Load Break Switch Use
Load Break Switch Use
Technical Manual
Version 28
Notices
Scope of this This document describes the features and opera- Switch, including the installation and maintenance
Manual tion of the RL 27 Pole Mounted Load Break procedures.
Limitations
This document is copyright and is provided solely party, nor to be used as the basis of a tender or
for the use of the purchaser. It is not to be copied specification without the express written permis-
in any way, nor its contents divulged to any third sion of the manufacturer.
Disclaimer
The advisory procedures and information con- quently, this Technical Manual is offered as a guide
tained within this Technical Manual have been only. It should be used in conjunction with the cus-
compiled as a guide to the safe and effective oper- tomers own safety procedures, maintenance pro-
ation of products supplied by Nu-Lec Industries gram, engineering judgement and training
Pty Ltd.
qualifications.
It has been prepared in conjunction with refer-
ences from sub-assembly suppliers and the col- No responsibility, either direct or consequential, for
lective experience of the manufacturer. injury or equipment failure can be accepted by Nu-
In-service conditions for use of the products may Lec Industries Pty Ltd resulting from the use of this
vary between customers and end-users. Conse- Technical Manual.
Copyright
© 2004 by Nu-Lec Industries Pty Ltd.
All rights reserved. No part of the contents of these
documents may be reproduced or transmitted in
any form or by any means without the written per-
mission of the manufacturer.
iii
RL27 Load Break Switch
iv
Technical Manual
CONTENTS
1 Introduction ................................................... 1 7 Operator Control Panel.............................. 27
Role of the Sectionaliser..........................................1 Description ............................................................ 27
Product Types..........................................................1 Organisation of Liquid Crystal Display .................. 28
Control Cubicle Overview (Type FA only)................1 Turning on the Control Panel ................................ 28
Version 28 Features ................................................2 Selecting Displays................................................. 28
2 Scope of this Technical Manual .................. 3 Using the MENU, SELECT and ARROW Keys .... 29
General ....................................................................3 Display Groups ..................................................... 29
Product Types Covered by this Manual...................3 System Status...............................................................29
RL27-LBS-FA-SF6-##-##-### ........................................3 Event Log......................................................................29
RL27-LBS-A-SF6-##-##-###...........................................3 Measurement ................................................................29
RL27-LBS-MA-SF6-##-##-###........................................3 Detection .......................................................................29
Controller Version Covered by this Manual .............3 Configurable Quick Keys ...................................... 29
Software Identification System ................................3 Configurable Quick Key Selection ................................29
Operation of the Quick Key ...........................................30
Software Version Covered by this Manual...............4
Password Protection ............................................. 30
Related Documents .................................................4
Languages ............................................................ 30
3 Technical Data............................................... 5
Main Display Groups............................................. 31
Load Break Switch...................................................5
Measurement Group ............................................. 31
Operational Specifications ..............................................5
Detection Group.................................................... 32
General Specifications ....................................................5
Bushings .........................................................................6
System Status Group............................................ 32
Environmental..........................................................7 8 Work Tags and Controller Mode .............. 33
Control Cubicle ........................................................7 Definition of Local or Remote User ....................... 33
General Specifications ....................................................7 Local/Remote Mode.............................................. 33
Fault Detect and Sectionalising Functions...............8 Local Mode ...................................................................33
Remote Mode ...............................................................33
Power System Measurements.................................9
Hit and Run ........................................................... 33
Demand History .....................................................10
Work Tagging........................................................ 34
Equipment and Crating Dimensions ......................10
4 Construction and Operation ...................... 13 9 Fault Detection ........................................... 35
Overview ............................................................... 35
Overview................................................................13
Control Electronics ........................................................13
Basic Fault Detection ............................................ 35
Features.................................................................13 Upstream Recloser Operation .............................. 35
SF6 Pressure Sensing...........................................14 Fault Flags ............................................................ 35
Fault Flag Display Page................................................35
Pressure Transducer.....................................................14
Resetting the Fault Flags ..............................................36
Low Gas Interlock .........................................................14
Higher Level Settings....................................................36
Switchgear Memory ...............................................14
Operator Settings.................................................. 37
Contact Life............................................................14
Fault Reset Time................................................... 37
5 Control Cubicle ........................................... 17 Sequence Reset ................................................... 37
Connection to LBS.................................................17 Detection Settings and Detection Groups............. 37
Tropical, Moderate and Temperate Versions ........17 Changing Detection Settings ................................ 37
Equipment Panel ...................................................17 Group Copy...................................................................38
Sealing & Condensation ........................................17 Live Load Blocking................................................ 38
Mounting & Earthing ..............................................18 Inrush and Upstream Recloser Operation ............ 38
Radio Mounting Tray Space ..................................18 Purpose of Inrush Restraint ..........................................38
Auxiliary Power Source..........................................18 Operation of Inrush .......................................................39
Auxiliary Supply Control Cubicle Options ..............18 Cold Load Pickup.................................................. 39
Cable Entry ............................................................19 Cold Load Pickup Status Display ..................................40
Current Injection Point ...........................................19 Operator Control of Cold Load Pickup ..........................40
Computer Port .......................................................19 Automatic Detection Group Selection ................... 40
6 Control Electronics Operation................... 23 Enabling Automatic Selection .......................................40
Disabling Automatic Selection ......................................41
Control & Protection Module..................................23
Selection Rules .............................................................41
Operator Panel Subsystem (OPS).........................23
10 Event Log .................................................. 43
Control Cable Entry Module (CCEM).....................23
Display Updating................................................... 43
CAPM Operation....................................................23
General Overview .........................................................23
Detection Generated Events................................. 43
Normal Operations ........................................................24 Loss of Supply Events .......................................... 43
Gas Low Lockout ..........................................................24 Typical Event Log Displays................................... 44
Event Log ......................................................................24 11 Power System Measurements................. 45
Manual Lockout.............................................................24 Power System Frequency..................................... 45
v
RL27 Load Break Switch
Switchgear Terminal Designation ..........................45 LV Auxiliary Power from Dedicated Utility Transformer 73
Power Flow Direction .............................................45 Auxiliary Power from Integrated Transformer ............... 73
Real Time Displays ................................................46 18 Maintenance .............................................. 77
Maximum Demand Data Displays .........................46 Fault Finding ......................................................... 77
Monthly Maximum......................................................... 46 Control Cubicle Maintenance ................................ 77
Weekly Maximum ......................................................... 47
Fault Detection and Operation Check........................... 77
Average Demand Data Displays - Default .............47
Load Break Switch Check ..................................... 77
Average Demand - Default ........................................... 47
Average Demand - Configurable .................................. 47 Control Cubicle Electronics Check ............................... 78
12 Supply Outage Measurement .................. 49 Load Break Switch Maintenance .......................... 78
Determination of Supply Outage............................49 LBS SF6 Recharging .................................................... 79
Configuration and Display......................................49 Battery Care .......................................................... 79
Resetting the Counters and Timers .......................50 Battery Replacement .................................................... 79
Event Record .........................................................50 Replacement of Electronic Modules ..................... 80
13 Generator Control..................................... 53 Replacement of Cables ................................................ 80
Operation ...............................................................53 Abnormal Operating Conditions.................................... 80
Configuration and Display......................................53 Low Power Mode .......................................................... 80
14 Communications Interfaces .................... 55 Appendix A System Status Pages.................81
V23 Interface .........................................................55 Fault Flags ............................................................ 81
RS232 Interface .....................................................55 Operator Settings .................................................. 81
P9 Configurable Baud Rate ...................................56 Switchgear Status ................................................. 82
Operation ...................................................................... 56 Live/Dead Indication ............................................. 82
Radio/Modem Power .............................................57 Phase Voltage and Power Flow ............................ 82
Connections Into Electronics Compartment ..........57 Switchgear Terminal Designation ......................... 82
15 Input Output Expander Card ................... 59 Radio and Time Set .............................................. 82
Field Excitation ......................................................59 Switchgear Type and Ratings ............................... 83
IOEX as Local/Remote User..................................59
Switchgear Wear/General Details ......................... 83
IOEX Status Page..................................................59
Capability .............................................................. 83
Inputs - Standard Mapping ....................................60
Outputs - Standard Mapping..................................60 Options ............................................................... 83
System Healthy Indicator .......................................61 Quick Key Selection .............................................. 83
Power Consumption ..............................................61 WSOS Port P8 Comms......................................... 84
Configurable IOEX .................................................61 WSOS Port P9 Comms......................................... 84
Scope............................................................................ 61 IOEX Status .......................................................... 84
Overview....................................................................... 61 Generator Control ................................................. 85
16 Accessories .............................................. 63 Hit and Run ........................................................... 85
Test and Training Set (TTS) ..................................63 Appendix B Fault Detect and Sectionaliser
Windows Switchgear Operating System (WSOS) .63 Pages87
Electronics Compartment Computer Port (P9) ............. 63
Telemetry Port (P8) ...................................................... 63 Detection Settings................................................. 87
Outline of Operation...................................................... 63 Appendix C Measurement Pages ..................89
Remote Control Panel ...........................................64 Instantaneous Demand ......................................... 89
Secondary Voltage Injection Interface Set.............64 System Measurements ......................................... 89
17 Installation................................................. 65 Source Side Voltages ........................................... 89
Unpacking & Checking ..........................................65 Load Side Voltages ............................................... 89
Contents of Crate.......................................................... 65 Source Side Voltages ........................................... 89
Unpacking Procedure ................................................... 65
Load Side Voltages ............................................... 90
Control Cable Connection............................................. 65
Testing & Configuring ................................................... 66 Supply Outages .................................................... 90
Transport to Site ........................................................... 66 Monthly Maximum Demand .................................. 90
Site Installation ......................................................67 Weekly Maximum Demand ................................... 90
Tools Required ............................................................. 67 Average Demand .................................................. 90
Parts Required (Not supplied by the manufacturer) ..... 67 Appendix D Event Log....................................91
Site Procedure .............................................................. 67
Additional Component Installations .......................68
Appendix E Replaceable Parts & Tools ........95
HV Bare Terminal ......................................................... 68 Appendix F Control Cubicle Schematics......97
HV Cable Tail Connections........................................... 68 Appendix G Dimensions ..............................107
Surge Arrester Mounting and Terminating.................... 68 Load Break Switch .............................................. 107
Protection of Radio Equipment ..................................... 71
Mounting Bracket ................................................ 108
IOEX Cabling ................................................................ 71
Earthing ........................................................................ 71 Radio Mounting Space........................................ 108
Connection of Auxiliary Power ...............................72 Control Cubicle ................................................... 109
LV Auxiliary Power from Mains..................................... 72 Appendix H Silicone Grease Hazard Data ..111
vi
LIST OF FIGURES
Positioning of the Load Break Switch ............................................................................................................... 1
Load Break Switch Assembly ......................................................................................................................... 15
Radio mounting space ................................................................................................................................... 18
Control cubicle ............................................................................................................................................... 20
Equipment Panel ............................................................................................................................................ 21
Control System Block Diagram ...................................................................................................................... 25
Operator Control Panel .................................................................................................................................. 27
Available Quick Key functions ........................................................................................................................ 29
Four main display groups ............................................................................................................................... 31
Measurement Group pages ........................................................................................................................... 31
Detection Group pages .................................................................................................................................. 32
System Status Group pages .......................................................................................................................... 32
Supply Interruption Detection ......................................................................................................................... 35
Fault Detection and Inrush ............................................................................................................................. 39
Downstream fault detection ............................................................................................................................ 39
OCLM Formula ............................................................................................................................................... 40
Event Log example-Phase to Phase fault ...................................................................................................... 44
Sequence Reset Example .............................................................................................................................. 44
WSOS Configuration data .............................................................................................................................. 48
Connecting the control cable (1) .................................................................................................................... 65
Connecting the control cable (2) .................................................................................................................... 66
Disconnecting the control cable ..................................................................................................................... 66
LBS mounting and dimensions ...................................................................................................................... 69
HV Termination .............................................................................................................................................. 70
LV Auxiliary Supply connection ...................................................................................................................... 71
Cable tail installation ...................................................................................................................................... 72
Common earthing and LV supply ................................................................................................................... 74
Utility aux transformer and integrated external transformer ........................................................................... 75
Control cubicle-general arrangement ............................................................................................................. 97
Control cubicle-battery loom .......................................................................................................................... 98
Control cubicle-main loom connection ........................................................................................................... 99
Control cubicle-Single integrated aux power supply .................................................................................... 100
Control cubicle-Single LV aux power supply ................................................................................................ 101
Control cubicle-Integrated plus LV aux power supply .................................................................................. 102
Control cubicle - Dual low voltage auxiliary supply -110/240 Volts .............................................................. 103
Control cubicle - Dual LV aux power supply ................................................................................................ 104
Control cubicle - heater / thermostat connection .......................................................................................... 105
Control cubicle - Control cable service drawing ........................................................................................... 106
Load Break Switch dimensions .................................................................................................................... 107
Mounting Bracket dimensions ...................................................................................................................... 108
Radio mounting space ................................................................................................................................. 108
Control Cubicle dimensions ......................................................................................................................... 109
vii
RL27 Load Break Switch
viii
Introduction
1 Introduction
The RL27 Load Break Switch is a state-of-the-art, Control electronics are housed in a stand-alone
pole or pylon mounted, gas insulated, three phase stainless steel control cubicle designed to
Load Break Switch (LBS)/Sectionaliser optimised withstand the harshest of environmental
for remote control and automation schemes. conditions. An all-weather, user-friendly operator
Innovative use of a puffer interruption system control panel is provided to facilitate interface
insulated by SF6 gas, enclosed in a sealed-for-life between an operator and the controller module.
stainless steel tank ensures a long, low-
maintenance service life. A fully insulated cabling Remote monitoring and control can also be
system and a simple pole hanging arrangement all provided without the addition of a Remote
contribute to quick, low cost installation. Terminal Unit (RTU).
Role of the The Load Braek Switch (LBS) is equipped with the upstream recloser restores supply to feeders
Sectionaliser automatic sectionalising logic. The sectionalising upstream of the LBS.
logic opens the LBS during the dead time of an
The following figure of a simple network shows the
upstream recloser after it has tripped and closed a
relative positioning of the LBS downstream of a
number of times as configured by the user.
recloser.
The sectionaliser feature can be enabled or
From this figure it can be seen how a fault
disabled by an operator from the operator control
condition downstream of the LBS can be isolated
panel. When enabled, the sectionaliser uses the
and supply restored by the recloser to feeders
Supply Interruption Counter to “count” the trips of
upstream of it.
an upstream recloser during a reclose sequence.
When the counter reaches the user configured The fault condition must be rectified before the
value the LBS is automatically tripped. The LBS is manually closed to restore downstream
downstream fault is isolated from the network and supply.
Product Types Product Type MA consists of an LBS with built in Product Type A consists of Type MA with a motor
Current Transformers (CTs), Capacitive Voltage pack to provide local and remote control.
Transformers (CVTs) and switches to indicate Product Type FA consists of Type A with a control
Close, Open and Lockout. cubicle providing fault detection, current, voltage,
and power metering and sectionaliser functionality.
Control The cubicle is insulated and designed to minimise All weather access is provided to the Operator
Cubicle any temperature rise resulting from solar heating. Control Panel (OCP) through a lockable door on
Overview An internal equipment panel is used to mount all the front of the control cubicle. Vents are screened
(Type FA only) the equipment, including the batteries, storage against vermin entry and the door is sealed
capacitors, mains transformer, low voltage circuit against the outer with a rubber extrusion. All
breakers, Control And Protection Module (CAPM), electronic parts are well protected from entry of
operator control panel and radio or modem. These moisture and condensation ensuring a long
components are carefully located so that the heat lifetime.
generating parts are at the top, while the battery is Three models of control and communications
at the bottom to keep it cool. In this way battery life cubicle are available, Tropical, Moderate and
in excess of 5 years can be achieved. Temperate.
1
RL27 Load Break Switch
All three cubicles are fitted with the same charged battery, excluding telemetry radio or
electronics and incorporate the functions of an modem usage). The architecture used has the
overcurrent through-fault detector, a sensitive advantage that the switch operation is
earth fault relay and a remote terminal unit. independent of the high voltage supply, relying on
Additionally, the electronics measure line current, a set of batteries charged by the auxiliary supply.
voltage, real and reactive power, fault currents,
A communications radio or special modem can be
and store these for transmission or off-line
mounted within the control and communications
analysis.
cubicle. A V23 FSK modem and two RS232 Ports
A unique feature of the RL-Series pole mounted are included as standard equipment.
load break switch / sectionaliser is the built in
microprocessor controlled power supply. This In Product Type FA the control electronics
provides uninterrupted operation of not only the measures the making/breaking current every time
load break switch and fault detector, but also the the LBS operates.
communications radio or modem. No other power This measured current is then used to calculate
supplies are required for connection into your the amount of contact wear each interrupter has
SCADA or Distribution Automation System. suffered and the contact life remaining is reduced
Due to careful design the efficiency of all parts is accordingly. The remaining contact life is held in
extremely high, allowing a battery hold up time of the switchgear memory and can be displayed on
five days after auxiliary supply failure (from fully the OCP.
Version 28 Version 28 software provides the following new Hit and Run functionality
Features features for the RL-27 LBS: 600 baud option for communication port P8
Operator-configurable Quick Keys Communication port P9 configurable baud
rate.
2
Scope of this Technical Manual
If the identification shown on your switch’s rating Please contact the manufacturer or your local dis-
plate does not correspond to any of the following tributor for provision of the correct manual.
product types then this manual is not applicable.
RL27-LBS-FA- Fully Automatable - This model is fitted with Cur- counter, and Switchgear Cable Entry Module
SF6-##-##-### rent Transformers (CT's), Capacitive Voltage (SCEM) and supplied with a Pole Top Control
Transformers (CVT's), Motor Pack (MP), manual Cubicle (PTCC) and Control Cable (CC).
and low gas interlocks, a mechanical operations
RL27-LBS-A- Automatable - fitted with CT's, CVT's, MP, manual Many parts of this manual are specific to the
SF6-##-##-### and low gas interlocks, a mechanical operations switchgear model FA. However, “Installation” on
counter, and SCEM. To upgrade to a model FA, page 65 and “Maintenance” on page 77 are appli-
please contact your distributor. cable to model A.
RL27-LBS-MA- Manual Automatable - fitted with CT's and CVT's, Many parts of this manual are specific to the
SF6-##-##-### manual and low gas interlocks, and a mechanical switchgear model FA. However, “Installation” on
operations counter. To upgrade to models A or FA, page 65 and “Maintenance” on page 77 are appli-
please contact your distributor. cable to model MA.
Controller The Control and Protection Module (CAPM) is “CAPM 5” then this manual does not apply and
Version explained in Section 6 (page 23). you should contact the manufacturer or your local
Covered by When the Operator Control Panel is turned on the
distributor for advice on obtaining the correct man-
this Manual ual required.
display will show the controller type. See Section 7
(page 27). If it does not show either “CAPM 4” or
Software The software loaded into the controller has two operator text displays are to be in English or
Identification important identifiers: another language.
System The Software Version which has the form Note that in order to change functionality of the
XXX-XX.XX. This exactly identifies the equipment it is sometimes necessary to change
the software, sometimes the configuration and
software loaded into the program memory on sometimes both.
the controller.
In order to obtain effective technical support from
The Configuration Number which has the form
the manufacturer or your distributor it is vital to
2XXXX. This identifies the configuration note down the software version and the
loaded into the database that controls what the configuration number of your equipment and to
software will do. For example, whether the quote these when making your inquiry. Without
3
RL27 Load Break Switch
this information it is impossible for the See Section 7 (page 27) to find out how to use the
manufacturer’s Customer Service to identify the Operator Control Panel.
software and provide correct support.
The software version and the configuration A typical example of software version and
number are both shown on the Operator Control configuration would be:
Panel page
Software 528-05.00
SYSTEM STATUS-SWITCHGEAR WEAR/GENERAL
DETAILS Configuration 21421
Software The electronic controller incorporates a See Section 7 (page 27) for instructions on using
Version microprocessor. The microprocessor software can the Operator Control Panel.
Covered by be configured for different capabilities such as fault Having found this page press SELECT and use
this Manual detection, a variety of communication protocols, the ½ ¾arrow keys to view the capability list.
etc. This is called its “Software Capability”.
This manual applies if the capability declarations in
The software version and configuration determine the screen below are shown.
the functionality of the controller. (See Software
- - - - - - - - CAPABILITY - - - - - - - S
Identification System - page 3) . RL27 LBS (Intl) ManualRL2-436
To find out if this manual applies to the software/ WSOS P8 Remote ManualN00-218R05+
WSOS P9 Local ManualN00-218R05+
configuration loaded in the controller it is
necessary to display the Software Capability list on
the Operator Control Panel found on : If not, contact the manufacturer or your distributor.
SYSTEM STATUS-CAPABILITY
Related Not detailed in this document are the following top- Workshop & Field Test Procedures – A set of
Documents ics that are covered by their own manuals: instructions on how to test the LBS.
Service Procedures – A set of instructions on
Windows Switchgear Operating System
how to remove and replace the controller
(WSOS) – Used to configure the switchgear
electronics.
from a Personal Computer.
Test and Training Set (TTS) – Used to test For further information on these products refer to
control cubicles. the manufacturer or your local distributor.
Specific Telemetry Protocol Implementations -
For communications to remote control
systems.
4
Technical Data
3 Technical Data
This section details the technical specifications of Where timing, current, voltage or other
the Load Break Switch (LBS) and Pole Top Control measurement accuracy is given it is as a
Cubicle (PTCC). percentage of value unless otherwise stated.
Operational
Specifications
Type RL27-LBS-##-SF6-## 15/12/125 15/16/125 27/12/150 27/16/150
Rated Continuous Current (RMS) 630 Amp 630 Amp 630 Amp 630 Amp
Breaking Capacity
Impulse Withstand
General
Specifications
Construction
Mass of SF6 required to fill the LBS from vacuum to 100kPag 1.0kg
5
RL27 Load Break Switch
Mechanism Operation
Basic Timings
Current Transformers
Ratio 2000:1
Duty Cycle - Maximum allowable duty cycle at rated mainly active load breakingc
No Load
Close to Open repeated 10 times in 1 minute. Then Close to Open repeated 1 per minute.
Bushings
Bushing Boots
The 27kV LBS must be fitted with cable tails which are supplied with outdoor elastomeric bushing boots.
These boots suit insulated cable sized 16-32mm diameter and achieve an unscreened fully insulated
system.The characteristics of the boot are detailed below.
Creepage 770mm
Bare Terminals
The standard 15kV Load Break Switch is supplied fitted with bare terminals for cable palm connection. It may
also be fitted with cable tails instead of these terminals if required.
6
Technical Data
Creepage 500mm
HV Cablesa
Cable is usually provided by the manufacturer pre-cut and terminated to fit the Load break Switch bushings
and rated to suit the requirements of the utility. Standard HV cable supplied by the manufacturer is as follows.
a. Alternatively, cable can be supplied by the utility if appropriate (e.g. to terminate HV Aerial Bundled Cable).Contact the
manufacturer or your local distributor to check cable type for suitability. The manufacturer warrants the equipment only if
suitably insulated and water blocked cable and terminations are used.
Environmental
Control
Cubicle
General
Specifications
Standard control cable length 7m
Radio/Modem
A radio or modem may be fitted by the manufacturer or by the utility, for remote communications. Space,
power and data interfaces are provided within the control cubicle.
7
RL27 Load Break Switch
Radio/Modem Power Supply Max Current 5A for 30 sec with 20% duty cycle
Fault Detect
and
Sectionalising Fault Detect
Functions
Phase Fault Threshold Current Setting Range 10 to 1260 Amps
Definite Time for Fault to Persist Setting Range 0.05 to 100.0 sec
Sectionaliser
Faults to trip 1 to 4
8
Technical Data
Inrush Restraint
Power System
Measurements
Voltage Measurement Range (RMS Phase to Earth) 2 to 15 kV
9
RL27 Load Break Switch
Demand
History
Average Demand Sample Timesa 5, 15, 30 and 60 minutes
Event History
Minimum number of typical events stored in the event history 3,000 events
a. Configurable history can be accessed via WSOS, thus allowing the operator to select sample period and items stored.
This will affect the specified storage times.See Section 11 (page 45)
Equipment
and Crating
Dimensions Equipment Weights
Control cable 6
Control cubicle 35
HV cables (3m long, 180mm2 Al cables, qty 6) complete with bushing boots. 26
Dimensions
10
Technical Data
Width 1150mm
Depth 1200mm
Height 800mm
11
RL27 Load Break Switch
12
Construction and Operation
Overview The LBS uses “puffer” interrupters inside a fully Motor driven rotation of the operating arm
welded and sealed stainless steel tank filled with using the motor pack (where fitted) mounted at
SF6 gas. the fixed bracket beneath the tank.
Three interrupters are ganged together on a
common shaft that is driven by an over-centering Current transformers are installed inside the tank.
spring mechanism which is activated either by: These are connected to the control electronics to
provide fault indication and current measurement.
Manual rotation of the operating arm using a
hookstick from ground level. By pulling Moulded epoxy bushings with in-built capacitive
downwards on the appropriate side of the arm
voltage transformers are installed inside the tank..
the LBS can be opened or closed. The
mechanism is “operator independent” so that it These are also connected to the control
does not matter how fast or slow the arm is electronics to provide voltage sensing and
moved by the operator. measurement.
Control The control electronics are located in the The PTCC is connected to the switchgear by the
Electronics manufacturer supplied Pole Top Control Cubicle control cable which plugs into the motor pack.
(PTCC).
Caution
Features Figure 2 (page 15) and Figure 23 (page 69) detail If mounted elsewhere they must be earthed to the LBS tank.
the general assembly and operational features.
An M12 earth bolt is provided at the top of the
These include the following: tank for earthing the LBS.
A mounting bracket suitable for mounting to all If an internal arc fault condition occurs, a vent
types of power poles. Optional clamping rings at the rear of the LBS tank ruptures to vent the
that secure the bracket to circular poles, over-pressure. This eliminates the risk of
thereby negating the need for bolts through the explosion or detachment from the power pole
pole, are also available from the manufacturer and since the unit is not oil filled, a major fire
if required. hazard is eliminated.
Support legs welded to the tank which have Reflective ON (Closed) / OFF (Open) position
the multi-purpose role of protecting the LBS indicators are provided on the operating arm
during transportation, securing the optional and the underside of the tank.
surge arrester mounting bracket and enabling
Operations counter mounted behind the motor
the LBS to be mounted onto flat topped
pack.
surfaces such as pylons or footings.
Mechanical locking of the LBS mechanism is
Four carry handles welded to the upper portion
of the tank. These also provide fixed points for provided by pulling downwards on the yellow
the attachment of slings and shackles during Manual Lock handle with a hookstick. When
installation. locked, the mechanism cannot be tripped or
closed either mechanically or electrically. Pre-
27kV LBS high voltage connections are made drilled holes through the manual lock enable
with insulated cable terminated on epoxy the application of a physical locking device
bushings. The cable and bushings are covered such as a padlock to enable full lock-out
by a gripping elastomeric boot that is filled with condition.
silicone grease to form an insulated system.
The status of the mechanical Low Gas
15kV LBS high voltage connections are made
Interlock is visible through the viewing port on
at either the standard bare terminals suited for the underside of the LBS. If the gas pressure is
cable palm connection or the optional cable tail
below minimum pressure, a reflective red disc
as above.
appears in the viewing port. The mechanism is
Provision is made for the installation of surge also mechanically locked at the same time so
arresters on the frame of the LBS. that it cannot trip or close.
13
RL27 Load Break Switch
Pressure The pressure transducer is mounted at the If the gas pressure falls below a pre-set threshold
Transducer Switchgear Cable Entry Module (SCEM) Boss then an SF6 Pressure Low message is shown on
inside the tank. It is monitored by the control the operator control panel and all electrical
electronics through the SCEM to display the SF6 operations are electronically locked out. The
gas pressure at the operator control panel. threshold for the low-pressure detection is
temperature compensated.
Low Gas The second sensor is mechanical and locks out all Once triggered the interlock can only be reset by
Interlock operations if the gas pressure reduces below the the procedure for re-gassing the switch, advised
minimum safe working level. This sensor is later in this manual.
temperature compensated.
Caution
Triggering of this interlock is indicated when the Always check the gas pressure displayed at the control
cubicle and that the red disc is not visible through the
reflective red disc is visible through the viewing viewing port prior to operation of the Load Break Switch.
port on the underside of the LBS tank.
Contact Life The control electronics measures the making/ The LBS should be replaced if the remaining
breaking current every time the LBS operates. life on any phase reaches zero.
See Section 3 (page 5) for the duty rating of
This measured current is then used to calculate
the amount of contact wear each interrupter has the LBS.
suffered and the contact life remaining is reduced
accordingly.
14
Construction and Operation
15
RL27 Load Break Switch
16
Control Cubicle
5 Control Cubicle
The control cubicle supplied with the Load Break maintenance staff. Both the door and the hatch
Switch is purposely designed for outdoor pole can be padlocked for security.
mounted operation. Figure 4 (page 20) shows the cubicle’s
It features a hinged hatch for all weather access dimensions.
by operations staff and a door for access by
Connection to The Load Break Switch is connected to the control the other OPEN) and the position of the gas
LBS cubicle by the control cable. The cable plugs into interlock/mechanical interlock.
compatible ports at both the cubicle and underside Current transformers and voltage screens
of the switch. embedded in the bushings. These send
signals to the control electronics to monitor line
The control cable carries the following current, earth current and phase to earth
connections: voltages. If the control cable is disconnected
(at either end) these signals are automatically
Motor Operating Signals.
shorted by circuitry inside the Load Break
Travel switches that monitor the position of the Switch.
contacts (one switch indicating CLOSE and Signals to read and write the switch memory.
Tropical, Tropical, moderate and temperate climate temperature rarely goes above 40qC and
Moderate and versions of the control cubicle are available: occasionally goes below -5qC with a lower limit
Temperate The tropical version is well ventilated and is of -15qC.
Versions suitable for climates where the ambient
The temperate version has reduced ventilation
temperature can reach 50q and only
occasionally goes below 0qC, with a lower limit and a heater fitted to the equipment panel. It is
of -10qC. suitable for climates where the ambient
The moderate version has reduced ventilation temperature rarely goes above 40qC but can
and is used in environments where the fall as low as -30qC.
Equipment Inside the cubicle is an equipment panel with the This is housed behind a removable panel. The
Panel following key features. See Figure 4 (page 20). incoming control cable connects to P1 of the
The Mains Compartment houses LV mains CCEM, the internal wiring loom N03-505
transformers (where fitted) and miniature connects to P2 of the CCEM.
circuit breakers for batteries and auxiliary A Heater for the control cubicle can be fitted.
supply.
The Electronics Compartment houses the Running up the centre of the equipment panel is a
Control and Protection Module (CAPM) and rubber cable duct used to carry the internal wiring.
the Operator Panel Sub-System (OPS). This The equipment panel can be removed by
compartment is sealed to protect the disconnecting external connections and unbolting.
electronics from airborne pollution.
The equipment panel is arranged so the most heat
The Battery Compartment houses two 12Volt
sensitive components, the batteries, are located
batteries.
low down close to the point of air entry. In tropical
The Radio Mounting Tray is used to mount situations this ensures the batteries stay within a
the communications radio, modem or IOEX few degrees of ambient at all times thus
(where fitted), see Section 15 (page 59). This maximising their life.
hinges down to expose the radio/modem and
can be detached to allow workshop fitting of Additionally, the part which generates the most
the radio/modem. heat, the mains power supply (where fitted), is
The Control Cable Entry Module provides located at the top of the cubicle where its heating
termination and filtering for the control cable. effect on other parts is minimised.
Sealing & All vents are screened against vermin entry and the bottom without affecting the electrical or
Condensation the door is sealed with replaceable foam tape. electronic parts. The well-vented and self-heating
Complete sealing against water entry under all nature of the cubicle ensures moisture will dry out
conditions is not expected e.g. during operation in rapidly. The extensive use of stainless steel and
the rain with the hatch open. Instead, the design is other corrosion proof materials ensures the
such that if any water does enter, it will run out of presence of moisture has no detrimental effects.
17
RL27 Load Break Switch
Condensation can be expected to form under the bottom and be dried by ventilation and self
some atmospheric conditions such as tropical heating.
storms. However, due to the insulated and well- The Electronics Compartment, which houses the
vented design, any condensation will be on metal main electronic modules, is well sealed and is only
surfaces where it is of no consequence. The water opened for electronic module replacement.
runs out in the same way as any other water
entering the cubicle. Condensation will run out of
WARNING
Mounting & The control cubicle is mounted on the pole using The control cubicle must be earthed to the LBS to complete
Earthing either bolts through the pole or strapping around the earthing scheme as detailed in "Earthing" - page 71
Auxiliary The auxiliary supply is used to maintain charge on an LV Supply. In this case the control cubicle is
Power Source the sealed lead-acid batteries that provide standby fitted with a suitable transformer and its
power when auxiliary power is lost. The controller nameplate indicates the required auxiliary
monitors the status of both the auxiliary and supply voltage.
battery supplies. HV line supply to a Voltage Transformer (VT)
A low power mode is activated when the batteries fitted outside the LBS tank1. This external VT
are nearly exhausted due to loss of the auxiliary is connected to the LBS and is called an
supply. This mode minimises power consumption. Integrated HV Supply. In this case the rating
(See "Low Power Mode" - page 80) . plate on the transformer indicates its voltage
Auxiliary power comes from one of two sources: rating.
LV supplies provided by the utility. This "Connection of Auxiliary Power" - page 72 gives
connects into the control cubicle and is called details of auxiliary supply connection and earthing.
Auxiliary The control cubicle can be manufactured in a Supply from an external voltage transformer
Supply number of different auxiliary supply configurations supplied by the manufacturer.
Control such as: Dual 110/240V AC supply from an external
Cubicle Supply from an external 110V or 240V AC source.
Options source.
1. The VT is designed only for the manufacturer’s control cubicle and cannot provide power for any other purpose.
18
Control Cubicle
Dual supply from an external 110/240V AC protect the battery (centre MCB) and the auxiliary
source and external voltage transformer supplies.
supplied by the manufacturer.
When equipped for Integrated HV Supply the Aux
The configuration is indicated on the control MCB should always be closed during operation or
cubicle name plate as: testing even if the auxiliary supply transformer is
AUX SUPPLY 240VAC (or other voltage) for not energised. This ensures correct operation of
LV supply, or the memory in the LBS.
AUX SUPPLY INTEGRATED for integrated HV
For a single LV supply an AUX OUT socket can be
supply, with external VT supplied by the factory fitted as an option to provide a power outlet
manufacturer. in the control cubicle. This is shown in Figure 5
The Miniature Circuit Breakers (MCB) at the top of (page 21). For dual supplies two AUX supply
the control cubicle in the mains compartment MCB’s are fitted, one for each supply.
Cable Entry All cables enter the control cubicle from the One or two LV mains supplies (where fitted)
underside as shown in Figure 5 (page 21). Cable which run behind the equipment panel. The
entries are provided for: two 20mm holes provided for cable entry can
The control cable from the LBS that plugs into
also be used for external I/O entry if required.
connector P1 at the bottom of the battery Communication Cable/Radio Aerial (where
compartment. fitted), a 16mm hole is provided for cable entry.
Current A six way connector called the “Current Injection perform secondary injection while the LBS is
Injection Point Point” is located on the mains compartment. This connected. This allows injection of equipment in
is used with the Test and Training Set (TTS) to service without disconnection.
Computer Port A 25 way female D-type connector is located on This port is also used to upgrade electronic
the electronics compartment cover above the controller operating software, including installation
Operator Control Panel. It connects to an RS232 of new telemetry protocols.
port on the electronic controller for use with the
Windows Switchgear Operating System (WSOS)
on a portable computer.
19
RL27 Load Break Switch
20
Control Cubicle
21
RL27 Load Break Switch
22
Control Electronics Operation
Control & The main module of control electronics is the Monitoring of LBS insulant gas pressure
Protection Control and Protection Module (CAPM). through the pressure transducer and position
Module of the low gas interlock micro-switch.
The LBS accompanying this manual uses either
Controlling the DC motor to trip or close the
module version 4 (CAPM 4) or module version 5
LBS.
(CAPM 5). It is centred around a microprocessor
and carries out the following functions: Charging of the battery from the auxiliary
supply, changeover to battery on loss of
High speed sampling of the line Current auxiliary supply and disconnection when the
Transformers (CTs), calculation of RMS phase battery is exhausted.
current and earth spill current. Driving the Operator Panel Sub-system (OPS).
High speed sampling of the line Capacitive Driving the external communications interface
Voltage Transformers (CVTs), calculation of to allow monitoring and control from a remote
RMS phase/earth voltages. computer or operator over a communications
link.
Calculation of apparent, real and reactive Driving the Windows Switchgear Operating
power flows from the above. System (WSOS) over an RS232 link. The
Fault Detection functions. connector for this link is located on the
electronics compartment above the operator
Sectionaliser functions. control panel.
Monitoring of LBS auxiliary switches. The CAPM is a replaceable unit.
Operator This comprises the electronics compartment The Operator Panel Subsystem is a replaceable
Panel cover, an operator control panel with LCD display, unit.
Subsystem a membrane keyboard and its controlling
(OPS) microcomputer.
Control Cable This is located at the bottom of the battery The CCEM is a replaceable unit.
Entry Module compartment and provides termination and
(CCEM) filtering for the signals from the LBS.
CAPM Operation
General The CAPM utilises a Motorola 68332 On power-up, when the LBS is connected, the
Overview microprocessor, with non-volatile “Flash” CAPM reads the data from the Switch Cable Entry
EEPROM and 1Mbyte of volatile read/write static Module (SCEM) memory inside the LBS1. The
memory. memory data includes error check codes enabling
Non-volatile memory is used to hold programs, the CAPM to validate the data. The status of the
configuration parameters and historical data. data is displayed on the operator panel.
CAPM 4 has 2Mbytes of memory.
When a local operator presses buttons on the
CAPM 5 has 4Mbytes of memory. control panel a character is sent from the Operator
Volatile memory is used as run time Panel Subsystem to the CAPM, which then carries
workspace. out the required command.
There are no user-adjustable hardware features
on the CAPM, no links, no DIL switches and no The LBS operates when the CAPM activates the
variable resistors. Re-programming of the DC motor in the motor compartment to drive the
microprocessor can be carried out using a built-in mechanism. If the LBS fails to operate, the failure
loader from a portable computer. is recorded in the event log.
23
RL27 Load Break Switch
Normal The LBS, electronics and power supplies are a telemetry protocol or as an output on the
Operations monitored for correct operation. optional IOEX module. This data can be used for
Data is then used to generate a “system healthy” remotely monitoring the health of the LBS.
signal which is available either for transmission by
Gas Low The SF6 gas pressure inside the LBS is monitored The RL 27 also features an in-built mechanical
Lockout by the CAPM using the built-in pressure Low Gas Interlock. If operation of the interlock is
transducer. The actual pressure is displayed on initiated the mechanism is locked and cannot be
the operator control panel page:
operated. This action also generates a
SYSTEM STATUS - SWITCHGEAR STATUS: “MECHANISM LOCKED” event within the Event
SF6 Pressure Normal 100kPag
Log and is shown on:the page:
In the event of a low gas pressure fault condition
SYSTEM STATUS - SWITCHGEAR STATUS:
the same display will read: Mechanism Locked
Manual Lockout When the manual lockout is in the down position Unlocking the mechanism generates a
the mechanism is mechanically locked and cannot “Mechanism Unlocked” event and clears the
be operated. status display on the operator control panel.
This generates a Mechanism Locked event in the
event log and may be seen at the operator control
panel as a flashing title:
Switchgear Mechanically Interlocked
24
Control Electronics Operation
25
RL27 Load Break Switch
26
Operator Control Panel
Description The Operator Control Panel (OCP) is mounted Crystal Display (LCD) and keypad with switches
inside the control cubicle on the equipment and Light Emitting Diodes (LEDs) which are used
panel.The OCP consists of a four-line Liquid to select and monitor the functionality of the LBS.
OPS 0010
2 Close key Generates a Close request to the CAPM when the panel is active.
A red LED is embedded in the key. The LED is lit when the LBS‘
is closed.
3 Isolate/Enable Isolates the Close key. When the switch is in the Isolate position
Close switch the close coils in the magnetic actuator are disconnected from the
control electronics. Thus the switch provides a physical isolation
point for the control circuitry. The LBS cannot be closed and an
audible alarm in the panel will sound. The Close key operates
normally when the switch is in the Enable position.
4 Isolate/Enable Trip Isolates the Trip key. When the switch is in the Isolate position the
switch trip coils in the magnetic actuator are disconnected from the
control electronics. Thus the switch provides a physical isolation
point for the control circuitry. The LBS cannot be opened and an
audible alarm in the panel will sound. The Trip key operates
normally when the switch is in the Enable position.
5 Trip key Generates a Trip request to the CAPM when the panel is active.
A red LED is embedded in the key. The LED is lit when the LBS is
open.
6 Panel ON/OFF key The PANEL ON/OFF key turns the panel on and off.
27
RL27 Load Break Switch
The LED flashes at all times, even when the panel is turned off.
9 Enter key Activates selected Quick key setting, and restores original
display.
Organisation The four-line LCD display is structured as shown The data fields are used differently on each
of Liquid below. display page. Display pages with this format are
Crystal shown in Figure 9 (page 31).
Display - - - - - - PAGE TITLE - - - - - -
Some special display pages are different, these
Data Field 1 Data Field 2
Data Field 3 Data Field 4 are shown in the relevant sections in this manual,
Data Field 5 Data Field 6 Appendix A (page 81) and Appendix B (page 87).
Turning on the The PANEL ON/OFF key turns the panel on and When activated the control panel shows a start-up
Control Panel off. When off, the display is blank and none of the message for 5 seconds then shows the display
keys work. The panel will turn itself off if no keys page.
are pressed for ten minutes.
SYSTEM STATUS - FAULT FLAGS
If the time and date has not been set since the last
restart then the operator must set it.
Selecting The MENU key selects the display group. The ½ Where necessary changes can be made to
Displays ¾ keys select pages within the group, this is existing program settings using either of two
shown in Figure 9 (page 31). operator controlled methods at the control panel.
Therefore, to select a particular display page: The MENU, SELECT, ½ “LEFT ARROW” and ¾
“RIGHT ARROW” keys facilitate manual
1. Press the MENU key to get the desired navigation within the operator panel display pages.
group on display. The QUICK KEYS are interface keys that facilitate
2. Press ¾ to get the page or sub-group the rapid changing of operator settings.
required.
3. Press SELECT to get to the sub-page
required.
28
Operator Control Panel
Using the All settings can be changed by the following 3. Press ½ ¾ keys to change the setting to the
MENU, procedure: new value required.
SELECT and 1. Find the page on which the setting is shown Press MENU or ENTER to put the new setting
ARROW Keys as described in "Selecting Displays" - page 28. into service.
2. Press SELECT until the required setting
starts to flash.
Display Many different displays are available and are within each group display different data as shown
Groups divided into four main groups. Multiple pages in Figure 9 (page 31).
System Status Contains all status information about the LBS and Information on this display group is given in
control electronics e.g. battery low and operations Appendix A (page 81). All System Status displays
count. have the capital letter ‘S’ in the top right corner.
Event Log Shows the event record for the LBS. More
information is given in Section 10 (page 43) and in
Appendix D (page 91).
Measurement Contains all information about the HV line See Section 12 (page 49) and Appendix C (page
measurements made e.g. line current, line 89). All Measurement displays have the capital
voltages, maximum demand data. letter ‘M’ in the top right corner.
Detection Displays all the fault detection settings currently in All Detection displays have the capital letter’D’ in
use e.g. Fault Settings and Sectionalising. the top right corner.
Configurable Quick Keys give you quick access to particular Any one of the following fields can be linked to
Quick Keys settings from any screen. one of the four Quick Keys.
The fields containing settings that you will
A set of stickers is available from the manufacturer
frequently change can each be linked to a Quick
that includes the wording for each of the available
Key. You use a Quick Key for instant display and
functions. (See Appendix E (page 95) for part
selection of the linked field which, otherwise,
numbers.)
you would have to find by navigation.
You can configure the Quick Keys using the The operator can apply the sticker as required to
operator control panel or WSOS. match the selected functionality of the Quick Key. .
ACO On/Off
Cold Load On/Off
Sectionalise On/Off
Reset Flags
29
RL27 Load Break Switch
ENTER and the following screen is displayed with Press MENU or ENTER when the required
the first field flashing. function is displayed.
To configure another Quick Key press SELECT
- - - CHANGE QUICK KEY SELECTION - S
and repeat the above procedure.
Local/Remote Detect Group Only one function can be assigned to each Quick
Section ON/OFF Enter Work Tag Key.
If the operator selects a function that has been
Pressing the ARROW keys will scroll the operator assigned to another Quick Key the selection will
through the available functions. See Figure 8 revert to a blank setting.
(page 29) When a Quick key is changed an event is
generated in the Event Log.
Operation of the A Quick Key may be pressed at any time and will Pressing the ENTER key activates the newly
Quick Key display the relevant page, with the selected field selected setting and immediately restores the
flashing: original display.1
Pressing the Quick Key will continue to cycle Whenever a quick key is in use the ½ ¾ and
the flashing field through the options available. SELECT keys are disabled and pressing the
HELP key displays a special message which
details Quick Key operation.
Password Some settings require passwords to be entered 3. This sequence is repeated until the required
Protection before they can be changed. Appendix B (page number of characters has been entered.
87) details this. Once this is done the password does not need to
be entered again while the operator panel is on.
If a password protected field is selected for change However, when the operator panel turns OFF the
the user is prompted for the password. A password will need to be re-entered for further
password (which can be up to five characters in setting changes.
length) is entered in the following way:
The default factory password is <CAPM> but it
1. The½ ¾ keys are pressed until the first can be changed by the user with WSOS utility. The
character of the password is displayed. factory password does not have to be
remembered - the controller prompts the operator
2. SELECT key is then pressed. for it automatically.
Languages The OCPM language can be changed by The following languages are available:
selecting2 English (International and USA).
SYSTEM STATUS - OPTIONS 1: Language Spanish.
Portugese.
1. A particular option may not be available to the operator if it has been disabled on the “SYSTEM STATUS-OPTIONS” page
2. The changing of the language does not generate an event in the Event Log.
30
Operator Control Panel
Main Display
Groups
Oldest
Most Recent
EVENT LOG
MEASUREMENT DETECTION
Display Group Menu Display Group
Measurement
Group
31
RL27 Load Break Switch
Detection
Group
System Status
Group
FAULT FLAGS
OPERATOR SETTINGS SWITCHGEAR STATUS LIVE/DEAD INDICATION
1-2
SWITCHGEAR WEAR
and GENERAL DETAILS CAPABILITY OPTION 1 - 2 QUICK KEY SELECTION
WSOS PORT P9
HIT AND RUN WSOS PORT P8
IOEX STATUS COMMUNICATIONS
“when made available” COMMUNICATIONS
“when made available”
32
Work Tags and Controller Mode
Definition of There are three kinds of local user: to interface to a SCADA system remote
Local or The Operator Control Panel. terminal unit.
Remote User An IOEX card designated as “Local”. This A SCADA control protocol. These are always
might apply, for example, to an IOEX card designated as remote users. Full information is
used in a substation to provide control from a given in the relevant protocol manual.
panel inside a building.
A WSOS computer plugged into the computer Remote Panel - this panel provides the
port on the front of the user control panel. capability to access a maximum of five PTCC
from one location.
There are four kinds of remote user:
An IOEX card designated as “Remote”. This A WSOS computer plugged into the telemetry
might apply, for example to an IOEX card used port.
Local/Remote The Local Control/Remote Control selection1 is only be carried out by the designated local or
Mode carried out on remote users.
SYSTEM STATUS - OPERATOR SETTINGS Local/Remote does not affect automatic sectional-
ising or automatic change-over.
There is a quick key on the panel to make this fast
and easy. Setting this mode ensures closing can
Local Mode In this mode only a local user can manually close Only a local operator can apply/remove the Work
the LBS from the controller panel. Tag when the controller is in Local Mode.
This means a user can go to the control cubicle,
set local control mode and know that remote clos-
ing is disabled.
Remote Mode In this mode only a remote user can manually If the local operator is denied a close operation or
close the LBS. a Work Tag due to being in Remote Mode then the
Only a remote operator can apply/remove the operator panel will flash the message:
Work Tag when the controller is in Remote Mode. Not Allowed – Change to Local Control and/or remove Work
Tag
Hit and Run The Hit and Run feature provides a time delay Hit and Run is made available via WSOS only.
between a local operator control TRIP or CLOSE When Hit and Run is Available it is configured at:
request and when the LBS operates.
SYSTEM STATUS - Hit and Run
This feature is particularly useful in a Substation
because it allows the operator to avoid potential When Hit and Run has been made available
hazards when the LBS operates. through WSOS, it can be turned on at:
There is no change to the operation of the LBS SYSTEM STATUS - OPERATOR SETTINGS 1:Hit and Run
when Hit and Run is turned OFF. ON/Local Control ON/Remote Control ON
1. Most importantly the Local/Remote mode can only be set from the Operator Control Panel.
33
RL27 Load Break Switch
The following tables show the Hit and Run screen
and the field descriptions
Field Description
When Hit and Run is turned ON the operator has When the operator presses TRIP or CLOSE the
30 seconds to press either TRIP or CLOSE, following screen will be displayed and the
otherwise the setting will revert to the setting prior countdown will begin:
to turning Hit and Run ON.
- - - - - Hit and Run Countdown - - S
This will also occur when: TRIP will occur in 120 sec
Work Tagging Applying the Work Tag ensures that closing cannot Only a local user can apply/remove the tag when
take place at all, either by a local operator, a the controller is in Local Mode and only a remote
remote operator or automatically. Applying and user can apply/remove the tag when the controller
removing tags is password protected. is in Remote Mode.
This means that a local user can remove the Work
Work Tags are applied and removed from Tag applied by a remote user but they must first
SYSTEM STATUS - SWITCHGEAR STATUS: Work Tag put the controller into Local Mode.
OFF
If the local operator is denied a close operation
due to the Work Tag being applied, the operator
When applied the operator panel flashes the mes- panel will flash the message
sage
Not Allowed – Change to Local Control and/or remove Work
Warning – Work Tag Applied Tag
34
Fault Detection
9 Fault Detection
Overview The controller has many different detection fea- The controller stores up to ten groups of
tures, described in this section. In summary it Detection Settings that can be selected by the
operates as follows: operator, these are Detection Groups A to J.
The fault Detection Elements are Phase, In addition to the Detection Settings there are
Earth, and Sensitive Earth Fault (SEF). Each Operator Settings. This group of settings is
individual element can be programmed to log a independent of the Detection Settings and it
fault detection depending on the relevant changes the main functionality of the Load
setting. Break Switch.
Basic Fault The phase, earth and SEF fault detection ele- The current level at which the definite time timer
Detection ments are monitored with independent definite starts can be modified by a multiplier in the case of
time and fault current settings. Inrush Restraint or Cold Load Pickup.
A pickup event is generated for each element if the When all pickups have reset, a peak current event
current exceeds the fault current setting for that is generated for each element that have picked up.
element. A peak current event is a record of the maximum
A pickup normally inititates a timer which runs for current measured between fault pickup and fault
the definite time setting for that element. When reset.
this timer expires a fault is said to have occurred The Phase, Earth and SEF fault detection thresh-
and is reported in the Event Log. olds and definite times are found on: .
DETECTION SETTINGS - 2
Upstream The LBS can be configured to automatically trip in The supply interrupt count is displayed at: :
Fault Flags
Fault Flag This is the first page in the System Status menu to a fault and information on the fault history of that
Display Page appear when the panel is turned on. The display element.
identifies each detection element that could detect
1. Zero current is defined as all three phase currents less than 2.5 Amp.
35
RL27 Load Break Switch
Each element has an associated fault flag and a The Overcurrent element was the only one to
counter. If the fault flag is set thus it indicates detect a fault during the last fault sequence.
that the element detected a fault during the most There have been three overcurrent fault
recent fault sequence. If the overcurrent flag is set detections since this counter was last reset.
it will also display the phases between which the They may not have all occurred during the last
fault occurred. The counter indicates the number sequence. The last overcurrent fault detected
of faults that element has detected since the coun- involved A and B phases.
ter was last reset. The Earth Fault element has detected one
. fault since the last time its counter was reset.
This fault did not occur during the most recent
- - - - - - - - FAULT FLAGS- - - - - - - - fault sequence.
O/C 03 AB There have not been any SEF faults detected
E/F 01
SEF 00 OPS 0001 since the counters were last reset.
Each counter has a range of 00 to 99. Faults in
excess of 99 will not be recorded until the counters
have been reset.
The previous display is a typical example of this Only the overcurrent element displays the letters
page. A, B, C to identify the phase.
The page as shown indicates:
FAULT FLAGS
O/C 00
E/F 00
Field Description
O/C Phase Overcurrent The letters to the right of the O/C field identifies the phase or phases
faulted.
SEF Sensitive Earth Fault This field is not displayed when SEF is unavailable.
OPS Operations Counter The “OPS” field indicates the total number of operations performed by
the LBS.
Resetting the The fault flags may be manually reset using the The fault flags can also be reset by an operator trip
Fault Flags SELECT key at the operator control panel. or close but this does not reset the counters.
Pressing the SELECT key twice within a ten sec-
ond period resets the flags and clears all of the
RESET FLAGS
counters and phase indications. Press the key again to reset the
flags. Press the menu key to cancel.
On the first press, the following display appears
providing the operator with the option to abort the
reset operation.
Higher Level The LBS can be configured as a sectionaliser that is selected and the number of supply interrupts
Settings trips during the dead time of an upstream recloser counted exceeds the “Trip After” setting at:
after a configurable number of supply interrupts.
DETECTION SETTING - 1: Trip on Count #
Sectionalising occurs when:
The supply interrupt count is displayed on:
SYSTEM STATUS-OPERATOR SETTINGS: Sectionaliser
Auto OPERATOR SETTINGS: Supply Interrupt #
36
Fault Detection
Operator Operator Settings are different from Detection Set- Local/Remote Control selection.
Settings tings. Sectionaliser ON/OFF.
They are used by an operator, on an everyday Operational Cold Load Time and Multiplier.
basis, to set the controller into the required mode.
Selection of the Active Detection Group or
For example an operator may want to disable Sec-
tionalising and Sensitive Earth Fault prior to com- Detection OFF
mencing live line work. These operator settings are not affected by chang-
The Operator Settings are all found at: ing the Active Detection Group.
Fault Reset The fault reset time setting determines the amount If the current drops below the fault current setting
Time of time taken for a pickup to reset after the over- after a pickup but remains above the 90% level,
current that caused the pickup has gone. the definite time timer that started at pickup will
The fault reset time timer starts running after a continue to run. However even if this timer
pickup when the current falls to 90% of the fault expires, a fault will not be detected unless the cur-
current setting. If the current is still below 90% of rent rises back above the fault current setting.
the fault current setting when this timer expires,
the fault is reset. If the current returns to above the This setting is found on:
90% level before the fault reset timer expires, the
definite time timer continues uninterrupted. DETECTION SETTING - 3: Flt Reset Time ##ms
Sequence A sequence reset timer is used to reset the supply “expires” when it reaches the user set sequence
Reset interrupt counters to zero so that the next supply reset time at which a “Sequence Reset” event is
interrupt count starts again at one. then logged.
It starts timing when the Supply Interrupt count is The Sequence Reset Time is set on:
incremented. However, if the fault returns the
FAULT DETECT: Seq Reset Time 30s
detection will pick-up again and hold the sequence
reset timer at zero. The sequence reset timer
Detection Detection settings are normally applied when a Whenever a new Detection Group is activated or a
Settings and LBS is first put into service and don't need to be fault detection occurs, an event is written to the
Detection changed unless significant changes to network Event Log indicating which Detection Group is
Groups conditions occur. now in operation. The following are examples of
A detection group is a group of settings which logged events:
determines when a pickup or fault is detected for
Det Group A Active
each of the detection elements.
The CAPM4/5 controller supports up to ten com-
pletely independent detection groups referred to
as detection groups A to J. Det Group B Active
SYSTEM STATUS-OPERATOR SETTINGS: Det 'A' … 'J' All the detection parameters are programmed and
Active
stored independently for each of the groups. For
The number of detection sets (A-J) available to the example, if the Sequence Reset Time is required
operator may also be configured using the Win- to be 20 seconds in both A and B groups, then it
dows Switchgear Operating System (WSOS) pro- must be explicitly set to 20 seconds in both groups
gram. of detection settings.
Changing All detection parameters and operator settings are grammed into the CAPM. This is carried out either
Detection held in non-volatile memory on the CAPM. This through the operator panel or through Windows
Settings ensures they are retained through power interrup- Switchgear Operator System (WSOS).
tions. However, if a different CAPM is installed in a
control cubicle, or if the control cubicle is replaced, The ten groups of detection settings are pro-
then the detection parameters need to be re-pro- grammed on the detection pages and passwords
37
RL27 Load Break Switch
are required to make changes. Detection Groups the active group they do not go into service imme-
should not be changed whilst a detection diately. Instead the changes are saved into the
sequence is in progress. internal database in the controller and go into serv-
When programming detection settings the techni- ice when:
cian first selects which detection group of parame- The operator moves off the fault detection
ters to display on: group of pages.
The operator turns off the control panel.
DETECTION SETTING 1 (A - J): Group A - J Displayed The control panel turns itself off after the
timeout period.
This group can then be changed. Selecting a The controller is powered off and on again.
detection group to be displayed does not make it
active, that is done by the operator in: This allows the operator to edit the active group
and then put the new settings into service as a
OPERATOR SETTINGS: Det 'A' … 'J' Active whole. The operator is informed when the
changes are going into service.
Because one detection group can be active and
another detection group can be displayed (in the Whilst the active group is being edited, the page
detection pages), care must be taken or confusion title flashes to indicate the settings being worked
will result. However, the title line of the display on are different to the ones in service.
always shows which detection group is currently Changes can also be made by remote operators
being displayed by showing an “A",“B” to “J” using WSOS. If a WSOS operator changes set-
suffix, such as: tings, the local operator will see the page title flash
DETECTION SETTING 3 E
to indicate changes are pending. When any user
puts their changes into service, all pending
The operator can change either the active group changes (including those made by other users) go
or the inactive group. When changes are made to into service.
Group Copy Group Copy is available to facilitate the setting of Selecting the field allows the operator to scroll
several detection groups which all have the same through the available copy options as shown at
or similar settings. Appendix B (page 87).
It is possible to copy from the displayed detection Changes to detection groups are put into service
group to any of the groups available on the CAPM as for any other changes to the active detection
including the active group1. group.
This feature is accessed through the detection
group at:
DETECTION SETTING 3 (A-J Copy OFF)
Purpose of When closing onto a typical load there is always a Inrush restraint2 works by raising the phase and
Inrush Restraint short lived inrush current caused by, for example, earth Threshold Currents for a short period of time
transformer magnetisation currents, low resistance to allow the inrush to flow. The inrush time and
lamp filaments and motors starting. Inrush multiplier settings are specified on:
Restraint inhibits fault detection when inrush cur-
rent occurs. DETECTION SETTINGS 4 (A … J
1. It is not possible to replicate an existing group to itself i.e.; Detection Group “B” cannot be copied and saved as Detection
Group “B".
2. Inrush Restraint functionality does not apply to SEF
38
Fault Detection
Typical values would be 200ms with a multiplier of When the measured current at a later time
five. becomes non-zero (either through the LBS or an
upstream device being closed), inrush restraint is
Inrush Restraint is armed for operation whenever activated for the duration of the inrush restraint
the load current goes to zero (zero current is time setting. During this time, the phase, earth
defined as all three phase currents less than 2.5 and SEF elements will still pickup at their respec-
Amp). For example, when the load is discon- tive fault current settings, but the level required for
nected either by the LBS itself, or by an upstream phase and earth fault detection is raised to a new
or downstream LBS. threshold by the inrush restraint multiplier setting.
Operation of Whenever the current goes from zero to non zero, If the measured current had been still higher than
Inrush the inrush restraint timer is started. While this timer the fault current setting when the inrush restraint
is running the current threshold that must be timer expired, the definite time timer for that ele-
exceeded in order to start the phase or earth defi- ment would have started. If the current remained
nite time timers becomes the fault current setting above the fault current setting for the definite time
for those elements multiplied by the inrush setting, a fault for that element would be detected.
restraint multiplier setting. The inrush restraint
time and multiplier settings should be selected in Inrush restraint is disabled if the supply interrupt
order to mask the inrush current as shown in count is greater than zero.
Figure 14 (page 39).. In other words, if the current is zero due to the pro-
tection trip of an upstream recloser, the LBS
should have also seen the fault and its supply
interrupt count will be at least one. In this case as
shown in fig 11, the inrush restraint will be disabled
and the multiplier will not apply if the current goes
to non-zero when the upstream recloser closes.
Cold Load When a typical load has been without supply for a lated using the formula shown in Figure 16
Pickup period of time (hours) it loses its diversity. (page 40).The Operational Cold Load Multiplier is
The load is higher than usual when power is used to modify the phase and earth Threshold
restored because all the heater, refrigerator or air Current Multipliers.
conditioner thermostats have turned on. The Cold Load Pickup functionality does not apply to
longer the period without supply the greater the SEF.
loss of diversity and the higher the load current Therefore the phase and earth detection thresh-
when supply is restored. olds will increase at a rate specified by the cus-
The purpose of the Cold Load Pickup (CLP) fea- tomer when the load is turned OFF, but only up to
ture is to allow for this loss of diversity automati- the User Set Cold Load Multiplier. The controller
cally and inhibit fault detection. It works by timing calculates the new thresholds every minute.
the loss of supply to the load and then raising the For example, if the User Set Cold Load Time is
threshold current accordingly. 2 hours, the User Set Cold Load Multiplier is x2
The user specifies a multiplier and a time. The and the current has been off for 1 hour, then
controller detects when load current is zero (see the Operational Cold Load Time is 1 hour.
Inrush Restraint) and starts a timer called the Consequently the phase and earth thresholds
Operational Cold Load Time. Using this timer an are increased to equal the Operational Cold
Operational Cold Load Multiplier (OCLM) is calcu- Load Multiplier of 1.5.
39
RL27 Load Break Switch
Once load current is restored the Operational Cold The Operational Cold Load Multiplier will not
Load Timer starts to count down. This means that go above the user set Cold Load Multiplier or
the Operational Cold Load Multiplier reduces back below the user set thresholds on:
to one (1) and hence the phase and earth thresh-
DETECTION SETTINGS 4
old currents also reduce back to their values.
Note that the rate of increase and decrease of
On power up the load is assumed to be
threshold currents is the same.
diverse, i.e. the Operational Cold Load Time is
In this way, lost load diversity is automatically com- zeroed and “Cold Load IDLE” will be displayed.
pensated for. It doesn't matter where the current
was turned OFF (e.g. at the substation or at the Cold Load affects phase and earth detection
LBS) the compensation will still work. thresholds but not SEF.
The User Set Cold Load Time and the User
Set Cold Load Multiplier are set on:. Cold Load Pickup cannot be used if normal cur-
rents are expected to drop below 2.5A and
DETECTION SETTINGS 4 should be turned off.
Cold Load The operational status of the cold load pickup is Cold Load IDLE: Cold Load Pickup is
Pickup Status shown in: configured ON but Cold Load Pickup is not
Display affecting the thresholds (probably because the
load current is on and Operational Cold Load
SYSTEM STATUS - OPERATOR SETTINGS: Cold Load
Time is zero). This is the normal condition.
This can show the following states: CLP 60min X1.5mult (for example). The
display shows the Operational Cold Load Time
Cold Load OFF: Cold load pickup has been and Multiplier. This affects the detection
configured OFF in the currently active thresholds. In this example the Operational
detection group, no operator control of Cold Cold Load Time is 60mins and the Multiplier is
Load Pickup is possible. 1.5.
Operator When Cold Load Pickup is configured ON at the Zero the Operational Cold Load Time. Note
Control of Cold currently active detection group it can be further that if the load current is OFF the Operational
Load Pickup controlled by using the SELECT and the ½ ¾ Cold Load Time will start to increase.
keys. Set the Operational Cold Load Time and
SELECT and the ½ ¾keys enable the following: Multiplier to a desired value. Note that the
Operational Cold Load Time will then increase
or decrease depending on whether the load
current is OFF or ON.
Automatic Sometimes a Load Break Switch is used at a loca- In this situation the operator may have to select a
Detection tion within a supply network where the power flow different group of detection settings to compensate
Group may be in either direction depending on the config- for a change in power flow when changing the net-
Selection uration of the rest of the network. work configuration. In other situations, emergency
switching configurations may require more than
One example of this is at a network tie point. one pair of Detection Groups.
Enabling The Automatic Detection Group Selection (ADGS) ADGS is made available by setting:
Automatic function allows the appropriate Detection Group to
SYSTEM STATUS - OPTIONS 1: ADGS Allowed
Selection be selected automatically without the need for
operator intervention. It works by automatically Either the Primary or Alternate Group is
changing between Detection Groups depending selected.
on the direction of power flow. ADGS is then enabled by selecting:
SYSTEM STATUS - OPERATOR SETTINGS: Detection
Auto
40
Fault Detection
The display will show the currently active On power-down the controller saves the
detection group set by displaying: current status of Detection Auto and uses that
SYSTEM STATUS - OPERATOR SETTINGS: Auto 'A' to 'J' to determine the active Detection Group on
Active power-up.
Disabling ADGS is turned OFF (disabled) either by: Selecting a Detection Group other than
Automatic SYSTEM STATUS - OPERATOR SETTINGS: Detection
An operator change in power flow direction on
Selection the following page (e.g. changing from Source
Auto
Selection Rules Once the ADGS function is enabled the active Alternate Detection Group B, D, F, H or J is
Detection Group is automatically selected accord- used when the power flow is in the negative
ing to the following rules: direction (load to source).
There are a maximum of five pairs of ADGS
For ADGS to generate a change from Primary
Detection Groups: A & B, C & D, E & F, G & H
and I & J. Each pair consists of a primary to Alternate Detection Group the power flow
Detection Group and Alternate Detection must be greater than 50kW in the negative
Group respectively. direction (load to source) for longer than the
The number of ADGS pairs depends on how period set on
many detection sets are selected to be SYSTEM STATUS - OPTIONS: Auto Change Time 60s
available. Where an odd number of Detection
Groups have been selected, the last group To revert to the Primary Detection Group the
does not participate in ADGS. Detection Auto power flow must be greater than 50kW in the
cannot be selected with this last group active. positive direction (source to load) for longer
Primary Detection Group A, C, E, G or I is than the period set on
used when the power flow is in the positive
direction (source to load). SYSTEM STATUS - OPTIONS: Auto Change Time 60s
41
RL27 Load Break Switch
42
Event Log
10 Event Log
When the status of the control electronics or LBS Events are dated, time stamped to a 10ms resolu-
changes, events are generated which are tion and displayed in the order in which they
recorded in an Event Log for display to the opera- occurred.
tor. Examples of such events are ‘Load Supply On’
or ‘Lockout’. The ½ key scrolls the display downward to show
older events, the ¾ key scrolls the display upward
Events are viewed on the Event Log pages and to show more recent events. Pressing the ½ key
can also be up-loaded and viewed with the Win- removes the title of the display to make more room
dows Switchgear Operating System. for events. The title will only be restored when the
event log is selected again from the top level
The event log display looks like this:
menu.
- - - - - - - EVENT LOG - - - - - - - -
10/01/01 12:09:02.06 Close Coil Connect Appendix D (page 91) lists all the events in alpha-
10/01/01 12:09:03.95 Panel close req
10/01/01 12:09:37.95 Load Supply ON betical order and explains when they are gener-
ated.
Display The event log display will update automatically they are entered at the bottom of the screen and
Updating with new events if the most recent event is on the the older events are scrolled up.
bottom line of the screen. When new events occur
Detection The LBS generates events to aid the user in analy- The magnitude of the maximum RMS fault
Generated sis of faults or in testing. Events are generated currents detected by the relay. Some faults will
Events which indicate the following things: cause pickup of more than one element and
Detection 'Pickup' occurs when any of the
events are generated for these as well. These
enabled detection elements picks up (this events are not generated until all elements
event is particularly useful when current have fallen back below the setting current (i.e.
injection testing). reset). This means they will be time stamped
after the fault detection in the event log.
Switchgear fault detect. A series of events
indicate the active detection setting, whether Expiration of the sequence reset timer.
the fault was caused by phase, earth or SEF
detection elements. Supply Interruption count.
Loss of Supply The control electronics monitors voltage screens source side terminals for the time set by the user
Events embedded in the H.V. bushings to determine if the in page.
terminals are live.
SYSTEM STATUS - PHASE VOLTAGE and POWER
Live/Dead indication is shown on real time dis- FLOW: Supply Timeout 5.0s
plays (see later) when the phase/earth voltage
exceeds a user configured threshold, in page If this occurs then a 'Source Supply ON’ event
SYSTEM STATUS - PHASE VOLTAGE and POWER is generated.
FLOW:“LIVE”if > 2000V
When supply is lost on all three phases for the
Terminals are designated as Dead when the volt- Supply Timeout, a 'Source Supply OFF' event
age falls 20% below the live threshold. The live/ is generated.
dead status is used to generate events when
source supply is lost. To determine if supply is ON, The load side is also monitored to generate
the live status must be sustained on all three 'Load Supply ON' and 'Load Supply OFF'
events.
43
RL27 Load Break Switch
Typical Event A typical sequence of events for a phase/phase However, if the fault was cleared after the first trip
Log Displays fault, where an upstream recloser had instantane- has occurred, the controller will generate a
ous protection on the first trip and inverse time ‘Sequence Reset’ event once the Sequence Reset
detection on the second trip with two trips to lock- Time has expired, as shown in Figure 18
out, may result in the sequence shown in
Figure 17.
.
- - - - - - - EVENT LOG- - - - - -
- - - - - - EVENT LOG - - -
44
Power System Measurements
Power System The controller must be set for the correct power
Frequency system frequency – either 50 or 60 Hz. This is set
SYSTEM STATUS - PHASE VOLTAGE and POWER
on page: FLOW: System Freq 50/60 Hz
Switchgear The six bushings on the Load Break Switch (LBS) The first line of the display allows the operator to
Terminal are labelled I, II, III and X, XX, XXX. cycle between the six possible phase
Designation Bushings must have the correct power system combinations (ABC, ACB, BAC, BCA, CAB, CBA).
phase assigned at time of installation, a process When the operator presses the ENTER key, the
called “setting the phasing". Setting the phasing controller then orientates the currents and voltages
affects all the displays, events, etc., concerned to match the selection.
with switchgear terminals, for example: voltage After the phasing has been set, the operator
measurements, live/dead terminal displays and should record the details on the Operating
maximum current events. Instructions label affixed to the rear of the control
Phasing is set from page. cubicle door to indicate the relationship between
the bushings and phases.
SYSTEM STATUS - SWITCHGEAR TERMINAL
DESIGNATION .
II / XX Terminals B Phase P
Power Flow The switch is a symmetrical device meaning that When changed, this reverses the power flow
Direction either side can be connected to the power source. direction but not the phasing. See "Switchgear
Terminal Designation" - page 45) .
Consequently, after installation, the controller must
be configured to designate source side. This is Power flow direction setting is used to determine:
done by configuring the direction of power flow so
Whether the source or load corresponds to (I)
that positive power flows from source to load. The
or (X) on the voltage measurement displays.
engineer can configure which set of bushings
corresponds to the source and load. Which direction is positive power flow for use
on the kWh totals in the Maximum Weekly
The power flow direction is configured on Demand display and ADGS.
SYSTEM STATUS - PHASE VOLTAGE and POWER Which is the source or load for Live Load
FLOW: Source I, Load X Blocking.
45
RL27 Load Break Switch
Monthly For each calendar month, the period with the power flow irrespective of the direction
Maximum greatest average Real Power is recorded and depending on page.
displayed on the Operator Control Panel. Data
SYSTEM STATUS - PHASE VOLTAGE and POWER
displayed is as follows (each value is reset on FLOW: Power Flow Signed/Unsigned
power up):
The month/year for the peak period on display. The displayed data looks like this:
The time at the end of the peak averaging
- - - - - MONTHLY DEMAND - - - - - M
period.
Jan/2001 Total 28565kWh
The Real Power (kW) during the peak period. Peak Period 12/01/200117:15:00
This is a signed quantity unless Power Flow Peak Demand 1235kW 0.93PF
Unsigned has been selected on:
SYSTEM STATUS - PHASE VOLTAGE and POWER
FLOW: Power Flow Signed/Unsigned If there is no Monthly Demand data available the
display will look like this:
The Power Factor (PF) during the peak period.
The total integrated real power flow (kWh) - - - - - - MONTHLY DEMAND - - - - - M
during the month. In a system where power
can flow both ways this quantity will show NO MONTHLY DATA AVAILABLE
either the net energy flow (i.e.: zero if equal
energy had flowed both ways) or the total
46
Power System Measurements
Weekly For each week, the period with the greatest had flowed both ways) or the total power flow
Maximum average Real Power is recorded and displayed on irrespective of the direction depending on
the Operator Control Panel. Demand Data page.
displayed is as follows (each value is reset on
SYSTEM STATUS - PHASE VOLTAGE and POWER
power up): FLOW: Power Flow Signed/Unsigned
The date of the last day of the week for the The displayed data looks like this:
peak period on display.
The time of the end of the peak averaging - - - - WEEKLY MAXIMUM DEMAND- - - M
period. weekending 10/01/2001 total7565kWh
peakperiod 07/01/2001 17:15:00
The Real Power (kW) during the peak period.
peakdemand 31141kW 0.93 PF
This is a signed quantity unless Power Flow
Unsigned has been selected on:
SYSTEM STATUS - PHASE VOLTAGE and POWER
If there is no Weekly Demand data available the
FLOW: Power Flow Signed/Unsigned display will look like this:
The Power Factor (PF) during the peak period. - - - - WEEKLY MAXIMUM DEMAND - - M
The total Integrated Real Power flow (kWh)
during the week. In a system where power can NO WEEKLY DATA AVAILABLE
flow both ways this quantity will show either
the net energy flow (i.e.: zero if equal energy
Average The real time data is averaged over a user set screen to access the:
Demand Data period to provide average demand data that is
MEASUREMENT: SAMPLE PERIOD
Displays - then displayed on the control panel.
Default page. Press SELECT again and use the ½ ¾ keys
To set the average demand period press the to vary the displayed period. Press MENU to return
SELECT key from the: to page.
MEASUREMENT: AVERAGE DEMAND HISTORY MEASUREMENT: AVERAGE DEMAND
Average Data displayed is as follows: The displayed data looks like this:
Demand - Date and time of the end of the averaging
Default period.
- - - - - AVERAGE DEMAND - - - - - M
12/01/2001 13:45:00A Phase 123Amp
Currents in each phase averaged over the 2749 kW B Phase 128Amp
period. 0.93 PF C Phase 121Amp
Real Power (kW) averaged over the period.
This is a signed quantity unless Power Flow When first selected, the average demand display
Unsigned has been selected on: shows the most recent period.
SYSTEM STATUS - PHASE VOLTAGE and POWER To view older periods press the SELECT key and
FLOW: Power Flow Signed/Unsigned
then the ½ ¾ keys. To return to the most recent
Power Factor (PF) averaged over the period. period press the MENU key.
1. The Data Storage Time is calculated from the parameters selected from the above table and then displayed at the WSOS
screen. All data is averaged over the logging period.
47
RL27 Load Break Switch
48
Supply Outage Measurement
Determination The controller monitors the LBS terminal voltages and load side network segments are monitored
of Supply to determine when there is an outage. separately. The LBS logs the start and end time of
Outage A loss of supply voltage on one or more
each outage, the total duration and the number of
outages on each network segment. When an out-
phases for a user-set time is defined as the
start of the outage. age is detected on either segment it is timed and
the data is held in the database for future analysis.
When voltage is restored to all three phases
for the same user-set time it is defined as the
If the LBS is disconnected from the controller or
end of the outage.
the controller is powered down during an outage
The reported outage duration is the actual time
then the controller cannot determine the outage
without voltage.
duration. In such cases the outage duration data
Due to the LBS measuring voltages on both the for that specific outage is discarded. The outage
source and load terminals, outages on source side counter is maintained.
Configuration Supply Outage Measurement is configured and located in the Measurement Display Group. See
and Display displayed on the page. Appendix A (page 81).
MEASUREMENT – SUPPLY OUTAGES The following tables show the Supply Outages
screen and describe each field.
The top line of the display is the page title and the
letter “M” to the right indicates that this page is
SUPPLY OUTAGES M
49
RL27 Load Break Switch
Field Description
Duration Total duration of supply outages in hours, minutes and seconds for
both source and load-side terminals.
Maximum: 9999 hours, 59 mins, 59 sec.
- - - - - SUPPLY OUTAGES - - - - -M
Measure OutagesON Out.Duration 60s
Source Outages 3 Duration 4h14m56s
Load Outages 3 Duration6h23m24s
Resetting the To reset the counters find the page: Press the SELECT key until a counter field
Counters and flashes.
Timers MEASUREMENT – SUPPLY OUTAGES
Press ½or ¾ keys to reset the counter.
Press the MENU key to continue.
Event Record A supply outage event is logged in the event ON or OFF, resets the counters and changes the
record when the supply outage ends. Events are source and load terminals.
also logged when the operator turns this function
The Supply Outage events are listed in the table
below.
Load Out 59 m 59 s The LBS load terminals experienced a supply outage up to 59 minutes
59 seconds.
Load Out 99 h 59 m The LBS load terminals experienced a supply outage up to 99 hours
59 minutes.
Load Out 9999 h The LBS load terminals experienced a supply outage above 100
hours.
Outages ON The operator has turned ON or OFF the supply outage measurement
Outages OFF functions.
Outages reset The operator has reset the four outage counters.
Source Out 9999 h The LBS source terminals experienced a supply outage above 100
hours.
50
Supply Outage Measurement
The following example shows a typical sequence
of events where a LBS has lost supply due to an
upstream fault.
- - - - - - - - EVENT LOG - - - - - -
07/01/01 22:47:48.00 Source Supply OFF Loss of supply detected on both Source and
07/01/01 22:47:48.00 Load Supply OFF Load sides.
07/01/01 22:52:23.90 Source Out 4m 29s Supply outage is logged for source and load
07/01/01 22:52:23.90 Load Out 4m 29s sides.
51
RL27 Load Break Switch
52
Generator Control
13 Generator Control
Operation Generator control allows a generator to be When supply is restored to the system, and after
operated by an IOEX output in response to loss of the expiration of a preset time (HV Live Time) the
supply, which is sensed by the line side bushings. generator is turned off and the CAPM will close the
After a preset time period (HV Dead Time) the LBS to restore supply to the load.
CAPM will trip the LBS to isolate the load.
When the LBS opens, the CAPM, via a set of Closing is prevented when supplying the load via
IOEX contacts will turn the generator on. The the generator. This is a safety feature to prevent
generator will stay on until the supply is restored. closing onto unsynchronised supplies.
Configuration This option can be turned ON or OFF in With “Generator Control On” and the LBS in the
and Display SYSTEM STATUS - OPTIONS 1-Generator Control
open position, close is inhibited if the load side
bushings are energised.
The displayed screen is shown and described in
the following tables.
OPTIONS 1 S
Options 1 screen
Field Description
Generator Control S
GenCtrl OFF
GenCtrl ON
53
RL27 Load Break Switch
Field Description
To reconfigure the IOEX mapping for Generator Run Request” outputs should be assigned to IOEX
Control, the “Generator Control” and “Generator outputs.
54
Communications Interfaces
14 Communications Interfaces
The Control and Protection Module (CAPM) These are detailed below. In addition, a switch
provides an external communications interface for mode power supply is provided to power the radio/
connection into a communications system. modem.
RS232 Ports P8 and P9 and V23 Port P10 are not
This interface can be used by a remote computer isolated from each other or the controller
to monitor and control the LBS. Typical electronics.
applications would be connection into a SCADA Consequently, they should only be connected to
system for remote operator control or connection devices inside the PTCC that are powered by the
into a distribution automation system for automatic PTCC radio supply, including Modems, optical
control by a supervising computer. isolators, and radios.
Use of the serial ports to connect directly to other
Two physical interfaces are provided on the devices outside the PTCC may cause damage
CAPM, either interface can be used: and voids any warranty.
V23 FSK modem with radio interface signals. If V23 connection to devices outside the PTCC is
essential, the manufacturers 600 ohm interface
RS232 interface. accessory is recommended.
V23 Interface An in-built FSK modem provides half duplex V23 female 15 way “D” connector is fitted. The cable
signalling at 1200 bits per second. This interface is is run to the bottom of the radio panel. This cable
primarily designed for use with voice frequency allows a simple “personalised” cable to connect
radio systems and provides additional signals for from the standard cable to a particular radio type.
this purpose.This interface is available on CAPM The “personalised” cable can be fitted in the field
plug P10 which is a 16 way ribbon header, or a without the need to open the electronics
factory fitted cable may have been supplied to compartment. Contact the manufacturer for the
connect direct to the radio. supply of “personalised” cables suitable for
particular radio types required.
Unless a particular radio cable is ordered, a
standard cable (part number N03-530) with a Signals provided are:
Cable
P10 Pin Direction Use
(N03-530)
5 5 - 0 Volts (ground/earth)
RS232 An RS232 interface is available on CAPM plug P8 to the modem. This interface is provided to
Interface which is a standard D25 male or a factory fitted connect to conventional modems which provide
cable may have been provided to connect directly the correct signalling for the communications
55
RL27 Load Break Switch
network used, e.g. optical fibre modem or
telephone dial up modem, as follows :
1 0V (ground/earth)
6 X
7 0V (ground/earth)
9 X
10 X
11 X
12 X
13 X
14 X
15 X
16 X
17 X
18 X
19 X
20 From CAPM Data Terminal Ready (DTR)
21 X
22 X
23 X
24 X
25 X
P9 The CAPM Port P9 defaults to fixed 19200 baud, online it attempts to communicate at 19.2k baud. If
Configurable Local mode. If made available to the operator via unsuccessful it cycles through 9600, 2400, 1200,
Baud Rate WSOS, the baud rate and mode can be 600 and back to 19.2k baud until successful.
configured in the CAPM. When WSOS goes
Operation WSOS provides the capability for the operator to Set a fixed or configurable baud rate.
designate the mode of operation of the P9 port.
Designate P9 as Local or Remote.1
Port P9 can be configured by the operator when
made available via WSOS. This allows the Port P9 can be configured using WSOS or the
operator to: OCPM.
56
Communications Interfaces
The actual contents of the data rows and the field
descriptions are shown in the following table.
Baud19200 P ModeLocal P
Selection in the range 600,1200, 2400, 9600 ModeRemote
and 19200.
Radio/Modem A switched mode power supply for a radio/modem The supply is available on plug P3 of the CAPM
Power is built into the CAPM and draws its power from via a disconnect type terminal block. A factory
the auxiliary supply and/or the battery.1 fitted cable to connect directly to the radio/modem
may have been provided. Connections are as
follows:
The radio/modem power supply voltage is set by shutdown, except under special circumstances.
the user from the Operator Control Panel in the: See "Connection of Auxiliary Power" - page 72 .
The radio/modem power supply is restored when
SYSTEM STATUS -RADIO and TIME SET: Radio Supply
12 Volts
the auxiliary supply returns to normal.
page. This is a password protected parameter. The radio/modem power supply can be turned on
and off by the operator for radio maintenance
If the auxiliary power fails, battery power can be
without passwords in the
conserved by automatically shutting down the
radio/modem power supply. The shutdown takes SYSTEM STATUS -RADIO and TIME SET: Radio Supply
place after the radio holdup time, set on the: ON
Connections Connections to the CAPM (if not factory fitted) power. If these cables were not factory fitted the
Into must be run through the rubber cable ducting in slots will have been sealed with rubber cord.
Electronics the middle of the equipment panel. This ducting To run cables into the electronics compartment,
Compartment provides a sealed entry into the electronics remove the cords and use their slots.
compartment thus keeping out airborne pollution.
All cables running into the electronics
It should not normally be necessary to run compartment must be round, sheathed and
additional cables into the electronics between 9 and 10.5mm in diameter to ensure a
compartment. However, if cables must be run, good seal.
slots in the ducting have been left free for the Heatshrink sleeving can be used to increase the
purpose of connecting radio/modem data and diameter of a cable. See "Replacement of
1. The power supply is not isolated.
57
RL27 Load Break Switch
Electronic Modules" - page 80 for instructions on
removing the electronics compartment cover to
gain access to the CAPM.
58
Input Output Expander Card
Field The field excitation for IOEX inputs/outputs MUST the isolation barriers and introduce serious risk of
Excitation NOT be provided from the control cubicle battery damage or interference to the control electronics.
nor the radio power supply. Doing so will breach
IOEX as Local/ An IOEX can be designated from the IOEX Status "Definition of Local or Remote User" - page 33 for
Remote User Page as either Local or Remote User. See further information on Local and Remote Users.
IOEX Status The following page The top line of the display is the page title and the
Page SYSTEM STATUS - IOEX Status
letter “S” to the right indicates that this page is
located in the System Status Display Group. See
displays the status of the IOEX inputs and outputs Appendix A (page 81).
to assist debugging during installation and The following tables show the IOEX Status screen
maintenance. and field descriptions.
IOEX Status S
Inputs 1 – – – – * – – – – – – – 12 D Local P
Remote
Field Description
Inputs This indicates the current state of the inputs. A dash – represents the OFF
1 - - - - * - - - - - - - 12 state and an asterisk * the ON state.
Outputs This indicates the current state of the outputs. A dash – represents the
1-*-----*8 OFF state and an asterisk * the ON state.
IOEX Local Designates the IOEX to be either a local or a remote user. Refer to See
IOEX Remote "Definition of Local or Remote User" - page 33 .
Invalid Map “Invalid Map” means there is a problem with the IOEX mapping in the
database. Contact the manufacturer.
59
RL27 Load Break Switch
Field Description
Unplugged “Unplugged” is displayed if the CAPM is not receiving data from the IOEX.
Check the cabling.
Wrong Type “Wrong Type” is displayed if the IOEX hardware is detected as being
different to the mapping, contact Nu-Lec Industries.
LBS Standard Mapping See "Inputs - Standard Mapping" - page - 60 This is the title of the IOEX
map loaded and may be altered via the Configurable IOEX tool.
When the IOEX configuration is invalid or has type, the IOEX driver stops and flashes the
some other problems such as wrong hardware message : ::
Inputs - The IOEX has12 independent, optically isolated are accepted. Input Voltage range is 60–130 VAC
Standard inputs, each with Metal Oxide Varistor (MOV) or 18– 150 VDC.
Mapping protection. DC in either polarity or AC input signals
Inputs ON
Input Number Terminal Number
Load Break Switch
5 9-10 Sectionaliser ON
The LBS “close” input will only function when If the IOEX Trip input is held on while either the
the controller is set to the designated IOEX IOEX close or manual close input is activated,
mode and the Work Tag is off. For example, if the LBS will not close. This is indicated in the
the IOEX card is designated as local then the event log by a ‘Close Blocking ON’ and ‘Close
IOEX close input will only operate when the Blocking OFF’ event whenever the IOEX Trip
controller is in the Local mode of operation and input changes state.
the Work Tag is turned off. See Section 8 If both Sectionalise ON and OFF inputs are on,
(page 33). the default is Sectionalise ON.
Tripping and controlling all other settings works
in Local and Remote modes and is
independent of the Work Tag status.
Outputs - The IOEX has 8 independent voltage free relay contacts are rated for 150 VAC, 2A or 150 VDC,
Standard contact outputs, each with MOV protection. The 1A non-inductive.
Mapping
60
Input Output Expander Card
a. The IOEX contacts are not garanteed during a fast upstream auto-reclose sequence but will indicate the final steady
state condition within 150ms.
Phase Fault On On
a. The trip Source outputs do not indicate other causes of a trip such as Loss of Phase.
System The IOEX system healthy indicator is present Gas pressure normal.
Healthy when all of the following are true: Contact Life greater than 20% on all phases.
Indicator Aux Supply OK. IOEX to CAPM communications OK.
Battery Supply OK. Mechanism OK
SCEM Data Valid. Failure of any of these will cause the system
CAPM Electronics OK. healthy flag to be extinguished.
Power If an IOEX card is fitted to the control cubicle, the This is due to the current drawn by the IOEX card
Consumption battery holdup time can be affected. and its relay coils. The manufacturer’s battery
holdup time rating is based on an LBS installation
without the IOEX card fitted.
Configurable WSOS incorporates the Configurable IOEX tool This tool can be launched from within WSOS and
IOEX that allows users to generate custom I/O used to individually define each of the twelve
mappings for an IOEX card. inputs and eight outputs for an IOEX map.
Logic can be applied to each point with up to five
sets of logic or “actions” for each input and one
trigger action for each output.
Scope The Configurable IOEX tool can only create The tool can be used to read mappings from
mappings that are compatible with CAPM software previous versions of software but can only create
versions 027-07.xx (CAPM 4) and 527-07.xx files for use with the specified software versions.
(CAPM 5) or higher. The manufacturers WSOS Version 4.13 or higher
is also required to use the Configurable IOEX tool.
Overview Custom maps can now be created for an IOEX valid set of points to use when constructing logic
and loaded into a CAPM directly from WSOS. The within the tool.
types of actions that can be mapped to each input
The mappings and I/O logic are created using the
or output is dependent on the software version
tool and saved to an IOEX mapping file on the
loaded into the CAPM.
WSOS computer. Once a valid file has been
When the tool is started the user is asked to input created it is linked to the switchgear device
the software version.This is then used to retrieve a configuration in WSOS and written into the CAPM.
61
RL27 Load Break Switch
The IOEX Configuration tool is intended to be writes the new mapping into the CAPM along with
used Off-Line only. Mappings are created, saved the switchgear device configuration.
and linked to a WSOS switchgear device
When this tool is installed, a technical manual
configuration while disconnected from the
describing its operation and use is available
switchgear. Once these tasks have been
through its Help menu.
completed the user connects to the device and
62
Accessories
16 Accessories
Test and For simplified testing in the field or in the workshop also simulate the LBS and allow comprehensive
Training Set a purpose built test set called a Test and Training testing of the control electronics. The TTS is highly
(TTS) Set (TTS) is available. suited to train staff in maintenance and operations.
The TTS is a briefcase sized test set which con-
nects to the control cubicle and allows a standard The test and training set is purchased as a sepa-
secondary injection test set to be connected to rate item. For further information refer to your dis-
inject currents into the control cubicle. The TTS will tributor.
Windows Section 7 (page 27) describes the built-in operator Up-loading of historical data (e.g. event record
Switchgear control panel. An alternative interface to the opera- or demand measurements) into the computer,
Operating tor panel is the Windows Switchgear Operating which can be taken away and processed
System System (WSOS). This is a software package for a elsewhere.
(WSOS) Personal Computer (PC) that allows manage-
Automatic dial-back from the controller to the
ment, control and monitoring of a population of
WSOS PC on change of state.
Sectionalisers. WSOS is purchased as an addi-
tional item. For pricing information refer to your Embedded in the LBS controller is server software
distributor. for the WSOS package. The server provides two
WSOS provides facilities for: interfaces for connection to WSOS as described
below.
Online and Offline management of all
detection settings. Connection can be made from a PC to the WSOS
Tripping and Closing of the switchgear and server at either port but only one port can be used
other operator control functions. at any one time.
Electronics This is the computer port on the front of the elec- The port is normally used to connect a portable
Compartment tronics compartment also known as the P9 port. notebook PC for maintenance purposes such as
Computer Port See Figure 2 (page 15). downloading settings or uploading the event
(P9) It is a standard RS232 connection running at 19.2 record. This port is designated a Local User, as
kBaud unless otherwise configured. See Section defined in Section 8 (page 33), and may be config-
14 (page 55). ured as remote.
Telemetry Port This is a standard RS232 port and provides (page 55) gives details of the hardware interface.
(P8) remote access to a PC running WSOS located In some software configurations this port is used
elsewhere such as in an office or a workshop. For by other protocols, in which case it cannot be used
details of the hardware interface, please refer to for WSOS connection at the same time.
“Communications Interfaces” on page 55.
The port is configured on the
To gain remote access a modem must be installed
in the control cubicle allowing the PC to control the SYSTEM STATUS - WSOS Port P8 Communications
sectionaliser from another location. Typically the
modem is connected to a telephone line or is itself page and requires:
a digital cellular telephone modem.
The baud rate must be set to match the
The modem allows an engineer or operator to dial modem interface to allow dial-in access to
into the controller and check on the event record WSOS (this is not necessarily the same as the
or make detection setting changes. modem signalling speed, refer to the modem
In addition the controller can be configured to dial manual)
the PC automatically when events occur such as CAPM 4 possible range is 300 baud to 9.6
trip to lockout. This is called Change of State kBaud.
(COS) reporting and allows a WSOS computer to
be used as a monitoring system for a population of CAPM 5 possible range is 300 baud to 19.2
LBSs. More information is provided in the WSOS kBaud.
Technical Supplement Manual N00-402. “COS On” if Change of State Reporting is
This port is designated as a Remote User, as required. In this case a telephone number is
defined in Section 8 (page 33). Section 14 also required.
Outline of The WSOS manual supplement document tion of P8 as a remote WSOS port. In summary it:
Operation number N00-218 gives more details on the opera-
Operates as a RS232 interface.
63
RL27 Load Break Switch
Supports TXD, RXD and DCD and in turn then the modem is powered down and up
requires these signals to be supported by the again before further attempts to connect are
modem or otherwise correctly wired. made.
If communication to a WSOS PC has occurred
Once connected the controller waits for WSOS
in the last 10 seconds or DCD is asserted then
“Online” is displayed on the page. to interrogate (poll) it. Provided successful
polls take place, the controller then resets its
SYSTEM STATUS - WSOS Port P8 Communications change flags so that it will not call again until
The port uses the Hayes command set to there is another change. If at any time there is
make the dialup connection and therefore this no poll from the WSOS PC for 60 seconds
must be supported by the modem. Whilst then the controller will terminate the
dialling “Dialling” is displayed as the status. If connection using the Hayes hang-up
dialling does not result in a connection then command, or if that fails, by powering down
retries are made and if they do not succeed the modem.
Remote The remote control panel provides dual control for Control Cubicle.This panel can be used to select
Control Panel the manufacturer’s Sectionalisers installed in Sub- and monitor up to five LBS.
Station applications. The remote control panel The Remote Control Panel is purchased as an
duplicates the Operator Control Panel to provide additional item, for further information refer to your
almost identical functionality to that provided at the distributor.
Secondary The Secondary Voltage Injection Interface Set Confirm the Pole Top Control Cubicle (PTCC)
Voltage (SVIIS) enables the direct injection of low voltage and control cable connections on all the
Injection for testing of the control cubicle detection or Distri- manufacturers Pole Top LBSs.
Interface Set bution System Automation functions. The SVIIS is provided with a separate
Technical Manual N05-633. This manual
It may be used to: describes the configurations that the SVIIS
may be used within.
Inject voltage signals when connected to a
Test and Training Set. Test procedures using the SVIIS are described
in detail within the manufacturer’s “Workshop
Simulate loss of voltage on an energised and Field Test” Manual. Refer to the
sectionaliser. manufacturer or your local distributor.
64
Installation
17 Installation
Contents of Each crate includes: Control cubicle (which will normally contain
Crate Pole top LBS. two batteries unless arrangements have been
made to ship batteries separately).
Pole mounting bracket.
Control cable.
Six bushing boots with clamping rings
Six cable tails (where supplied by the
attached.
manufacturer) pre-terminated to fit into the
Six tubes of electrical silicone grease to fill
LBS bushings.
the bushing boots.
One clamping ring spanner to fit boots to the
On receipt the contents should be checked for
bushings. shipping damage and the manufacturer informed
immediately if any is found.
A mounting kit containing nuts and bolts for
bolting the mounting bracket to the LBS, pole
clamps and bolts if purchased.
Caution
Unpacking Tools required: Take great care not to drop the bracket, which weighs nearly
30kg, onto the LBS.
Procedure Wrecking bar to remove nails.
Four D shackles, two slings and crane with 3. Fit D-shackles to the lifting points on the LBS
a safe working load of 300kg to lift the LBS. and lift out of the crate onto the ground using the
Screwdriver or battery drill with 8mm socket. crane.
4. Lay the crate down on its side and remove
Procedure:
the HV cables.
1. Remove top of crate and lift out the control 5. Remove the two bolts securing the control
cable and bushing boots. Store carefully in a cubicle and slide the unit from the crate.
clean dry place.
2. Unscrew and remove the four (4) screws WARNING
located on the wall of the crate. The mounting The control cubicle weighs approx 35kg.
bracket, mounting kit and the two pieces of
wood that the screws have just been removed
from are all secured together. Lift the complete
mounting bracket out of the crate.
Caution
Control Cable When installing or testing the LBS it is necessary Never pull the plug out by the cable.
Connection to connect and disconnect the control cable.
To do this successfully requires the correct tech-
nique that is explained below with reference to
Figure 20 (page 65) and Figure 21 (page 66) and
Figure 22 (page 66)
Power down the control cubicle by switching
off all MCB’s. This should be done whenever
connecting or disconnecting the control cable
from the control cubicle
To connect: hold the plug by the long sides,
check orientation, gently locate it on the socket
and push firmly home. Check it has locked by
wriggling the plug. If the plug cannot be
pushed on with moderate force then it has not Check orientation
been located properly. Heavy force is never Figure 20: Connecting the control cable (1)
required.
To disconnect: hold the plug by the short
sides and grip hard to release the clips inside
the plug (not visible). Wriggle to allow the clips
to release and then pull the plug out.
65
RL27 Load Break Switch
Testing & The tests can be carried out on site or in the work- 1. Manual trip and close of the LBS.
Configuring shop as preferred. 2. Insulation test the high voltage connections
Unpack the crate as above and put the HV cables, to earth to check for shipping damage on the
boots and the control cable in a clean safe place high voltage side of the LBS.
where they will not be damaged or soiled. Make a 3. Configure the fault detection settings.
temporary earth connection between the control 4. Perform primary current injection as
cubicle and the LBS, this need only be 1mm² cop- required.
per wire. 5. Perform secondary current injection as
Unbolt one of the compartment cover plates from required using a Test and Training Set (TTS).
the bottom of the LBS and connect the control 6. The radio/modem plate can be unscrewed
cable to plug P1 on the Switch Cable Entry Mod- and a radio or modem fitted, connected and
ule (SCEM) located inside the compartment. See tested as required.
"Control Cable Connection" - page 65 for the cor-
rect way to connect the control cable. Caution
Once the LBS has been connected to a powered-up control
If desired the LV auxiliary supply (if cubicle, do not disconnect or turn off the control cubicle for
at least ten minutes after the last trip or close.
applicable) can be connected as shown in
Figure 25 (page 71). Attend to the battery using the care
If the LBS has an integrated power transformer instructions given in "Battery Care" - page 79 .
then a temporary auxiliary supply can be made by
connecting a fused and isolated twenty-four Volt Caution
Connecting the batteries with reverse polarity will cause
AC or thirty-six Volt DC (24VAC or 36VDC) supply damage to the electronic systems.
between terminals 2 and 3 of the terminal block in
the mains compartment. A fused, isolated, 36 Volt An application note detailing workshop and
battery is a good way to do this.1 field test procedures is available. Contact your
Turn on the battery and aux supply circuit breakers agent or distributor.
at the top of the control cubicle and carry out the It may be desirable at this time to fit the cable tails
following tests: and surge arresters to the LBS. See "Surge
Arrester Mounting and Terminating" - page 68 .
Transport to If the unpacking and testing was carried out in the and control cubicle and put back the cover
Site workshop then the LBS and control cubicle must plate on the bottom of the LBS.
be transported safely to site. It is important the fol- Either remove the batteries from the control
lowing steps are carried out: cubicle and safely transport them separately or
Turn off all control cubicle circuit breakers secure the batteries in the control cubicle.
and disconnect all auxiliary power supplies. Transport the LBS, control cubicle and all
Disconnect the control cable from both LBS parts in a safe and secure manner to site.
1. This supply connects directly to the CAPM and cannot be turned off by the control cubicle miniature circuit breakers.
66
Installation
Site Installation
Tools Required Torque wrench and metric socket set, Tools to prepare pole and HV connections
standard engineer’s tools. as required.
Standard 300gm cartridge applicator. Crane or other lift for LBS and control
(Caulking Gun). cubicle, four D shackles and slings.
Bushing boot clamping spanner. (supplied
by the manufacturer).
Parts Required Two 20mm galvanised or stainless steel Earth wire and lugs for the earthing scheme
(Not supplied by bolts with washers and nuts etc. to bolt and parts for LV mains auxiliary power
the mounting bracket to power pole. See Figure 2 connection. See Figure 27 (page 74),
manufacturer) (page 15). If the optional pole clamp has been Figure 25 (page 71), and "LV Auxiliary Power
purchased this is not required. from Mains" - page 72 .
Mounting parts for control cubicle. Either 20mm sealing cable entry glands to suit
20mm steel strapping or 10mm galvanised or auxiliary supply mains cables, 16mm sealing
stainless steel bolts, nuts, etc. See Figure 4 cable entry glands to suit Aerial or
(page 20). communications cable as required.
Fixing hardware for control cable. This is Aerial, aerial feeder cable and surge
standard 25mm sheathed conduit and can be arrester as required if a radio is fitted (unless
fixed to the pole with ties, straps, P-clips or supplied by the manufacturer).
saddles. Cable ferrites for IOEX cables (If IOEX is
fitted).
WARNING
Site Procedure It is vital that the earthing scheme described is 9. Run the earth connections as shown in
carried out Figure 27 (page 74). See "Earthing" - page 71 .
10. For LV mains supply run auxiliary wiring as
To erect and test the LBS carry out the following shown in Figure 28 (page 75). See "LV
steps. Mounting details are given in Figure 23 Auxiliary Power from Mains" - page 72 . Make
(page 69) and Figure 24 (page 70): connection inside control cubicle as shown in
See Figure 25 (page 71). Make sure the LV
1. Transport to site and carry out testing prior to
mains cable is run behind the equipment
erection as required.
panel.
2. Connect cable tails and surge arresters, if
required, before elevating or raising the Caution
LBS.See "HV Cable Tail Connections" - It is vital that the scheme described above is carried out.
page 68 and "HV Cable Tail Connections" -
page 68 . 11. For LV supply from a dedicated transformer
supplied by the utility, connect as shown in
3. Ensure that the pole is of sufficient strength
Figure 28 (page 75).
to support the LBS. A structural engineer may
be needed to calculate the stresses involved. 12. For Integrated supply from an external
transformer, connect as shown in Figure 28
4. Securely mount the LBS mounting bracket
(page 75).
on the power pole.
13. Unbolt the compartment cover plate with the
5. Lift the LBS into position and slide it on to
blanking plate from the bottom of the motor
the mounting bracket so that it hangs from the
enclosure. Remove the blanking plate and fit the
mounting bracket. Figure 2 (page 15).
control cable in its place. Connect the control
6. Bolt the LBS to the mounting bracket with cable to plug P1 on the Switch Cable Entry
the two 12mm nuts and bolts provided. Tighten Module (SCEM) located inside the
to 40 Nm. compartment, put back the compartment cover.
7. Complete the high voltage connections as See "Control Cable Connection" - page 65 for
shown in Figure 24 (page 70) or as appropriate the correct way to connect/disconnect the
for the site installation. control cable.
8. Lift the control cubicle into position and bolt 14. Run the control cable from the LBS down to
or strap to the power pole. Note that the control the control cubicle.
cubicle mounts are provided with key holes so it 15. Power down the control cubicle by switching
can be lifted onto the 10mm bolt and simply slid off all MCB’s. Note that this should be done
into position. whenever connecting or disconnecting the
control cable from the control cubicle. Remove
67
RL27 Load Break Switch
the cover of the control cubicle and feed the Trip and Close buttons to trip and close the
control cable through the bottom of the control switch.
cubicle. Connect the control cable to port P1 on 18. Mount the aerial and run aerial feed to
the Control Cable Entry Module (CCEM), as control cubicle or run external communications
shown in Figure 5 (page 21). cable to control cubicle. Use the cable entry
16. Fit batteries to the control cubicle. shown in Figure 4 (page 20) with a sealing
16mm gland.
Caution 19. The LBS is now ready for energising and
Connecting the batteries with reverse polarity will cause
damage to the electronic systems. commissioning. This should include setting the
frequency, power flow direction and the phasing.
17. Power up control cubicle by switching on all See Section 11 (page 45).
MCB’s ( batteries, auxiliary supply circuit
breakers) and test operation of LBS by using the
HV Bare This is a factory fitted option as an alternative to HV cable. Silicone grease is not required for use
Terminal insulated cable tails which enables the rapid con- with bare terminals.
nection of HV cables to the bushings. Refer to Figure 26 (page 72) for identification of
The terminal and shorter boot are fitted to the LBS cable palm connection point. This figure may also
during assembly at the factory and require no fur- be used if the terminal is to be removed and then
ther installation actions other than making and re-installed during its service life.
securing the connection between the palm and the
HV Cable Tail HV cables are supplied in one of two forms: grease provided. Start at the closed end and
Connections Fitted with a lug to be bolted to a factory
finish approx 60mm for the open end of the
fitted palm on the end of the bushing (250 or boot. Hint - as you fill the boot with grease,
400A). keep sliding it down the cable as this pushes
the grease up into the boot.
Fitted with a threaded termination that is
screwed into the bushing (630A). For cables terminated with a screw thread,
ensure the thread, locknut and bushing
In both cases the procedure is to attach the cable surfaces are clean and dry. Screw the tail into
to the bushing and then cover with the bushing the bushing by turning the whole cable tail.
boot as detailed in the following sections, refer to Tighten the brass locknut to 50 Nm using a
Figure 26 (page 72). torque wrench. Take care to apply only twisting
The bushing is supplied clean and protected forces to the terminal (no shear force).
with a plastic cap. Ensure this is undisturbed For cables terminated with a lug, smear with
and the bushing body and tin plated central aluminium jointing paste and bolt the lug to the
conductor or palm are clean and undamaged. bushing palm with the bolt provided. Tighten to
If the bushing has become soiled then clean 60Nm.
with methylated spirits. Sand or brush the Grease the surface of the bushing, and slide
aluminium palm to remove oxide. the bushing boot down over the bushing while
Grease the bushing and the conductor with rotating the boot to and fro. Fix into place using
the silicone grease provided (part number the clamping ring and spanner provided. The
LUB058044). bottom of the boot should be firmly seated on
Unpack the cable tail and bushing boots. the top of the LBS tank.
Check that the cable termination and the boot During the clamping process silicone may
are clean and undamaged. If necessary, clean bleed from the top of the boot where the cable
with methylated spirits. tail comes out. This is quite normal and can be
Push the boot down the cable to a distance assisted by sliding a small screwdriver into the
approx 1 metre from the termination (place a boot alongside the cable tail. Silicone grease
small amount of grease on the closed end of will also come out around the bottom of the
the boot to assist the boot to slide down the bushing. This is quite normal. Wipe off excess
cable). Fill the bushing boot with the silicone silicone grease with a clean cloth.
Surge Arrester Purpose designed mounting brackets are provided using bolts through pre-drilled holes. The bolts are
Mounting and for the installation of surge arresters. provided with the brackets and arresters. Connec-
Terminating The brackets are secured to the support legs tions from the surge arresters to the cable tails can
welded to the LBS tank. The brackets are secured be made by stripping off the cable tail insulation
68
Installation
69
RL27 Load Break Switch
70
Installation
and using a parallel or “T” type clamp to make the The cable tail is watertight, hence additional water
connection to the cable tail. The connection should blocking where the insulation has been removed is
be made far enough up the tail so that phase/ not required, however it is good practice to tape
phase and phase/earth clearances are main- the joint to maintain the cabling system insulation.
tained. A distance of 200mm above the bushing
boot is suggested.
Protection of It is highly advisable to connect a gas discharge an equipment panel mounting stud by the shortest
Radio type of surge arrester in the aerial feed to the possible wire. Holes are provided for a Poly-
Equipment radio. phasor, IS-B50 type bulkhead surge arrester. See
Figure 4 (page 20). A suitable type of bulkhead
Caution mount surge arrester is specified in Appendix E
Failure to protect the aerial feed in this way could result in (page 95).
complete radio and control electronics failure due to
lightning activity. Damage of this nature is not covered by
the product’s general warranty arrangements. If a surge arrester is not fitted then the co-ax earth
screen should be earthed to an equipment panel
A feed-through or bulkhead type arrester fitted to mounting stud by the shortest possible wire.
the bottom of the control cubicle is ideal. If fitted
internally the surge arrester should be earthed to
IOEX Cabling Turn off the controller before connecting the IOEX The wiring to the IOEX must be shielded with the
to the CAPM. shield bonded to the control cubicle stud only. The
To ensure electromagnetic compatibility compli- manufacturer recommends shielded 12 pair data
ance is maintained, ferrite filters should be fitted to cable with a separate common for inputs and out-
all input/output IOEX cables. A suitable type of fer- puts. Insulation must withstand a minimum of 150
rite is specified in Appendix E (page 95). V DC.
Separate the CAPM cable from input/output wiring
as much as possible.
71
RL27 Load Break Switch
aerial should be bonded to the Load Break Switch are allowed since surge currents will also flow in
or the main earth bond. those paths. This arrangement should be followed
The control cubicle is connected to this main earth on both conducting and insulating power poles.
bond by a tee-off. The control cubicle electronics The main earth bond should be physically sepa-
are internally protected from potential differences rated from the control cable as they run down the
which may occur between Load Break Switch power pole by the maximum spacing available.
frame and control cubicle frame whilst surge cur- This should be at least 200mm for wood and con-
rents are flowing down the main earth bond. No crete poles and 100mm for steel poles.
other connections to earth from the control cubicle
LV Auxiliary Where LV mains are connected to the control cubi- when surge currents are flowing. Fit additional LV
Power from cle to provide auxiliary power the connection must surge arresters to all the other LV phases (if they
Mains connect the neutral of the LV system to a tee-off exist), to balance the supply for other users con-
from the main earth bond as shown in Figure 27 nected to the LV system.
(page 74). An LV surge arrester must also be fit- If local conditions or wiring rules prohibit bonding
ted from the LV phase connection to this tee-off. the HV and LV systems in this way, providing the
This connection scheme bonds the LV and HV auxiliary supply to the control cubicle from the LV
earths and so protects the primary insulation of the mains system is not possible. Instead, use one of
auxiliary supply transformer in the control cubicle the alternative arrangements detailed below.
72
Installation
LV Auxiliary Figure 28 (page 75) shows wiring and earthing if a Figure 28 (page 75) shows how the transformer
Power from dedicated transformer is supplied by the utility. and any steelwork must be earthed to the switch-
Dedicated Note that this should not be used to supply any gear tank and one side of the transformer second-
Utility other equipment without consulting the manufac- ary earthed to the earth stud on the equipment
Transformer turer to ensure that no hazard is caused to the panel inside the control cubicle.
control cubicle electronics.
Auxiliary Power The manufacturer can also provide an external which is pre-fitted with a cable gland through the
from Integrated dedicated voltage transformer that connects hole, secure the gland, connect the auxiliary sup-
Transformer directly into the control electronics. This is called ply to the screw terminal block on the SCEM and
an Integrated Auxiliary Supply. replace the compartment cover.
An external transformer is mounted on the pole as The earthing required for an Integrated Auxiliary
shown in Figure 28 (page 75) which also shows Supply, in addition to the common earthing, is
the suggested HV connections. shown in Figure 28 (page 75).
The secondary of the external transformer con-
nects into the SCEM on the underside of the LBS.
To connect the transformer secondary remove the
SCEM compartment cover plate, pass the cable
73
RL27 Load Break Switch
74
Installation
75
RL27 Load Break Switch
76
Maintenance
18 Maintenance
Maintenance is carried out using standard electri-
cians’ and mechanics’ tools.
Fault Finding If there is a problem it may be explained in "Con- If a Test and Training Set is not available then use
trol Cubicle Electronics Check" - page 78 . If not, the switchgear check suggested below and
the fault must be traced as follows. employ substitution techniques to determine
Faults can only arise in one of the following: where the fault lies.
Load Break Switch. Faulty units can be returned for factory repair.
Control Cable.
Faulty control cables should be replaced. Faulty
Control Cubicle.
control cubicles can be checked and repaired as
indicated below.
The best way to determine which part is faulty is to
use a Test and Training Set to isolate the faulty
part.
Door Seal Check the door sealing rubber for perishing or undue hardening.
Renew the seal if unserviceable.
Control Cubicle Cleaning Check for excessive dirt on the cubicle, particularly the roof, and clean off.
Ensure the louvres are not blocked and that all cooling and water drainage
holes in the base are open.
Control Cable The control cable is a “1-1”cable. This means a direct end-to-end test of all the
connections in the control cable can be made with a DVM set to resistance. All
pins should show a 1-1 resistance less than 0.2 Ohms with no shorts between
pins.
Fitting or Replacing Heater For models fitted with a control cubicle heater Control Cubicle Schematic
Figure 37 (page 105) shows the wiring. The thermostat is located inside the
electronics compartment and is set to +15°C for correct operation.
PTCC Maintenance
Fault Detection Bypass the LBS and carry out primary injection Set manual gives procedures for in-service and
and Operation testing to check LBS detection and operation. bypassed testing of both the control cubicle and
Check Alternatively use a Test and Training Set to per- the LBS.
form secondary injection. The Test and Training
Load Break Connections to the LBS are available on the The procedure is to test the resistance between
Switch Check underside of the LBS and/or on the control cable the pins on the control cable as detailed in the fol-
connector where it plugs into P1 on the Control lowing table.
Cable Entry Module (CCEM) at the bottom of the
control cubicle. Some (but not all) of these connec-
tions can be simply tested with a hand held DVM. Caution
Do not apply any tests to the LBS other than those shown
This can show up some LBS faults with a simple below.
test.
77
RL27 Load Break Switch
21 to 11 Resistance Auxiliary travel switch, closed < 10 Ohm when LBS is tripped.
indicates the LBS is tripped >100kOhm when LBS is closed
22 to 11 Resistance Auxiliary travel switch, closed < 10 Ohm when LBS is closed.
indicates the LBS is closed >100kOhm when LBS is tripped
Control Cubicle Fault finding within the control cubicle involves problems (Aux Supply Fail and/or Battery
Electronics determining whether the fault lies in the electronic OFF) which can be traced and rectified.
Check modules, the wiring or elsewhere. The electronic If the display indicates switchgear
modules are user replaceable items. Other faults disconnected or if there are operating
require the equipment panel or the control cubicle problems then the control cable and the CCEM
to be returned to the factory. Appendix F (page 97) should be inspected and replaced as required.
gives the control cubicle wiring schematics to If the microprocessor running LED is not
assist in re-assembly of the control cubicle wiring. blinking, the most likely problem is loss of
A suggested fault finding approach is as follows: power. Check the presence of battery voltage
on the battery circuit breaker and the presence
If the microprocessor running LED on the
of aux supply on the aux supply circuit breaker
operator panel is blinking then the CAPM
and rectify as required.
micro and the Operator Panel Sub-system
(OPS) microprocessor are running. If the If power supply is present then attempt to go
operator display does not operate there is a on-line with WSOS to determine whether the
problem with the display itself and the OPS CAPM is functioning correctly. Replace the
should be replaced. CAPM or Operator Panel Sub-system as
If the display is operating, check the: required.
If this does not rectify the problem then the
SYSTEM STATUS-SWITCHGEAR STATUS
equipment panel should be returned for factory
page for an indication of any power supply repair.
Load Break No user maintenance of the LBS mechanism is areas of high atmospheric pollution more frequent
Switch required. cleaning may be appropriate.
Maintenance The LBS should be replaced if the mechanical At suitable intervals:
duty or breaking duty is exceeded. This is checked
by examining the remaining contact life on the Check that the red Low Gas Interlock disc is
Operator Control Panel. When the remaining con- not visible through the view port.
tact life in any phase approaches zero, the LBS is Check that the gas low alarm is not showing
worn out. on the operator control panel.
Every five years the bushings should be checked, If either low gas pressure indicator is active,
cleaned if necessary and the pointer checked to recharge the LBS SF6 using the gas fill adaptor
ensure it is free from mechanical obstructions. In (see next section).
78
Maintenance
LBS SF6 LBS SF6 recharging is carried out using a Gas Fill to the gas fill adaptor for safety purposes, but it
Recharging Adaptor (GFA) and a standard size-D SF6 cylinder. will not protect the LBS from overpressure. If
See Appendix E (page 95) for these part numbers. excess gas is put into the LBS it can be released
by disconnecting the gas fill adaptor from the
The LBS is refilled to a pressure of 100kPa on the
gas cylinder.
gauge, corrected by +0.68kPa for every degree
Celsius above 20q Celsius and -0.68kPa for every 7. The gauge reads high while gas is flowing,
degree below 20q Celsius. For altitudes above so you will have to monitor the pressure during
1000m it is recommended that you increase the the filling process. Do this by turning off the
gauge pressure for altitude by 9.6kPa / 1000m valve on the gauge assembly at regular intervals
above sea level. to get the correct pressure reading.
The recharging procedure is as follows: 8. At correct pressure, turn off the gauge
assembly valve and then the cylinder valve.
1. Calculate the required pressure to suit the
9. Unplug the gas fill hose valve by pushing in
ambient conditions (see above).
the knurled ring on the gas fill valve.
2. Remove the cap from the gas fill valve on
the pole side of the LBS. 10. Remove the old 'O' ring from the gas fill
valve and discard it. Clean the 'O' ring seat on
3. Connect the gas fill adaptor to the SF6
the gas fill valve and cap with a clean lint-free
cylinder and slowly open the valve on the
cloth. Grease with DOW111 silicone grease and
cylinder to bleed gas into the hose. Close the
fit a new 'O' ring. See Appendix E (page 95) for
valve on the gauge assembly when the air in the
suitable parts. Replace and re-tighten cap.
hose has been flushed.
4. Check that the regulator output pressure is 11. It is recommended you use the Gas Fill
between 50-150kPa. If it needs to be reduced, Adapter for recharging. However, other SF6
wind anti-clockwise and release a small amount charging equipment can be connected to the
of gas to check the setting. LBS with a Swagelok fitting, part number B-
QM2-S-2PF.
5. Push in the knurled ring on the gas fill valve
and plug in the mating part of the gas fill adaptor
Caution
hose. The LBS gas pressure should now be Any non-manufacturer’s equipment must be suitable for the
visible on the pressure gauge. purpose, i.e., is airtight and won’t allow over pressure. The
Swagelok fitting is not suitable for permanent sealing and
6. Open the valve on the gauge assembly to must be disconnected after the charging operation is
bleed gas into the LBS. This operation must be complete. The permanent seal is formed by the o-ring in the
base of the fill valve sealing onto the cap. This o-ring must
carried out slowly and you must take care not to be replaced after any recharging operation.
over-pressurise the LBS. A relief valve is fitted
Battery Care The battery is predicted to provide good perform- If the batteries become exhausted in service,
ance for the recommended five year service and are left for more than two weeks without
period. This is based on the battery manufacturer's auxiliary supply being restored to the control
data. No battery warranty is given by the LBS cubicle, they should be taken out, cycled and
manufacturer. In some environments, an excep- have their capacity checked before being
tionally high control cubicle temperature can mean returned to service.
a shorter battery replacement period. Consult the
manufacturer if you suspect your environment to To cycle a battery, discharge with a 10 Ohm 15
be excessively hot. Watt resistor to a terminal voltage of 10V. Next,
recharge it with a voltage regulated DC supply set
Once in service, batteries need little care. Proce-
to 13.8V. A 3A current limited supply is appropri-
dures for storage and other contingencies are as
ate.
follows:
Batteries should be stored at a temperature of Battery type is given in Appendix E (page 95).
between -10qC to 30qC and cycled every six More information on the battery care is available
months. Batteries should be stored for a from the battery manufacturer.
maximum of one year.
Batteries should be cycled prior to putting into
Caution
service if they have not been cycled within These batteries are capable of supplying very high currents.
three months. When shipped by the Always turn off the battery circuit breaker before connecting
or disconnecting the batteries in the cubicle. Never leave
manufacturer the batteries will have been flying leads connected to the battery.
cycled within the previous 30 days.
Battery Battery replacement is recommended after a 1. Turn off the battery LBS.
Replacement period of five years. See "Battery Replacement" - 2. Unplug batteries and replace with new
page 79 . batteries. Ensure that polarity is correct.
The procedure is:
79
RL27 Load Break Switch
3. Turn on the battery LBS and ensure that
“Battery Normal status”, is restored on the:.
SYSTEM STATUS-SWITCHGEAR STATUS
display page.
Replacement Electronic modules are user replaceable as the ¼ inch spacer underneath the board with a
of Electronic detailed below. These modules can be damaged spanner and remove the four M4 screws.
Modules by static electricity, water, dirt and mishandling. The electronics compartment houses the Control
Therefore replacement should only be carried out and Protection Module (CAPM) and the trip and
in a suitable place such as a workshop and carried close capacitors. The compartment cover itself
out by competent personnel. forms part of the Operator Panel Subsystem
(OPS). For access to these parts refer to CAPM
Access to the Control Cable Entry Module Replacement Procedure in the service manual.
(CCEM) is by removing its cover plate held in See Appendix F (page 97) for control cubicle wir-
place by fixing screws. To remove the CCEM, hold ing schematics.
Abnormal The operation of the CAPM can be affected under capacity is very low. The following features are
Operating abnormal conditions such as when the battery used to protect the controller in this situation.
Conditions
Low Power When the batteries are nearly exhausted, the con- formed. If an operator trip or close request is
Mode troller will change its mode from normal to low denied, a “Denied Battery Low” event will be
power. A 'Low Power Mode' event is logged when- logged.
ever this happens.
To return to normal power mode, either replace the
In low power mode the radio supply is shut down. batteries or re-establish the auxiliary supply for a
and close and trip operations can not be per- minimum of 15 minutes.
80
Appendix A System Status Pages
This appendix shows all the System Status group Where the display field can show alternative text,
of pages on the Operator Control Panel display. all the different text displays are shown in the
table, one below the other.
For more information on the data refer to
Section 7 (page 27). This is illustrated in the table below, which shows
The top line of the display is the page title. To the the page.
right of the title is a letter, these have significance SYSTEM STATUS - OPERATOR SETTINGS
as follows:
Here the first data field can be either:
S System Status Display Group
Local Control ON, or
D Detection Display Group
Remote Control ON
M Measurement Display Group
To the right of the data field column is a small col-
umn showing the type of data displayed, these
The next three lines are the data on display. Most have significance as follows:
displays have six data fields. These are shown in
the following tables
O Operator Controlled
Where a display field contains a numeric value,
the table gives a typical value or the default value if D Display Only
(i.e. cannot be changed)
applicable.
For example Seq Reset Time 30.0 sec is shown P Password Protected
(i.e. can only be changed if the password is known)
for the sequence time setting. When the user
comes to the display it would show Seq Reset R Operator Controlled Reset
Time 25.0 sec if that was the actual setting1. (i.e. resets a field or group of fields)
Fault Flags
FAULT FLAGS S
O/C 00 ABC I R
E/F 00 I R
Operator
Settings
OPERATOR SETTINGS 1 S
LOCAL CONTROL ON O O
Remote Control On
Hit and Run ON
Hit and Run OFF
Sectionaliser OFF O
Sectionaliser Auto
OPERATOR SETTINGS 2 S
81
RL27 Load Break Switch
Switchgear
Status
SWITCHGEAR STATUS S
Live/Dead
Indication
LIVE/DEAD INDICATION S
Ai Live D Ax Live D
Ai Dead Ax Dead
Bi Live D Bx Live D
Bi Dead Bx Dead
Ci Live D Cx Live D
Ci Dead Cx Dead
Phase Voltage
and Power PHASE VOLTAGE and POWER FLOW S
Flow
“LIVE” if > 2000V P Supply Timeout 4.0s P
Switchgear
Terminal
Designation SWITCHGEAR TERMINAL DESIGNATION S
I / X Terminals A Phasea P
II / XX Terminals B Phase P
a. The phase designations can be rotated from this field by pressing the arrow key (ABC, ACB, BAC, BCA, CAB, CBA).
Radio and
Time Set RADIO and TIME SET S
82
Switchgear
Type and
Ratings SWITCHGEAR TYPE and RATINGS S
Switchgear
Wear/General
Details SWITCHGEAR WEAR/GENERAL DETAILS S
Capability
CAPABILITY S
a. Some software configurations will support another protocol on Port P8 as an alternative to WSOS.
Options
OPTIONS 1 S
OPTIONS 2 S
Quick Key
Selection
QUICK KEY SELECTION S
83
RL27 Load Break Switch
WSOS Port P8
Comms WSOS Port P8 Communications S
P8 Not Available D
Offline
Dialling
Online
WSOS Port P9
Comms
WSOS Port P9 Communications S
a. The default may not be LOCAL if the CAPM database is configured differently.
IOEX Status
IOEX Status S
Inputs 1 – – – – * – – – – – – – 12 D Local P
Remote
84
Generator
Control
Generator Control S
GenCtrl OFF O
GenCtrl ON
85
RL27 Load Break Switch
86
Appendix B Fault Detect and Sectionaliser Pages
This appendix shows all the Detection Group of
pages on the Operator Control Panel display.
Detection .
Settings DETECTION SETTINGS 1 (A – J) P
a.Use the select key to scroll through these options. When either the ENTER or MENU key is pressed, the copy is performed and
the field defaults to the “Copy OFF” display.
b. Advises failure of the copy feature.
DETECTION SETTINGS 2 (A – J) P
DETECTION SETTINGs 3 (A – J) P
DETECTION SETTINGS 4 (A – J) P
87
RL27 Load Break Switch
88
Appendix C Measurement Pages
This appendix shows the Measurement Group of Refer to Section 12 (page 49) for more information
pages on the Operator Control Panel display. on measurement functionality.
Instantaneous
Demand
INSTANTANEOUS DEMAND M
System
Measurements
SYSTEM MEASUREMENTS M
Source Side
Voltages
SOURCE SIDE VOLTAGESa M
a. Phase to earth.
Load Side
Voltages LOAD SIDE VOLTAGESa M
a. Phase to earth.
Source Side
Voltages
SOURCE SIDE VOLTAGESa M
D
Ai – Bi phase to phase 22000 Volt
D
Bi – Ci phase to phase 22000 Volt
a. Phase to phase.
89
RL27 Load Break Switch
Load Side
Voltages LOAD SIDE VOLTAGESa M
D
Bx – Cx phase to phase 22000 Volt
D
Cx – Ax phase to phase 22000 Volt
a. Phase to phase.
Supply
Outages SUPPLY OUTAGES M
Monthly
Maximum MONTHLY MAXIMUM DEMAND M
Demand JAN/2001 Total 28865 kWh D
Weekly
Maximum WEEKLY MAXIMUM DEMAND M
Demand Week ending 10 / 01 / 2001 Total 7565 kWh D
Average
Demand AVERAGE DEMAND M
90
Appendix D Event Log
The following table lists the events that can appear
in the Event Log, in alphabetical order.
A/B/C Phase Fault The indicated element has exceeded its fault threshold for its set amount of time.
A Max NN Amp Following pickup of the overcurrent detection element on A, B or C phase, the maximum fault current
B Max NN Amp recorded was NN Amps. This event is logged only after the current has fallen back below the phase setting
C Max NN Amp current.
Aux Supply Normal The auxiliary power supply has become normal.
Battery Low Volts The battery voltage is below the low battery threshold.
Battery Overvolt The battery voltage is too high. This will only occur if there is a battery charger hardware failure.
The above events may be generated if there is a problem with the on-board capacitor charging circuit or if
there has been a large number of operations in a short period of time, e.g. 10 operations within 60 seconds.
Chrg Charge OK
Chrg Charging
Chrg Disable
Chrg Full
Chrg OFF
Chrg Resting
Chrg Run-up
The above events may be logged if the CAPM fails to trip or close when the internal logic expects it to.
Capmload Reset The electronic controller has been reset after loading new software.
Close Blocking OFF The LBS will now close when requested.
Close Coil Connect The Close/Trip solenoid isolate switch on the operator control panel was changed to the Enable/Isolate
Close Coil Isolate position.
Denied Battery Low Operation denied if either a Trip or Close request is made when the CAPM is in 'Low Power Mode'
Denied Gas Low This event is recorded if an operation is attempted with SF6 pressure low.
Denied Wrong Mode When the switch is in a different mode (Local, Remote or Work Tag Applied) to the device which attempted
the close.
Det Group # Active Indicated the detection group that is in service when a new group is selected or just before logging a pickup.
# may be A to J.
E Max NN Amp Following pickup of the overcurrent detection element on earth or SEF, the maximum fault current recorded
was NN Amps.
This event is logged only after the current has fallen back below the earth setting current.
Earth Fault The indicated element has exceeded its fault threshold for its set amount of time.
Excess Motor Ops Indicates that a Trip or Close request has been made:
§ After there has been 10 or more operations within a 60 second period and more than 1 operation per 60
seconds for 600 seconds thereafter.
GenCtrl Trip Req Generator control opening switch in preparation for starting the generator.
GenCtrl Close Req Generator control closing switch to restore line supply.
91
RL27 Load Break Switch
IOEX InputXX On IOEX Input XX has changed from the Off state to the On state (where XX is from 01 to 12).
IOEX InputXX Off IOEX Input XX has changed from the On state to the Off state (where XX is from 01 to 12).
IOEX OutputXX On IOEX Output XX has changed from the Off state to the On state (where XX is from 01 to 08).
IOEX OutputXX Off IOEX Output XX has changed from the On state to the Off state (where XX is from 01 to 08).
LBS Open On power up and switch re-connection the LBS is either open or closed.
LBS Closed
Live Load Blocking A close request was disregarded due to a load side terminal being alive.
Load out 59 m 59 s The LBS load terminals experienced a supply outage up to 59 minutes 59 seconds.
Load out 99 h 59 m The LBS load terminals experienced a supply outage up to 99 hours 59 minutes.
Load out 9999 h The LBS load terminals experienced a supply outage above 100 hours.
Load Supply OFF/ON All three load side voltages are OFF/ON.
Loader: Close Iso The close/trip isolate needs to be activated to allow a new program to be transferred to the controller.
Loader: Trip Iso
Low Power Mode If the power supply voltage reduces below a threshold for a certain time, the radio supply is turned off
immediately.
The LBS will still operate but will go to lockout if the capacitors cannot be charged quickly enough.
Mech Locked / Unlocked The LBS mechanism has been locked or unlocked.
Mechanical Close The LBS was closed using the mechanical close lever.
Mechanical Trip The LBS was tripped using the manual mechanical trip lever.
Normal Power Mode If the power supply voltage returns to normal then the power mode will return to normal after 15 min.
NP-xxxxxx Connected LBS with serial number xxxxxx has been connected.
OCPM Door Closed This message is only ever logged if the control cubicle is equipped with a door switch.
OCPM Door Open
Outages ON The operator (local or remote) has turned ON or OFF the supply outage measurement functions.
Outages OFF
Outages Reset The operator (local or remote) has reset the four outage counters.
Phasing order The Terminal Designation has been changed where order is one of the following – ABC, ACB, BAC, BCA,
CAB, CBA.
Pickup One of the detection elements picked up (phase, earth or SEF). This event is generated by the first element to
pick up, if more elements pick up subsequently then no more pickup events are generated until all the
elements have reset.
Power Up The electronics just had power applied or had a power up reset or watchdog reset. The time displayed will be
approximately the time that power down occurred plus 1 sec.
P9 Baud xxxxx The operator has altered the baud rate of P9, via the panel or WSOS, to be the value shown. Where xxxxx is
one of 19200, 9600, 2400 or 1200.
P9 Mode yyyyy The operator has altered P9’s mode, via the panel or WSOS, to be that shown. Where yyyyy is either Local or
Remote.
QKx <function> Quick Key X has been mapped to the function. Thus pressing this Quick Key will now allow alteration of the
<function> setting. Eg. “QK1 Local/Remote”b
Radio Supply Failed This message indicates a radio power supply fault.
Radio Supply OK This message indicates that the fault has been rectified and power supply has been returned to normal.
Radio supply faults may occur when the batteries are depleted.
SCEM Type type The control cable has been connected to a different type of SCEM where type can be SCEM 9, 93C46 or
Unknown.a.
SEF Fault The indicated element has exceeded its fault threshold for its set amount of time.
Sequence Reset The sequence reset timer has expired. The supply interrupts count will start again.
92
Event Text Explanation
SF6 Pressure Normal The SF6 pressure status has changed state.
SF6 Pressure Low
Pressure Invalid
Source I Load X The operator (local or remote) has changed the power flow direction.
Source X Load I
Source Fault The element (as indicated by source) has exceeded its fault threshold for its set amount of time.
Source may be any one of the following:
A Phase
B Phase
C Phase
Earth
SEF
Source Supply OFF/ON All three source side voltages are OFF/ON.
Source Trip Req A trip/close request was issued from the source. Where source can be one of, Panel, WSOS, IOEX, Protocol,
Source Close Req etc.
Panel = Operator Control Panel.
WSOS = Windows Switchgear Operating System
IOEX = Input Output Expander Card.
Protocol = A communications protocol such as DNP3.
Supply Interrupt NN All currents fell to zero within one second of a fault.
This indicates upstream device operating. This was the NNth interruption since the sequence reset timer
started timing.
Switch Connected The LBS has been connected to the control cubicle.
Switch/SCEM Mismatch The LBS has been installed with the wrong SCEM.
I contact < 20% Less than 20% contact life remaining in the I-X, II-XX or III-XXX puffer interrupter.
II contact < 20%
III contact < 20%
Work Tag Applied The Work Tag has been applied/turned off.
Work Tag OFF
Wrong Switch No n This version of software and the connected switch type are incompatible.“n”is the switchgear type. The
controller will have to be loaded with correct software. a.
a. If this event occurs, the equipment may require maintenance. Contact the manufacturer or your local distributor for advice.
b. This event will be logged if the Quick Key configuration is changed via the panel osr WSOS.
93
RL27 Load Break Switch
94
Appendix E Replaceable Parts & Tools
All replacement parts are available from the LBS
manufacturer.
Listed below are the parts that may be required for
replacement following customer maintenance.
Also listed are special purpose tools .
Panasonic Batteries:
• LCR12V7.2P 12 Volt Battery BAT8250011
Cable Tail Kit: Quantity 6 off 400 Amp, 3m cable fitted with bushing boot and lug N01-612
Cable Tail Kit: Quantity 6 off 630 Amp, 3m cable fitted with bushing boot and screw termination N01-694
Control Cubicle
Tropical Version PTCC-TRO
Moderate Version PTCC-MOD
Temperate Version PTCC-TEM
Ferrite Filters (ID = 10mm) for incoming cable. ELCIND0030 (two reqd)
Round and Flat Cable (external communications data cables) Various - to suit application
95
RL27 Load Break Switch
96
Appendix F Control Cubicle Schematics
97
RL27 Load Break Switch
98
Figure 31: Control cubicle-main loom connection
99
RL27 Load Break Switch
100
Figure 33: Control cubicle-Single LV aux power supply
101
RL27 Load Break Switch
102
Figure 35: Control cubicle - Dual low voltage auxiliary supply -110/240 Volts
103
RL27 Load Break Switch
104
Figure 37: Control cubicle - heater / thermostat connection
105
RL27 Load Break Switch
106
Appendix G Dimensions
Load Break
Switch
107
RL27 Load Break Switch
Mounting
Bracket
Radio
Mounting
Space
108
Control
Cubicle
109
RL27 Load Break Switch
110
Appendix H Silicone Grease Hazard Data
Silicone grease type LUB058044 is supplied by The following is reproduced from the original
the manufacturer for filling the bushing boot document provided by Rhodia Silicones, Australia.
cavities. This product is supplied to the Release date of original document: June 1998.
manufacturer as Gensil Paste 12.
MATERIAL SAFETY DATA SHEET GENSIL
PASTE 12 INFOSAFE No: 2RH7J
COMPANY DETAILS
Tel / Fax Ph: +6103 9541 1000 Fax: +6103 9587 5989
IDENTIFICATION
Product Code GS 12
PHYSICAL DATA
OTHER PROPERTIES
pH Value Neutral
Odour None
Form Liquid
INGREDIENTS
HEALTH EFFECTS
111
RL-Series
FIRST AID
ADVICE TO DOCTOR
PERSONAL PROTECTION
Protective Equipment General safe work practice provides adequate
protection.
FLAMMABILITY
112
Fire / Explosion Hazard Low hazard.Non-flammable liquid. Forms
essentially amorphous silica, carbon dioxide and
carbon monoxide on combustion. Fire can be
extinguished by carbon dioxide, powder or a water
type extinguisher.
OTHER INFORMATION
Packaging and Labelling Keep in original container, ensure product name and
code is marked on the container.
CONTACT POINT
Further Advice to the User: enable appropriate risk assessment, the user
should contact Rhodia Silicones Australia. Our
This material safety data sheet should be used in responsibility for products sold is subject to our
conjunction with the technical data sheets. It does standard terms and conditions sent to customers.
not replace them. The information given is based No liability whatsoever can be accepted with
on our knowledge of the health and safety data of regard to the handling, processing or use of the
this product at the time of publication. It is given in product concerned which, in all cases, shall be in
good faith. The attention of the user is drawn to the accordance with the appropriate regulations and/
possible risks incurred by using the product for any or legislation.
purpose other than that for which it was intended.
If clarification or further information is required to
113
RL-Series
114
INDEX
A Configurable Quick Keys .................................... 29
Active Detection Group ...................................... 37 Configuration Number .......................................... 3
ADGS ...........................................................9, 40 Configuring Average Demand ............................ 47
enabling ....................................................... 40 Connections into electronics compartment .......... 57
and ................................................................... 53 Contact life
Automatic sectionalising ....................................... 1 Greater than 20% on all phases ........................ 61
Aux supply ........................................................ 82 Contents of crate ............................................... 65
Fail .............................................................. 91 Control and protection module ............................ 23
Normal ......................................................... 91 (CAPM-4) ..................................................... 95
OK .............................................................. 61 Control cable ............................................... 65, 95
Auxiliary power Connection ................................................... 65
Control cubicle options .................................... 19 Entry module ................................................. 23
From mains ................................................... 72 Service drawing ........................................... 106
Source ......................................................... 18 Control cubicle .................................................. 95
Averaged Data displays ..................................... 47 Check .......................................................... 78
B Construction .................................................. 17
Control cable service drawing ......................... 106
Battery ........................................................82, 91
Dual LV aux power ...............................103, 104
Care ............................................................ 79
Heater ......................................................... 95
Replacement ................................................. 79
Schematics ................................................... 97
Supply OK .................................................... 61
Control cubicle entry module (CCEM) ................. 95
Bushing boot ...............................................68, 95
Clamping ring ................................................ 95 Control System block diagram ............................ 25
Clamping ring spanner ..............................67, 95 Controller
Installation tool .............................................. 95 Mode ........................................................... 33
Version .......................................................... 3
C
CT .................................................................... 45
Cable entry ....................................................... 19
Current injection point ........................................ 19
Cable Tail
Currents in each phase averaged over the period 47
Connections .................................................. 68
CVT .................................................................. 45
Cables
Personalised ................................................. 55 D
Replacement ................................................. 80 Date and time of the end of the averaging period . 47
Capability .......................................................... 83 Definition of Local / Remote user ........................ 33
Declaration ..................................................... 4 Denied Wrong Mode .......................................... 91
CAPM 4 and CAPM 5 ........................................ 23 Detection .................................................... 35, 37
CAPM Electronics OK ........................................ 61 basic fault ..................................................... 35
CCEM ............................................................... 23 changing ...................................................... 37
Check Displays ....................................................... 29
Circuit breaker ............................................... 77 Elements ...................................................... 92
Control cubicle ............................................... 78 elements ...................................................... 35
Circuit breaker feature ........................................................... 9
Check .......................................................... 77 Generated Events .......................................... 43
SF6 Recharging ............................................. 79 Options ........................................................ 83
Setting 1 (A–J) ............................................... 87
Clamping ring spanner–bushing boot ............67, 95
Setting 2 (A– J) .............................................. 87
Clamping ring–bushing boot .........................68, 95 Setting 3 (A–J) ............................................... 87
Close Blocking Setting 4 (A–J) ............................................... 87
OFF ............................................................ 91 settings ........................................................ 37
ON .............................................................. 91
Disconnected .................................................... 91
Close Coil
Display groups .................................................. 29
Connect ....................................................... 91
Display Page Organisation ................................. 31
Isolate .......................................................... 91
Dual LV aux power ..................................103, 104
Cold Load
OFF............................................................ 81 E
Cold Load Pickup ........................................39, 40 Earth connections .............................................. 67
Communications Earthing ............................................................ 72
External ....................................................... 55 Electronics compartment .................................... 57
Interfaces ..................................................... 55 Equipment panel ............................................... 17
WSOS Port P8 .............................................. 83 Equipment versions covered by this manual .......... 3
Computer port ................................................... 19 Event
Configurable Baud Rate ..................................... 56 Log .......................................................29, 43
Configurable IOEX ............................................. 61 External communications ................................... 55
115
RL27 Load Break Switch
F O
Fault Operator Control Panel ...................................... 27
Flags ........................................................... 35 Operator Panel subsystem ........................... 23, 95
Fault Detection .................................................. 77 Operator settings ......................................... 37, 81
Fault flags Optically isolated input contacts ......................... 59
Resetting ...................................................... 36 Options 1 .......................................................... 83
Feed-through or bulkhead type arrester .............. 71 Outputs ............................................................ 60
Ferrite filters ................................................ 71, 95 P
G P8 .................................................................... 55
Gas Panel ON/OFF ............................................ 27, 28
Pressure normal ............................................ 61 Parts and tools .................................................. 95
Gas discharge surge arrester ............................. 71 Parts required ................................................... 67
Gas fill adaptor .................................................. 79 Password protection .......................................... 30
Generator Control .............................................. 53 Peak averaging period ................................. 46, 47
Configuration ................................................ 53 Personalised cables .......................................... 55
Operation ..................................................... 53 Phase
Group Copy ...................................................... 38 Rotation ....................................................... 92
H Voltage ........................................................ 82
High Voltage connections .................................. 67 Pickup .............................................................. 92
Hit and Run ....................................................... 33 Power Down ..................................................... 92
HV Line supply .................................................. 18 Power Factor (PF) ....................................... 46, 47
I Power Flow direction ................................... 45, 82
Input Output Expander (IOEX) Card ................... 59 Power System measurements ............................ 45
Inputs ............................................................... 60 Power Up ......................................................... 92
Installation ........................................................ 65 Press to Talk (PTT) ........................................... 55
Interrupter .............................................13, 14, 93 Protection
IOEX Of radio equipment ......................................... 71
Cabling ........................................................ 71 Q
Card ............................................................ 59 Quick Key ......................................................... 29
Status .................................................... 59, 84 Quick Key Selection .......................................... 29
L Quick Keys ....................................................... 83
Liquid Crystal Display ........................................ 28 R
Live Load Blocking ............................................ 38 Radio and IOEX ................................................ 82
Live Load blocking ......................................... 9, 92 Radio and Time Set ........................................... 82
Live/Dead indication .................................... 46, 82 Radio holdup time ............................................. 57
Load Supply OFF/ON ........................................ 92 Radio/Modem
Local Power .................................................... 57, 82
Control ........................................................... 8 Real Power (kW) ......................................... 46, 47
Mode ..................................................... 33, 60 Real Time Displays ........................................... 46
Local/Remote Recloser earthing .............................................. 72
Mode ........................................................... 33 Related documents ............................................. 4
Loss of Supply Remote
Events ......................................................... 43 Control Panel ................................................ 64
LV Mode ........................................................... 33
Mains cable .................................................. 67 Operator control ............................................ 55
Supplies ....................................................... 18 Remote Control ON ........................................... 81
Surge arrester ............................................... 72 Remote Panel ................................................... 33
LV auxiliary supply Replacement of cables ...................................... 80
From dedicated utility transformer ...................... 73 Resetting
M Fault flags .................................................... 36
Maintenance ..................................................... 77 Trip flags ...................................................... 36
Measurement displays ....................................... 29 RS232 interface ................................................ 55
Mechanical Close .............................................. 92 S
Mechanical trip .................................................. 92 SAIDI ............................................................... 49
Mechanism OK. ................................................ 61 SAIFI ................................................................ 49
Menu key .......................................................... 28 SCEM Data ....................................................... 61
Moderate version .............................................. 17 Sealing and condensation .................................. 17
Monthly Maximum ............................................. 46 Secondary Injection Test Set .............................. 63
Mounting and earthing ....................................... 18 Select key ......................................................... 28
N Selecting displays ............................................. 28
Normal Power mode .......................................... 92 Sequence
116
INDEX
Reset ........................................................... 92 Work Tag ..............................................33, 60, 82
SF6 ................................................................... 82 WSOS .............................................................. 29
Gas cylinder .................................................. 95 WSOS Port P8 communications ......................... 83
Pressure ...................................................... 93
Recharging ................................................... 79
Silicone grease .................................................. 68
Silicone grease MSDS ..................................... 111
Site installation .................................................. 67
Site procedure ................................................... 67
Software
Capability ....................................................... 4
Software Capability .............................................. 3
Software Identification .......................................... 3
Software Version .............................................3, 4
Startup message ............................................... 28
Supply Outages
Display ......................................................... 90
Measurement ................................................ 49
Status .......................................................... 49
Supply Timeout ................................................. 82
Surge arresters
LV ............................................................... 72
Mounting and terminating ................................. 71
Switchgear
Cable Entry ................................................... 95
Status .......................................................... 82
Terminal designation ....................................... 82
Type and ratings ............................................ 83
Wear/general details ....................................... 83
Switchgear Wear ............................................... 83
System
Average Interruption Duration Index ................... 49
Average Interruption Frequency Index ................ 49
Healthy indicator ............................................ 61
Status displays .............................................. 29
Status pages ................................................. 81
T
Temperate version ............................................. 17
Test and Training Set ...................................63, 95
Testing & configuring ......................................... 66
Tools required ................................................... 67
Transport to site ................................................ 66
Trip Coil
Isolate.......................................................... 91
Trip flags ........................................................... 35
Resetting ...................................................... 36
Tropical version ................................................. 17
U
Unpacking & checking ........................................ 65
Updating the Event Log ...................................... 43
V
V23 FSK modem ............................................... 55
V23 interface ..................................................... 55
Version 28 Features ............................................ 2
Voltage free output contacts ............................... 59
Voltage on line side terminals ............................. 46
W
Weekly Maximum .............................................. 47
Windows Switchgear Operating System (WSOS) 43,
63, ................................................................... 95
117
RL27 Load Break Switch
118
Schneider Electric Nu-Lec Industries As standards, specifications and designs change from time to
Industries SA 35-37 South Street time, please ask for confirmation of the information given in this
Lytton, 4178 publication.
Queensland
Australia
e-mail: [email protected]
RL2-436
http://www.nulec.com.au
12 Aug 2004