messages are identified with the letter W.
The message numbers are not numbered consecutively.
In this table, you will see "%d" for a variable value, e.g. a number, duration or I/O address.
Complete possible causes and remedies for your defined message text (see chapter 8.8).
External message 1
0015 W The bus link via Com module inter‐ Check bus conduits and plug.
Com-Module face is interrupted.
communication error
0016 W Oil temperature T3 too low Check ambient conditions.
T3 ↓
0017W Oil temperature T3 too high (only Check the operating conditions
T3 ↑ when used in screw blowers) → oil (max. speed/pressure)
temperature Ambient temperature too high
Cooling air feed clogged
Check the direction of rotation for
the sound enclosure fan.
Call KAESER SERVICE.
0018W Pressure ratio across the block is Inlet conditions (pressure) or back
π=p2_a/p1_a ↑ too high - warning. pressure is too high.
Check filter.
Check the position of the process
valves.
0019W Inlet temperature too low – warning. Check the inlet conditions (pipe,
T1 ↓ room)
Check the climatic conditions in the
machine environment
0020W Compressor drive motor overhea‐ Keep ambient conditions within
T_M ↑ ted. specified limits.
Check the cooling air supply.
Clean the motor.
0021W Inlet pressure too low – warning. Check the inlet conditions (pipe,
p1 ↓ room)
Check the position of the process
valves.
Severe clogging of the inlet louvre.
0022W Max. switching frequency / h excee‐ Check the operating conditions
Motor starts ↑ ded. and/or operating mode.
0023W The numerical value is the fault Call KAESER SERVICE.
FC error %d code of the frequency converter.
0024W FC in service mode Deactivate the service mode in
FC service mode menu 10.1.1.2
activated
0025W STO channels must be tested. Switch off the FC.
Test of cut-of paths
required
0026W The test operation is active. Conclude the test operation.
Machine test
measurement of block
speed active
External message 2
0075 W 1)
External message 3
0080 W Alarm from vibration monitoring Check operating conditions.
Vibration monitoring
VSE ⇞
0081 W Warning from vibration monitoring Check operating conditions.
Vibration monitoring
VSE ↑
0082 W High vibration values Call KAESER SERVICE.
Vibration monitoring
sum signal ↑
0092 W 1)
Switch p1
0093 W 1)
Switch p2
0094 W 1)
Switch T1
0095 W 1)
Switch T2
0096 W 1)
Switch T3
Switch T_S
0100 W The frequency converter provided Deactivate the service mode in
FC service mode by the customer is in service mode menu 10.1.1.3
activated
0200 W Lubricating oil: Change the lubricating oil.
Change lube h ↑ Maintenance interval has elapsed.
0201 W V-belt: Call KAESER SERVICE.
Change belt h ↑ Maintenance interval has elapsed.
0202 W Inlet filter: Replace the inlet filter.
Change filter h ↑ Maintenance interval has elapsed.
0203 W Air filter: Change the filter mat.
Change filter mat h ↑ Maintenance interval has elapsed.
0204 W Motor bearing of drive motor: Re-lubricate the motor bearing of
Motor bearings lube h Maintenance interval has elapsed. drive motor.
↑
0205 W Motor bearing of drive motor inspec‐ Check the motor bearing of drive
Check motor bearings tion. motor.
h↑
0206 W Motor bearing of drive motor: Call KAESER SERVICE.
Change motor Maintenance interval has elapsed.
bearings h ↑
0207 W Motor bearing of sound enclosure Call KAESER SERVICE.
Check motor bearings fan motor:
encl. fan h ↑ Maintenance interval has elapsed.
0208 W Motor bearing of control cabinet fan Call KAESER SERVICE.
Check control cabinet motor:
fan h ↑ Maintenance interval has elapsed.
0209 W Motor bearing of frequency convert‐ Call KAESER SERVICE.
Check FC fan h ↑ er fan motor:
Maintenance interval has elapsed.
0210 W Last maintenance was 1 year ago. Carry out the necessary mainte‐
Annual maintenance nance tasks and reset the corre‐
due sponding maintenance interval
counters.
0211 W Maintenance interval has elapsed Change the filter
Filter change
transmission venting h
↑
0212 W Maintenance interval has elapsed Carry out the necessary mainte‐
Electrical equipment h nance tasks and reset the corre‐
⇞ sponding maintenance interval
counters.
0300 W Fault while writing data to SD card. Call KAESER SERVICE.
SD card write error
Complete possible causes and remedies for your defined message text (see chapter 8.8).
Message Meaning
0011 O The optional heating has not yet heated the blower suffi‐
Waiting for cold start enabling ciently
0012 O The solenoid valve for the gear ventilation has opened
Oil return started
0013 O Currently the oil level is low. Wait for oil return, this may
Oil deficiency remedy the low oil level
Please wait for oil return
Message Meaning
0014 O The restart inhibitor is still activated. Wait until the blow‐
Restart lock-out active er starts
External message 1
0074 O 1)
External message 2
0075 O 1)
External message 3
0080 O Warning from vibration monitoring
Vibration monitoring VSE ↑
0081 O Increased vibration values
Vibration monitoring sum signal ⇡
0092 O 1)
Switch p1
0093 O 1)
Switch p2
0094 O 1)
Switch T1
0095 O 1)
Switch T2
0096 O 1)
Switch T3
0098 O 1)
Switch T_S
0300 O Service information
Cycle-exact data recording active
1000 O You successfully registered 2 RFID Equipment Cards at
2 RFID Equipment Cards successfully the controller.
registered
In the event of a fault in the bus communication, the red "Communication" and the yellow "Warn‐
ing" LEDs flash at the SIGMA CONTROL 2. The system displays the following warning message:
In addition to the 0015 W Com-Module communication error warning message, the system dis‐
plays the following information for troubleshooting:
Result The bus communication is automatically continued as soon as the cause of the fault is remedied.
In the event of a fault in the bus communication, the red "Communication" and the yellow "Warn‐
ing" LEDs flash at the SIGMA CONTROL 2. The system displays the following warning message:
In addition to the 0015 W Com-Module communication error warning message, the system dis‐
plays the following information for troubleshooting:
1. See chapter 9 for display on the communication module.
If one or both LEDs are illuminated red or blink red, contact KAESER SERVICE.
Result The bus communication is automatically continued as soon as the cause of the fault is remedied.
In the event of a fault in the bus communication, the red "Communication" and the yellow "Warn‐
ing" LEDs flash at the SIGMA CONTROL 2. The system displays the following warning message:
In addition to the 0015 W Com-Module communication error warning message, the system dis‐
plays the following information for troubleshooting:
1. See chapter 9 for display on the communication module.
If one or both LEDs are illuminated red or blink red, contact KAESER SERVICE.
Result The bus communication is automatically continued as soon as the cause of the fault is remedied.
In the event of a fault in the bus communication, the red "Communication" and the yellow "Warn‐
ing" LEDs flash at the SIGMA CONTROL 2. The system displays the following warning message:
In addition to the 0015 W Com-Module communication error warning message, the system dis‐
plays the following information for troubleshooting:
Result The bus communication is automatically continued as soon as the cause of the fault is remedied.
In the event of a fault in the bus communication, the red "Communication" and the yellow "Warn‐
ing" LEDs flash at the SIGMA CONTROL 2. The system displays the following warning message:
In addition to the 0015 W Com-Module communication error warning message, the system dis‐
plays the following information for troubleshooting:
1. For displays on the communication module, see chapter 9.
Please contact KAESER SERVICE techician if the LED MS illuminates red or flashes in a 4:1
rhythm.
2. Displays in the <Communication – Com-Module> menu.
In the 8.2 <Communication – Com-Module> menu, communication faults are displayed as text
beneath the line Status or as a number after the term Error.
Result The bus communication is automatically continued as soon as the cause of the fault is remedied.
11 Maintenance
11.1 Changing the battery
If the time and date are no longer up-to-date after you switch the supply voltage back on, the inte‐
grated battery for buffering the real-time clock is discharged and must be replaced. Contact
KAESER SERVICE. With a discharged battery, the date and time of the controller always restarts
on the 1st of January 1970 at 01:00:00 in the time zone Europe/Berlin.
3. Press «Enter».
The 5.1.1.1 SIGMA CONTROL 2 - MCS menu is displayed.
400mbar 08:15AM 80° C Header
5.1.1.1 SIGMA CONTROL 2 - MCS Menu
Software blow_2.X.X Software version
······························
KAESER
PN 7.7601.0 Material number
SN 123456 Serial number
······························
➤ Run the machine once a week for at least 30 minutes under LOAD to ensure sufficient protec‐
tion against corrosion.
If the machine is equipped with one or more condensate drain(s), drain condensate from every
condensate drain.
1. Drain condensate from all condensate drains and dispose according to applicable environment
protection regulations.
2. Remove the user-supplied condensate conduits.
The condensate drains are not supplied with power when the machine is switched off?
➤ Detach and drain the condensate drains.
4. Option W2/W3:
Detach the user connecting lines and use compressed air (<2 bar) to blow out the heat recov‐
ery system until liquid no longer escapes.
5. Properly close all open connecting ports.
13.2 Packing
➤ Follow the instructions in the machine's service manual.
13.3 Storage
➤ Follow the instructions in the machine's service manual.
13.4 Transporting
➤ Follow the instructions in the machine's service manual.
Further information Refer to the machine’s Operating Manual for details regarding the battery’s environmentally sound
disposal.
Further information Refer to the SIGMA CONTROL 2user manual for details regarding battery removal and replace‐
ment.