Phase Sequence Relay PFN Mecotron: Operation

Uploaded by

honafa- R.O.N.O
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
676 views1 page

Phase Sequence Relay PFN Mecotron: Operation

Uploaded by

honafa- R.O.N.O
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

E021019 000831

Phase sequence relay Operation


PFN mecotron® The PFN monitors three-phase supply voltage for
incorrect phase sequence, overvoltage,
undervoltage and failure of one of the three
phases. The output relay de-energizes and the
LEDs indicate nature of the fault if one of the
above faults occurs. The output relay remains
energized with correct phase sequence (rotary
field right handed polarized) and correct voltage.
If the voltage exceeds 1.1 times the rated value
or falls below 0.9 times the rated value, the output
relay will de-energize. It will automatically energize
again as soon as the voltage again attains the
rated value, the set hysteresis of 5% thereby
being effective.
A delay on operate or on release time can be set
for the overvoltage and undervoltage monitoring
functions. The delay time is adjusted with a
Monitors three-phase supply voltage for incorrect potentiometer. Phase failure and incorrect phase
phase sequence, overvoltage, undervoltage
Monitoring range: 0.9 to 1.1 VN
sequence are indicated without delay.
Fixed switching hysteresis of 5 % With motors running on two phases the
Selectable delay on operate or on release of regenerated voltage may be so high that the
0.1 ... 10 s on overvoltage or undervoltage output relay cannot de-energize if one of the
2 SPDT contacts phases fails. For such application, we recommend
5 LEDs to indicate all operational states the use of phase unbalance relay ASN.
3 three-phase voltage monitoring versions:
220 V, 400 V, 500 V
3 supply voltage versions:
Approvals:
110...130 V, 220...240 V, 380...415 V
Monitoring voltage (3-phase) Types for special measuring ranges and voltages on request

Supply voltage P/N: P/N: P/N: P/N: P/N: 2 Functions


50...60 Hz 220 V/50 Hz 380 V/50 Hz 400 V/50 Hz 400 V/60 Hz 500 V/50 Hz
Delay on operate error message
110...130 V AC 2 450 310 02 2 450 310 04 2 450 310 05 2 450 310 07
220...240 V AC 2 450 311 02 2 450 311 04 2 450 311 05 2 450 311 07 Supply A1/A2
+10 %
380...415 V AC 2 450 312 02 2 450 312 04 2 450 312 05 2 450 412 05 2 450 312 07
monitoring +5 %
Accessories P/N: voltage VN
-5 %
Sealable transparent cover 3 440 005 01 L1, L2, L3 -10 %
Level
Adapter for screw mounting 3 430 029 01 SPDT 25/28
contact 1 25/26
Technical data SPDT 25/28
contact 2 25/26
Input circuit
Supply voltage - power consumption A1-A2 110...130 V AC - 3 VA
A1-A2 220...240 V AC - 3 VA t = delay time t only effective for undervoltage monitoring

A1-A2 380...415 V AC - 3 VA
Tolerance of supply voltage -15 % ... +10 %
Supply voltage frequency 50...60 Hz
Delay on release error message
Time circuit message: overvoltage, low voltage (Instantaneous error message with storage)
Delay on operate time adjustable 0.1...10 s
Supply A1/A2
Delay on release time adjustable 0.1...10 s
+10 %
Timing error within tolerance of supply voltage ≤ 0.5 % monitoring +5 %
Timing error within temperature range ≤ 0.06 % / °C voltage VN
-5 %
Measuring circuit L1, L2, L3 L1, L2, L3 -10 %
Monitoring voltage Vnom. 220 V AC 380 V AC 400 V AC 500 V AC SPDT
Level
25/28
Frequency 50 Hz or 60 Hz contact 1 25/26
Response value at overvoltage/ undervoltage 0.9/1.1-VNom (0.85/1.1 for 380 V/50 Hz version) SPDT 25/28
contact 2 25/26
Reset value at overvoltage/ undervoltage 0.95/1.05-VNom (0.9/1.05 for 380 V/50 Hz version)
Measuring cycle max. 80 ms
t = delay time t only effective for over-/undervoltage monitoring
Hysteresis (fixed) 5%
Temperature error ≤ 0.06 % / °C
Error within tolerance of supply voltage ≤ 0.5 %
Display of operating status
Supply voltage V LED, green
Output relay energized R LED, yellow
Overvoltage >V LED, red
Undervoltage <V LED, red
Phase failure and phase sequence error P LED, red
Output circuit 15-16/18, 25-26/28 Relay, 2 SPDT contacts, closed-circuit principle
Rated voltage VDE 0110, IEC 947-1 400 V
Rated switching voltage max. 400 V AC
Rated switching current AC 12 (resistive) 5 A (at 230 V)
Rated switching current AC 15 (inductive) 3 A (at 230 V)
Rated switching current DC 12 (resistive) 5 A (at 24 V)
Rated switching current DC 13 (inductive) 2.5 A (at 24 V)
Maximum mechanical life 30 x 106 operations
Maximum electrical life (acc. to AC 12 / 230 V / 5 A) 1 x 105 operations
Short-circuit proof, max. fuse rating 5 A / fast, operating class gL
General data
Rated impulse withstand voltage Vimp 4 kV
Operating temperature -25°C ... +65°C
Storage temperature -40°C ... + 85°C
Mounting position any
Mounting to DIN rail (EN 50022) Snap-on mounting/Screw mounting by adapter
Cable size stranded with wire end ferrule 2 x 14 AWG (2 x 2.5 mm2) Note:
Weight approx. 0.66 lb (300 g) Dimensions (W x H x D), 45 x 78 x 101 mm