New Design of Ground Fault Protection: J. Blumschein, Y. Yelgin
New Design of Ground Fault Protection: J. Blumschein, Y. Yelgin
J. Blumschein*, Y. Yelgin*
Keywords: Ground fault protection, directional element, This paper explains the new algorithm in more detail and
faulted phase selection illustrates the advantages of the proposed method using some
real fault records. With the new design the ground fault
Abstract protection takes a lot of advantages regarding phase selection
and directional element from the distance protection. The
Ground fault protection is widely used to protect transmission main difference between distance protection and ground fault
and distribution lines in case of ground faults. Combined with protection remains the different grading. For distance
a directional element and used in a teleprotection scheme protection the sensitivity is limited by the resistive reach. The
ground fault protection can detect and isolate even high basic principle for grading of ground fault protection remains
resistive ground faults which are not seen by distance a simple threshold of zero sequence current.
protection.
Today in general the directional element of ground fault
protection is based on zero sequence components or negative 1 Introduction
sequence components. There is no clear advice which kind of
polarization should be preferred for a special application. In general for single-phase to ground faults the current of the
However there are a lot of maloperations due to incorrect faulted phase is increasing and the voltage of the faulted
result of the directional element of ground fault protection phase is decreasing.
using either zero sequence or negative sequence quantities. Ground fault protection calculates the ground current 3I0 as
Analyzing numerous fault records it seems obvious that these criterion for pickup and grading:
problems with the directional elements cannot be solved using
either zero sequence or negative sequence because these 3I0 = IA + IB + IC (1)
quantities are sometimes very small or not related to the fault.
One great advantage of numerical relays is that these relays If the ground current 3I0 exceeds a certain threshold, the
measure all the voltages and currents of a three phase system. ground fault protection will generate a pickup signal. In case
Analyzing fault records related to complicate cases for ground of directional ground fault protection the direction to fault
fault protection it can be seen that there is much more needs to be calculated to validate the trip command.
information about the fault than used by today’s Electromechanical relays uses zero sequence voltage or zero
implementations of ground fault protection. For instance the sequence current of transformer star point to calculate the
location of the impedance in the complex plane often gives a direction to fault. These quantities were easy to obtain and
clear indication about the direction to fault. valid for all types of fault.
This paper suggests a new design of ground fault protection Later polarizing with negative sequence quantities was
using this additional information given by the numerical applied because negative sequence is more immune against
relays. The starting condition for the ground fault protection mutual coupling of parallel lines. However even polarizing
remains a threshold of zero sequence current. Once this with negative sequence is not a perfect solution.
threshold is exceeded a multi-criteria phase selector selects In chapter 2 three different cases of incorrect operation of
the faulted phase. Several criteria based on magnitudes of directional ground fault protection are explained. Chapter 3
voltages and currents, changes in voltages and currents, introduces a new idea for the phase selection of the ground
symmetrical components and impedances are applied in fault protection using more information about the fault which
parallel. The results of each single criterion are weighted and is available in a multifunctional relay. Chapter 4 explains a
combined to get a final result for the selection of the faulted new idea of a directional element for ground fault protection
phase. based on the combination of different criteria used in distance
Using the information of the faulted phase a multi-criteria protection.
directional element is suggested to estimate the direction to
the fault. Different criteria based on actual voltages, 2 Real-world cases of incorrect operation of
memorized voltages, symmetrical components and delta directional ground relays
quantities are applied in parallel. The final result is obtained
by the multi-criteria directional element as a weighted In the following subchapters three cases of incorrect operation
combination of the result of each single criterion. of directional ground fault protection are explained in detail.
2.1 Case 1: Wrong trip using zero sequence polarization The ground current iE exceeds the sensitive threshold of 50A
primary which leads to a pickup of the ground fault
The first case presents a wrong trip of directional ground fault protection. The current of phase B is raising most which is
protection on a 147 km line, 132 kV in Malaysia. Figure 1 consistent with the pickup of phase B.
shows the impedance trajectories in the complex plane. It can The changes of voltages after fault inception are not very big
be seen that the fault was BG, far away from the polygons of but leaving enough quantity of zero sequence voltage and
distance protection in reverse direction. negative sequence voltage for the directional element.
Figure 3 is showing the zero sequence quantities and negative
sequence quantities in the phasor diagram. It can be seen that
the zero sequence current is leading the zero sequence voltage
by approximately 100° which is a clear indication for a fault
in forward direction. The negative sequence current however
is lagging the negative sequence voltage by approximately
60° which is a clear indication for a fault in reverse direction.
In this case zero sequence quantities are a little larger than
negative sequence quantities. That’s why zero sequence is
chosen as directional element which leads to the wrong trip of
the directional ground fault protection in this case.
Figure 2 shows the currents and voltages for the BG fault and
the related binary signals.
Figure 5 shows the currents and voltages for the AG fault and
the related binary signals.
I2 = I0
L2-E
I2 = a2*I0
Figure 9: Voltages, currents and binary signals of BG fault Figure 11: Negative sequence current in relation to zero
sequence current for the BG fault
3 Multi-criteria phase selection
Figure 13 gives an example of the output quality of the
If there is a pickup of ground fault protection due to ground voltage criterion. A strong voltage drop in case of a fault
current exceeds the threshold the next step should be to find results in a high quality of the voltage criterion for the related
out the faulted phase. This is important to be able to issue a phase. If the voltage drop is only marginal the quality of the
single pole trip in case of a single phase to ground fault. It is voltage criterion of the related phase will have a low quality.
also important to know the faulted phase to improve the
directional element of ground fault protection which is
explained in the next chapter.
Today the basic principle of phase selection for ground fault
protection is based on the relation between the angle of
negative sequence current and the angle of zero sequence
current like shown in Figure 10.
In a modern multifunctional digital relay there is much more
information about the faulted phase which could be used by
the ground fault protection. The suggestion is to apply at least
parts of the faulted phase selection used by distance
Figure 13: Quality of voltage criterion
protection for the phase selection in ground fault protection.
In [3] an example is given for a multi-criteria loop selector for
Figure 14 illustrates the output quality of the impedance
the distance protection.
criterion. If the measured impedance of a phase to ground
Figure 12 explains the principle of the multi-criteria phase
loop is close to the origin the quality of the phase to be the
selector for the ground fault protection. Several criteria for
faulted phase is high. If the impedance is measured far away
phase selection are applied in parallel. Each criterion gives a
or has an angle which is not typical for a faulted loop the
certain quality for each phase to be the faulted phase.
quality of the impedance criteria is low.
Additional to this each criterion can be weighted according to
its importance for the decision about the faulted phase.
Finally there is a weighted sum of quality for each phase to be
the faulted phase. The faulted phase is chosen to be the one
with the highest quality exceeding a dynamic threshold.
weight 1
Criteria 1 quality
weight 2
Criteria 2 quality
quality phase A
Σ quality phase B
Figure 14: Quality of impedance criterion
quality phase C
Acknowledgements
The author thanks Ms. Sophie Gray from CenterPoint Energy,
Mr. Jorge Ywasaki from Red de Energía del Perú and
Sarawak Energy Malaysia for sharing fault records used to
explain problems with the directional ground fault protection.