Procurement and Installation: Approved: H. Zoghbi Signed Original On File
Procurement and Installation: Approved: H. Zoghbi Signed Original On File
16-137-01
STANDARD CATEGORY: MANDATORY RECOMMENDED DESIGN AIDE
Approved: H. Zoghbi
Signed original on file Pneumatic HVAC Controls - SHEET 1 OF 9
Date: 7/10/03 Procurement and Installation
Table of Contents
1.0 Scope
This standard, together with the purchase documents and drawings, provides the basis for
the procurement and installation of a complete pneumatic automatic control system for
heating, ventilation and air conditioning (HVAC) systems. Electronic DDC HVAC
control systems are not included in this standard.
3.0 Requirements
3.1 The HVAC controls Contractor shall furnish all materials and labor required to
perform the design, installation and calibration of automatic control systems to
control HVAC systems in accordance with the sequences of operation described in
the purchase documents and drawings. When practical, all the components of the
system shall be products of a single Manufacturer. All control components shall be
tagged in accordance with purchase documents.
3.2 Electrical Wiring and Components
3.2.1 All field electrical wiring (between device and control panel) and pre-wired
control panels shall be installed in accordance with the purchase documents.
3.2.2 All electric or electric-pneumatic devices mounted on or in the control
panels shall be pre-wired to numbered terminal strips.
5.21.2 Mixing and modulating dampers shall be equipped with linkages providing
linear flow characteristics.
░ 5.21.3 Dampers shall be positioned by single-stage diaphragm-piston type damper
operators. Operators shall be selected to position dampers through their full
range of operation and shall provide adequate force in both directions of
travel. Multiple damper operators shall be provided for larger damper sizes
requiring force beyond the capabilities of single operators. Damper
operators shall be equipped with universal mounting brackets to facilitate
installation in field under widely varying mounting conditions.
5.21.4 Where dampers are operated in sequence, damper operators shall be
equipped with positive positioning relays (see Positive Positioning Relays
above). Damper operator stroke limiting devices shall be provided as
required to limit opening and/or closing of dampers.
░ 5.21.5 All control dampers shall be standard products of the HVAC controls
Manufacturer's factory or an approved equal. Field fabrication of dampers
is not allowed.
5.22 Smoke Control Dampers
Smoke control dampers shall be furnished by the HVAC controls Contractor and
installed by the Sheet Metal Contractor in the HVAC system where shown on plans.
All smoke dampers and actuators shall be Underwriters Laboratories tested under
Standard 555S, latest revision, and classified Class II leakage at 250°F temperature
rating, unless otherwise specified, and shall bear the UL label.
5.23 Pressure Reducing Valves
Control air pressure reducing valves shall be a diaphragm type pressure regulator
with integral safety relief valve. Reducing valves shall be capable of accurately
regulating the control pressure between 0 and 25 psig with inlet air pressure between
45 and 150 psig.
5.24 Temperature Indicating Gages
All temperature gages shall have an adjustment screw on the back of the case to
permit rotation of the gage mechanism. Gages shall be equipped with dials
indicating the temperature being measured. Dials shall be selected to have proper
range for temperature being measured. Indicator accuracy shall be plus or minus 2
percent of full scale, unless otherwise specified. Minimum diameter shall be 2-1/2”.
Gages shall be suitable for panel mounting.
5.25 Pneumatic Control Tubing
5.25.1 Complete air piping shall be provided for the pneumatic control system and
is subject at all times to the approval of the Owner.
5.25.2 Pipe shall be of seamless copper tubing, aluminum tubing and/or non-
metallic tubing. All piping shall be concealed except in mechanical rooms
or areas where other piping is exposed. Hard drawn tubing will be used in
all exposed areas and either hard drawn or annealed if concealed. Where
copper
Technical Standard
Pneumatic HVAC Controls -
16-137-01
Procurement and Installation
Date: 7/10/03 SHEET 8 OF 9
After completion of the installation, the Contractor shall calibrate and adjust all
thermostats, control valves, actuators, controllers and other equipment provided in
accordance with the Manufacturer's requirements. The controls shall be placed in a
complete operating condition subject to the approval of Owner or Owner's representative.
9.0 Submittals
Submit one (1) reproducible of schematic control diagrams to the Owner for his review and
approval. Drawings shall show all components of the control system, properly identified
with catalog numbers, with all pneumatic and electrical connections shown. Schematic
drawings shall show setpoints for the various instruments and shall indicate operational
modes, transmitter ranges, operating pressure ranges of all controlled devices, normal
position of all ports (C, NO, NC), type of action, etc. A detailed description of the
sequences of operation, written in layman's language, shall be included on schematic
drawings.
Submittals of schematic diagrams shall be accompanied by catalog cuts of all material
furnished together with valve and damper schedules. Valve schedules shall indicate valve
sizes, flow coefficients and pressure drops (at design flow).
Furnish terminal-to-terminal wiring diagrams.
Following completion and acceptance of the HVAC controls installation, the following
shall be issued to BASF:
9.1 "As-built" schematic diagrams (not “red-lined”).
9.2 Installation drawings.
9.3 Complete vendor manuals for each instrument as needed for calibration and/or
repair.
9.4 Certification of completion and controls calibration sheets.
9.5 Spare parts list.