Complete Report
Complete Report
Short-Circuit Analysis
Number of Buses: 3 2 39 44
Line/Cable/
XFMR2 XFMR3 Reactor Busway Impedance Tie PD Total
Number of Branches: 6 0 0 34 0 1 41
Number of Machines: 3 0 0 14 8 25
Project Filename:
Output Filename:
Project: - ETAP Page: 2
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Apply Individual
Temperature Correction Adjustments /Global Degree C
44 Buses Total
Branch Connections
G-6501 Steam Turbo Bus1 4.350 6.600 1500 85.00 0.932 17.70 0.0 0.05 143.70 Turbine 130%
G-6502 Steam Turbo Bus3 4.350 6.600 1500 85.00 0.932 17.70 0.0 0.05 143.70 Turbine 130%
G-6503 Steam Turbo Bus4 4.350 6.600 1500 85.00 0.932 17.70 0.0 0.05 143.70 Turbine 130%
% Impedance
Induction Machine Connected Bus Rating (Motor Base)
PM-2219A Motor 1 Bus29 350.00 407.97 6.600 35.69 92.06 2.96 15.10 0.20 0.18
PM-2219B Motor 1 Bus33 350.00 407.97 6.600 35.69 92.06 2.96 15.10 0.20 0.18
PM-3203A Motor 1 Bus42 220.00 257.63 6.600 22.54 91.87 3.36 15.01 0.22 0.11
PM-3203B Motor 1 Bus43 220.00 257.63 6.600 22.54 91.87 3.36 15.01 0.22 0.11
AM-4103B Motor 1 Bus46 300.00 350.26 6.600 30.64 91.99 3.09 15.07 0.20 0.15
AM-4103A Motor 1 Bus47 300.00 350.26 6.600 30.64 91.99 3.09 15.07 0.20 0.15
CM-3411_1 Motor 1 Bus7 318.00 371.03 0.415 516.18 92.02 3.29 16.34 0.20 0.16
CM-3411_2 Motor 1 Bus7 172.00 201.95 0.415 280.95 91.76 3.90 16.20 0.24 0.09
CM-3412_1 Motor 1 Bus11 318.00 371.03 0.415 516.18 92.02 3.29 16.34 0.20 0.16
CM-3412_2 Motor 1 Bus11 172.00 201.95 0.415 280.95 91.76 3.90 16.20 0.24 0.09
CM-3413_1 Motor 1 Bus16 318.00 371.03 0.415 516.18 92.02 3.29 16.34 0.20 0.16
CM-3413_2 Motor 1 Bus16 172.00 201.95 0.415 280.95 91.76 3.90 16.20 0.24 0.09
CM-3414_1 Motor 1 Bus17 318.00 371.03 0.415 516.18 92.02 3.29 16.34 0.20 0.16
CM-3414_2 Motor 1 Bus17 172.00 201.95 0.415 280.95 91.76 3.90 16.20 0.24 0.09
AUX-CM-3411 Bus7 66.3 0.415 92.24 85.00 30 70 16.9 10.5 6.46 15.37 0.42 0.02
AUX-CM-3412 Bus11 66.3 0.415 92.24 85.00 30 70 16.9 10.5 6.46 15.37 0.42 0.02
AUX-CM-3413 Bus16 66.3 0.415 92.24 85.00 30 70 16.9 10.5 6.46 15.37 0.42 0.02
AUX-CM-3414 Bus17 66.3 0.415 92.24 85.00 30 70 16.9 10.5 6.46 15.37 0.42 0.02
Lump-EM-1001 EM-1001 1242.0 0.415 1727.88 85.00 30 70 231.2 143.3 6.46 15.37 0.42 0.32
Lump-MCC-1001A MCC-1001A 842.0 0.415 1171.40 85.00 30 70 122.4 75.8 6.46 15.37 0.42 0.21
Lump-MCC-1001B MCC-1001B 579.0 0.415 805.51 85.00 30 70 124.0 76.9 6.46 15.37 0.42 0.15
Lump-MCC-1001C MCC-1001C 321.0 0.415 446.58 85.00 30 70 49.9 30.9 6.46 15.37 0.42 0.08
AC Rating
% Impedance
kVA kV FLA Input Output Bypass Equipment Base
ID Output Input Output Input Output % EFF % PF Hz % Imax Switch R X
VFD-PM-2219A 400.00 6.600 6.600 34.99 34.99 100.00 87.50 60.00 150.0 No 66.67 0.00
VFD-PM-2219B 400.00 6.600 6.600 34.99 34.99 100.00 87.50 60.00 150.0 No 66.67 0.00
Project: - ETAP Page: 13
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal
SHORT-CIRCUIT REPORT
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 69.138 kA Method C
Steady State = 27.174 kA rms
Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 17.558 kA Method C
Steady State = 6.147 kA rms
Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 22.758 kA Method C
Steady State = 2.208 kA rms
(Cont.)
Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 22.758 kA Method C
Steady State = 2.208 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 70.853 kA Method C
Steady State = 28.421 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 70.325 kA Method C
Steady State = 28.585 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 75.582 kA Method C
Steady State = 28.751 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 85.753 kA Method C
Steady State = 27.983 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 86.594 kA Method C
Steady State = 28.246 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 63.796 kA Method C
Steady State = 26.581 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 62.051 kA Method C
Steady State = 26.438 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 64.537 kA Method C
Steady State = 26.297 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 45.953 kA Method C
Steady State = 22.033 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 30.724 kA Method C
Steady State = 16.383 kA rms
Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 29.631 kA Method C
Steady State = 15.921 kA rms