Plumbing Fixtures
Plumbing Fixtures
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
0.2 SUMMARY
A. This Section includes plumbing fixtures and trim, faucets, other fittings, and related
components.
B. Related Sections: The following Sections contain requirements that relate to this Section:
1. Division 7 Section "Joint Sealants" for sealing between fixtures and walls, floors, and
counters.
2. Division 10 Section "Toilet and Bath Accessories" for toilet and bath accessories.
3. Division 15 Section "Valves" for general-duty valves used as supply stops.
4. Division 15 Section "Plumbing Specialties" for backflow preventers and other
specialties not specified in this Section.
0.3 DEFINITIONS
A. Accessible: Plumbing fixture, building, facility, or portion thereof that can be approached,
entered, and used by physically handicapped, disabled, and elderly people.
B. Fitting: Device that controls flow of water into or out of plumbing fixture. Fittings
specified in this Section include supplies and stops, faucets and spouts, shower heads and
tub spouts, drains and tailpieces, traps and waste pipes. Pipe fittings, tube fittings, and
general-duty valves are included where indicated.
0.4 SUBMITTALS
A. Product Data: For each plumbing fixture category and type specified. Include selected
fixture, trim, fittings, accessories, appliances, appurtenances, equipment, and supports.
Indicate materials and finishes, dimensions, construction details, and flow-control rates.
C. Maintenance data for plumbing fixtures and components to include in the operation and
maintenance manuals specified in Division 1.
A. Source Limitations: Obtain plumbing fixtures, faucets, and other components of each
category from one source and by a single manufacturer.
1. Exception: Where fixtures, faucets, or other components are not available from a
single manufacturer, obtain similar products from other manufacturers specified for
this category.
B. Listing and Labeling: Provide electrically operated fixtures and components specified in
this Section that are listed and labeled.
C. Select combinations of fixtures and trim, faucets, fittings, and other components that are
compatible.
A. Field Measurements: Coordinate roughing-in and final fixture locations and verify that
plumbing fixtures can be installed to comply with original design and referenced standards.
A. Furnish extra materials described below that match products installed, are packaged with
protective covering for storage, and are identified with labels describing contents. Deliver
extra materials to the Employer.
1. Faucet Washers and O-Rings: Furnish quantity of identical units not less than 10
percent of each type and size installed.
2. Faucet Cartridges and O-Rings: Furnish quantity of identical units not less than 5
percent of each type and size installed.
3. Faucet, Laminar-Flow Fittings: Furnish quantity of identical units not less than 10
percent of each type and size installed.
4. Faucet, Flow-Control Fittings: Furnish quantity of identical units not less than 10
percent of each type and size installed.
5. Supply, Flow-Control Fittings: Furnish quantity of identical units not less than 5
percent of each type and size installed.
6. Shower, Flow-Control Fittings: Furnish quantity of identical units not less than 5
percent of each type and size installed.
7. Flushometer Valve, Repair Kits: Furnish quantity of identical units not less than 10
percent of each type installed.
8. Provide hinged-top, wood or metal box, or individual metal boxes, having separate
compartments for each type and size of extra materials listed above.
9. Flushometer Tank, Repair Kits: Furnish quantity of identical units not less than 5
percent of each type installed.
10. Water-Closet Tank, Repair Kits: Furnish quantity of identical units not less than 5
percent of each type installed.
11. Toilet Seats: Furnish quantity of identical units not less than 5 percent of each type
installed.
12. Filter Cartridges: Furnish quantity of identical units not less than 50 percent of each
type and size installed.
PART 2 - PRODUCTS
A. Comply with ASME A112.18.1M and other requirements specified for lavatory, sink, and
similar-type-fixture faucet fittings. Include hot- and cold-water indicators; 0.16-L/s-
maximum flow rate; and polished, chrome-plated finish; except where otherwise indicated.
Coordinate faucet inlets with supplies and fixture holes and outlet with spout and fixture
receptor.
A. Comply with ASME A112.18.1M and other requirements specified for bathtub and shower
faucet fittings. Include hot- and cold-water indicators; 0.16-L/s- maximum flow rate; and
polished, chrome-plated finish; except where otherwise indicated. Coordinate faucet inlets
with supplies and outlet with diverter valve; tub spout; and shower head, arm, and flange.
A. Comply with ASME A112.18.1M and other requirements specified for fittings, other than
faucets. Include polished, chrome-plated finish, except where otherwise indicated.
Coordinate fittings with other components and connectors.
A. Comply with applicable standards below and other requirements specified for components
for plumbing fixtures, equipment, and appliances.
0.6 FITTINGS
A. Fittings for Plumbing Fixtures: Refer to plumbing fixture schedules at the end of this
Section for materials for supplies, supply stops, supply risers, traps, and other fittings.
B. Fittings for Equipment Specified in Other Sections: Fittings include the following:
1. Supply Inlets: Brass pipe or copper tube, size required for final connection.
2. Supply Stops: Chrome-plated brass, angle or straight; compression, loose-key type;
same size as supply inlet and with outlet matching supply riser.
3. Supply Stops: Chrome-plated brass, angle or straight; compression, wheel-handle
type; same size as supply inlet and with outlet matching supply riser.
4. Supply Risers: DN10 flexible copper tube with knob end. Use chrome-plated tube
for exposed applications.
5. Supply Risers: DN10 rigid brass tube with DN8 straight, knob-end tailpiece. Use
chrome-plated tube for exposed applications.
6. Supply Risers: DN10 rigid brass tube with DN8 offset, knob-end tailpiece. Use
chrome-plated tube for exposed applications.
7. Traps: Tubular brass with 1.1 mm wall thickness, with no-leak slip-joint inlet,
cleanout, wall flange, escutcheons, and size to match equipment. Use chrome-plated
tube for exposed applications.
8. Traps: Cast brass with no-leak slip-joint inlet, cleanout pipe nipple to wall, wall
flange, escutcheons, and size to match equipment. Use chrome-plated tube for
exposed applications.
9. Continuous Waste: Tubular brass, 1.1 mm wall thickness, with no-leak slip-joint
inlet, and size to match equipment.
10. Continuous Waste: Tubular brass, 0.8 mm wall thickness, with no-leak slip-joint
inlet, and size to match equipment.
11. Continuous Waste: Tubular plastic with no-leak slip-joint inlet and size to match
equipment.
12. Indirect Waste: Tubular brass, 1.1 mm wall thickness, and size to match equipment.
13. Indirect Waste: Tubular brass, 0.8 mm wall thickness, and size to match equipment.
14. Indirect Waste: Tubular plastic and size to match equipment.
PART 3 - EXECUTION
0.1 EXAMINATION
A. Examine roughing-in for potable, hot- and cold-water supply piping systems; soil, waste,
and vent piping systems; and supports. Verify that locations and sizes of piping and
locations and types of supports match those indicated, before installing and connecting
fixtures. Use manufacturer's roughing-in data when roughing-in data are not indicated.
B. Examine walls, floors, and cabinets for suitable conditions where fixtures are to be installed.
0.2 APPLICATIONS
A. Include supports for plumbing fixtures specified in this Section or other Sections, according
to the following:
1. Carriers: For wall-hanging water closets and fixtures supported from wall
construction.
2. Chair Carriers: For wall-hanging urinals, lavatories, sinks, drinking fountains, and
electric water coolers.
3. Heavy-Duty Chair Carriers: For accessible urinals, lavatories, and other fixtures
where indicated.
4. Reinforcement: For floor-mounted lavatories and sinks that require securing to wall
and recessed, box-mounted, electric water coolers.
5. Fabricate reinforcement from 50 mm by 100 mm or 50 mm by 150 mm fire-retardant-
treated-wood blocking between studs or 6 mm by150 mm steel plates attached to
studs, in wall construction, to secure fixtures to wall. Include length that will extend
beyond ends of fixture mounting bracket and attach to at least 2 studs.
B. Include fitting insulation kits for accessible fixtures according to the following:
1. Lavatories: Cover hot- and cold-water supplies, stops and handles, drain, trap, and
waste to wall.
2. Lavatories: Cover hot-water supply, stop and handle, drain, trap, and waste to wall.
3. Sinks: Cover hot- and cold-water supplies, stops and handles, drain, trap, and waste
to wall.
4. Sinks: Cover hot-water supply, stop and handle, drain, trap, and waste to wall.
5. Fixtures with Offset Drain: Cover hot- and cold-water supplies, offset drain, trap,
and waste to wall.
6. Fixtures with Offset Drain: Cover hot-water supply, offset drain, trap, and waste to
wall.
7. Other Fixtures: Cover exposed fittings below fixture.
A. Assemble plumbing fixtures and trim, fittings, faucets, and other components according to
manufacturers' written instructions.
B. Install fixtures level and plumb according to manufacturers' written instructions, roughing-in
drawings, and referenced standards.
C. Install floor-mounted, floor-outlet water closets with closet flanges and gasket seals.
D. Install floor-mounted, back-outlet water closets with fittings and gasket seals.
E. Install wall-hanging, back-outlet water closets with support manufacturer's tiling frame or
setting gage.
H. Install flushometer valves for accessible water closets and urinals with handle mounted on
wide side of compartment. Install other actuators in locations that are easy for handicapped
people to reach.
I. Install tanks for accessible, tank-type water closets with lever handle mounted on wide side
of compartment.
K. Fasten floor-mounted fixtures to substrate. Fasten fixtures having holes for securing fixture
to wall construction, to reinforcement built into walls.
P. Set shower receptors and mop basins in leveling bed of cement grout.
Q. Install individual stop valve in each water supply to fixture. Use gate or globe valve where
specific stop valve is not specified.
S. Install faucet, laminar-flow fittings with specified flow rates and patterns in faucet spouts
when faucets are not available with required rates and patterns. Include adapters when
required.
T. Install supply, flow-control fittings with specified flow rates in fixture supplies at stop
valves.
U. Install faucet, flow-control fittings with specified flow rates and patterns in faucet spouts
when faucets are not available with required rates and patterns. Include adapters when
required.
V. Install shower, flow-control fittings with specified maximum flow rates in shower arms.
W. Install traps on fixture outlets. Omit traps on fixtures having integral traps. Omit traps on
indirect wastes, except where otherwise indicated.
X. Install disposers in sink outlets. Install switch where indicated, or in wall adjacent to sink if
location is not indicated.
Y. Install hot-water dispensers in back top surface of sink or in counter with spout over sink.
Z. Install escutcheons at wall, floor, and ceiling penetrations in exposed, finished locations and
within cabinets and millwork. Use deep-pattern escutcheons where required to conceal
protruding pipe fittings.
AA. Seal joints between fixtures and walls, floors, and counters using sanitary-type, 1-part,
mildew-resistant, silicone sealant according to sealing requirements specified in Division 7
Section "Joint Sealants." Match sealant color to fixture color.
BB. Comply with ADA requirements for installation of fixtures in areas accessible to the
handicapped.
0.4 CONNECTIONS
1. Install piping connections between plumbing fixtures and piping systems and
plumbing equipment specified in other Division 15 Sections.
B. Supply and Waste Connections to Plumbing Fixtures: Refer to plumbing fixture schedules
at the end of this Section for fitting sizes and connection requirements for each plumbing
fixture.
D. Ground equipment.
E. Arrange for electric-power connections to fixtures and devices that require power. Electric
power is specified in Division 16 Sections.
A. Verify that installed fixtures are categories and types specified for locations where installed.
B. Check that fixtures are complete with trim, faucets, fittings, and other specified components.
C. Inspect installed fixtures for damage. Replace damaged fixtures and components.
D. Test installed fixtures after water systems are pressurized and demonstrate proper operation.
Replace malfunctioning fixtures and components, then retest. Repeat procedure until units
operate properly.
A. Operate and adjust faucets and controls. Replace damaged and malfunctioning fixtures,
fittings, and controls.
B. Operate and adjust disposers, hot-water dispensers, and controls. Replace damaged and
malfunctioning units and controls.
C. Adjust water pressure at drinking fountains, electric water coolers, faucets, shower valves,
and flushometer valves having controls, to produce proper flow and stream.
PLUMBING FIXTURES 15440 - Page 8/30
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>
D. Replace washers and seals of leaking and dripping faucets and stops.
E. Clean fixtures, faucets, and other fittings, including flush tanks, with manufacturers'
recommended cleaning methods and materials. Include the following:
1. Remove faucet spouts and strainers, remove sediment and debris, and reinstall
strainers and spouts.
2. Remove sediment and debris from flush tanks and drains.
0.7 PROTECTION
B. Do not allow use of fixtures for temporary facilities, except when approved in writing by the
Engineer.
A. Water Closet EWC-[#]: Where plumbing fixtures of this designation are indicated, provide
products complying with the following:
3. Flushometer Valve:
4. Toilet Seat:
16. Flushometer Valve Finish: [Rough brass.] [Polished, chrome-plated, exposed metal
parts.]
17. Flushometer Valve, Water Consumption and Pressure: Factory set or field adjusted,
6 L maximum per flushing cycle at 0.5 bars. <INSERT OTHER>
18. Flushometer valve components include the following:
B. Wheelchair Water Closets: Provide same as specified for water closets P-[ ] except water
closet height to top of seat shall be 432 to 483 mm above floor and complete with two white
nylon coated aluminium grap/support rails with fixing plates to wall provided with four sets
of walls plugs and 45 mm screws, 450 mm and 970 mm long
A. [Accessible] }Urinal UR-[#]: Where plumbing fixtures of this designation are indicated,
provide products complying with the following:
4. Flushometer Valve:
5. Fixture Color: [White.] <INSERT OTHER>
6. Type and Operation: [Siphon jet.] [Washdown.] [Blowout.] <INSERT OTHER>
7. Mounting and Outlet: [Wall hanging, back outlet.] [Wall hanging, bottom outlet.]
[Floor mounted, floor outlet.]
8. Fixture Bolt Caps: [White,] [Color matching bowl,] plastic or china.
9. Rim Height: [610 mm.] [432 mm.] <INSERT OTHER>
10. Design Water Consumption: [3.8 L per flushing cycle.] <INSERT OTHER>
11. Flushometer Valve Construction: Cast-brass body, brass or copper pipe or tubing
inlet with wall flange and tailpiece with spud, screwdriver check stop, and vacuum
breaker.
12. Flushometer Valve Operation: [Diaphragm.] <INSERT OTHER>
13. Flushometer Valve Finish: [Rough brass.] [Polished, chrome-plated, exposed metal
parts.]
14. Flushometer Valve, Water Consumption and Pressure: [Factory set or field adjusted,
3.8 L maximum per flushing cycle at 0.5 bars.] <INSERT OTHER>
15. Flushometer valve components include the following:
16. Fixture Support: Type I, vertically adjustable, urinal, chair carrier with coupling;
[steel-pipe] [heavy-duty, rectangular-steel,] upright members; bearing plate; and feet.
<INSERT OTHER>
17. Reinforcement: <INSERT SPECIFIC REQUIREMENTS, IF APPLICABLE>
B. Wheelchair Flush Valve Type Urinals: Provide same as specified for urinal UR [] except
with elongated projecting bowl, 508 mm long from wall to front of flare, and ASME
A112.19.5 trim. Furnish urinal manufacturer's certification of conformance. Provide
ASME A112.6.1M concealed chair carriers. Mount urinal with front rim a maximum of 432
mm above floor and flush valve handle a maximum of 1118 mm above floor for use by
handicapped on wheelchair.
A. Bidet BD-[#]: Where plumbing fixtures of this designation are indicated, provide products
complying with the following:
a. Handle{s}: [Dual lever.] [Dual, metal knobs.] [Dual, crystal knobs.] [Single
lever.] <INSERT OTHER>
b. Spout: [Integral with body.] [Spray nozzle in bowl.] <INSERT OTHER>
A. [Accessible] Lavatory LAV-[#]: Where plumbing fixtures of this designation are indicated,
provide products complying with the following:
6. Stainless-Steel Lavatory:
7. Plastic Lavatory:
8. Faucet:
a. <INSERT PRODUCT NAME;>
a. <INSERT PRODUCT NAME;>
above rim, 100 mm wrist action handles, perforated grid strainers with offset tailpiece, and
32 mm adjustable P-trap.
A. [Accessible] Shower SH-[#]: Where plumbing fixtures of this designation are indicated,
provide products complying with the following:
4. Antiscald Faucet:
19. Supplies: [Copper tubing with ball, gate, or globe valve if check stops not included
with faucet.] <INSERT OTHER>
20. Drain: [Included with enclosure.] [Included with receptor.] [DN50, nickel-bronze-
strainer, floor drain.] <INSERT OTHER>
21. Trap: [DN50 drainage piping.] <INSERT OTHER>
22. Reinforcement: <INSERT SPECIFIC REQUIREMENTS, IF APPLICABLE; ADD
BASE SUPPORT IF REQUIRED>
A. [Accessible ]Bathtub BT-[#]: Where plumbing fixtures of this designation are indicated,
provide products complying with the following:
5. Plastic Bathtub:
14. Supplies: [Copper tubing with ball, gate, or globe valve if check stops not included
with faucet.] <INSERT OTHER>
15. Supplies: DN15 copper tubing. <INSERT OTHER>
16. Waste and Overflow Fitting: DN40, [1.1 mm] [0.8 mm] wall thickness, tubular brass.
Include lever-operated, pop-up waste and overflow with universal-type outlet
connection on waste tee; and DN40, [1.1 mm] [0.8 mm] wall thickness, tubular
waste. <INSERT OTHER>
17. Trap: DN40 cast brass with [pipe] [1.1 mm wall thickness, tubular-brass] waste.
<INSERT OTHER>
18. P-Trap: [DN40] [DN50] drainage piping.
19. Reinforcement: <INSERT SPECIFIC REQUIREMENTS, IF APPLICABLE; ADD
BASE SUPPORT IF REQUIRED>
A. [Accessible] Whirlpool Bathtub WP-[#]: Where plumbing fixtures of this designation are
indicated, provide products complying with the following:
A. [Accessible] Wash Fountain WF-[#]: Where plumbing fixtures of this designation are
indicated, provide products complying with the following:
A. [Accessible] Sink S-[#]: Where plumbing fixtures of this designation are indicated, provide
products complying with the following:
a. <INSERT PRODUCT NAME>
a. <INSERT PRODUCT NAME>
a. <INSERT PRODUCT NAME>
6. Plastic Sink:
a. <INSERT PRODUCT NAME>
7. Faucet:
a. <INSERT PRODUCT NAME>
a. <INSERT PRODUCT NAME>
9. Disposer:
a. <INSERT PRODUCT NAME>
a. <INSERT PRODUCT NAME>
a. <INSERT PRODUCT NAME>
21. Supply Inlets: [DN15, brass pipe or copper tubing.] <INSERT OTHER>
22. Supply Stops: Manufacturer's standard brass, angle or straight, compression, [loose-
key type,] [wheel-handle type,] same size as supply inlet and with outlet matching
supply riser. <INSERT OTHER>
23. Supply Shutoff Valves: DN15 gate, globe, or ball.
24. Supply Risers: [DN10 flexible with knob end.] [DN10 rigid with DN8 straight,
knob-end tailpiece.] [DN10 rigid with DN8 offset, knob-end tailpiece.] [DN15 copper
tubing.] <INSERT OTHER>
25. Supply, Flow-Control Restrictors: DN15, [0.032 L/s.] [0.06 L/s.] <INSERT
OTHER>
26. Drain[s]: [38 mm grid strainer with] [38 mm removable, stainless-steel strainer
bucket with] [89 mm grid strainer with] [89 mm removable, stainless-steel crumb
cup with] [89 mm removable, chrome-plated, brass crumb cup with] [DN40 tubular-
brass tailpiece.] [DN40 tubular stainless-steel tailpiece.] <INSERT OTHER>
27. Plaster Sink Drain: Grid strainer with [DN40,] [DN50,] 1.1 mm thick, tubular-brass
tailpiece. <INSERT OTHER>
28. Plaster Sink Waste: [DN40,] [DN50,] 1.1 mm thick, tubular-brass tailpiece.
<INSERT OTHER>
29. Continuous Waste: [DN40,] [1.1 mm thick, tubular brass with slip-joint inlet.] [0.8
mm thick, tubular brass with slip-joint inlet.] [tubular plastic with slip-joint inlet.]
<INSERT OTHER>
30. Tubular Trap: [DN40,] [1.1 mm wall thickness, tubular brass,] [0.8 mm wall
thickness, tubular brass,] [plastic tubular fittings,] with slip-joint inlet [, cleanout,]
and wall flange.
31. Cast-Brass Trap: [DN40,] [DN40 by DN32,] cast-brass trap, with slip-joint inlet,
[cleanout,] [DN32,] [DN40,] pipe nipple to wall, and wall flange.
32. Cast-Brass/Tubular Trap: [DN32,] [DN40 by DN32,] cast-brass trap, with slip-joint
inlet, {cleanout,} [DN32] [DN40] tubular brass, waste to wall, and wall flange.
33. Indirect Waste: [DN40,] [DN50,] [1.1 mm thick,] [0.8 mm thick,] [tubular brass.]
[plastic tubular fittings.] [pipe.] <INSERT OTHER>
34. Interceptor: [Cast iron with interior and exterior, acid-resistant-enamel coating,]
[Stainless-steel] [plaster] [sediment] interceptor designed for floor mounting. Include
[DN40,] [DN50,] inlet and outlet; removable, corrosion-resistant screens or bucket;
and [DN40,] [DN50,] waste piping with wall flange.
35. Food-Waste Disposer: Household, continuous feed. Include 115 VAC, 29-rev/s
motor with overload protection and reset button; wall switch; corrosion-resistant
chamber with jam-resistant grinder or shredder; DN40 outlet; quick-mounting,
stainless-steel sink flange; antisplash guard; and combination cover/stopper.
<INSERT OTHER DESCRIPTION; BATCH-FEED TYPE IS ALSO AVAILABLE>
a. Model: [1/3 hp,] [1/2 hp,] [3/4 hp,] model with cutlery- or stainless-steel
grinder or [shredder.] [shredder and sound-insulated chamber.] [shredder,
sound-insulated chamber, and stainless-steel outer shell.] <INSERT OTHER>
37. Supply Insulation Kit: [Molded, soft-plastic covering for supplies from wall to
fixture with removable covering for stops and handles.] [Molded, soft-plastic
covering for hot-water supply from wall to fixture with removable covering for stop
and handle.] [Shaped, cushioned-jacket plastic covering with self-sticking fastening
system for supply stops and risers to fixture.] [Shaped, cushioned-jacket plastic
covering with self-sticking fastening system for hot-water supply stop and riser to
fixture.] Include manufacturer's standard fasteners, straps, and adhesives. <INSERT
COLOR IF REQUIRED>
38. Drain Insulation Kit: [Molded, soft-plastic covering for drain piping from fixture to
wall.] [Shaped, cushioned-jacket plastic covering with self-sticking fastening system
for drain piping and trap.] Include manufacturer's standard fasteners, straps, and
adhesives. <INSERT COLOR IF REQUIRED>
39. Fixture Support: [Type I, exposed arm;] [Type II, hanger plate;] [Type III,
combination, exposed arm and hanger plate;] [Type IV, support plate;] vertically
adjustable, sink, chair carrier with [steel-pipe] [heavy-duty, rectangular-steel,] upright
members; and feet. <INSERT OTHER>
40. Reinforcement: <INSERT SPECIFIC REQUIREMENTS, IF APPLICABLE>
A. Service Sink SS-[#]: Where plumbing fixtures of this designation are indicated, provide
products complying with the following:
6. Faucet:
a. <INSERT PRODUCT NAME>
14. Trap Standard: [DN80 ] [DN50 ] with grid strainer, enameled interior, cleanout, floor
support, and pipe waste to wall. <INSERT OTHER>
15. Drain: [DN80 ] [DN50 ] with grid strainer. <INSERT OTHER>
16. P-Trap: [DN80 ] [DN50 ] drainage piping.
17. Supplies: DN15 copper tubing{ with ball, gate, or globe valve}. <INSERT
OTHER>
18. Reinforcement: [Provide for wall-mounting faucet{ and wall brace}.] <INSERT
SPECIFIC REQUIREMENTS, IF APPLICABLE>
A. Mop-Service Basin MS-[#]: Where plumbing fixtures of this designation are indicated,
provide products complying with the following:
6. Faucet:
a. <INSERT PRODUCT NAME>
A. Laundry Tray LT-[#]: Where plumbing fixtures of this designation are indicated, provide
products complying with the following:
10. Supply Inlets: [DN15, brass pipe or copper tubing.] <INSERT OTHER>
11. Supply Stops: Manufacturer's standard brass, angle or straight, compression, [loose-
key type,] [wheel-handle type,] same size as supply inlet and with outlet matching
supply riser. <INSERT OTHER>
12. Supply Shutoff Valves: DN15 gate, globe, or ball.
13. Supply Risers: [DN10 flexible with knob end.] [DN10 rigid with DN8 straight,
knob-end tailpiece.] [DN10 rigid with DN8 offset, knob-end tailpiece.] [DN15
copper tubing.] <INSERT OTHER>
14. Drain{s}: Manufacturer's standard grid drain with DN40 tubular-brass tailpiece.
<INSERT OTHER>
15. Continuous Waste: [DN40,] [1.1 mm thick, tubular brass with slip-joint inlet.] [0.8
mm thick, tubular brass with slip-joint inlet.] [tubular plastic with slip-joint inlet.]
<INSERT OTHER>
16. Tubular Trap: [DN40,] [1.1 mm wall thickness, tubular brass,] [0.8 mm wall
thickness, tubular brass,] [plastic tubular fittings,] with slip-joint inlet [, cleanout,]
and wall flange.
17. Cast-Brass Trap: DN40, cast-brass trap, with slip-joint inlet, [cleanout,] DN40, pipe
nipple to wall, and wall flange.
18. Cast-Brass/Tubular Trap: DN40, cast-brass trap, with slip-joint inlet, [cleanout,]
DN40 tubular brass, waste to wall, and wall flange.
19. Fixture Support: [Type I, exposed arm;] [Type II, hanger plate;] [Type III,
combination, exposed arm and hanger plate;] vertically adjustable, sink, chair carrier
with steel-pipe upright members and feet.] [Manufacturer's standard steel stand or
base unit.] <INSERT OTHER>
20. Reinforcement: [Provide for wall-mounting faucet.] <INSERT SPECIFIC
REQUIREMENTS, IF APPLICABLE>
A. Shampoo Bowl SB-[#]: Where plumbing fixtures of this designation are indicated, provide
products complying with the following:
4. Hair Interceptor:
a. <INSERT PRODUCT NAME>
A. [Accessible ]Drinking Fountain DF-[#]: Where plumbing fixtures of this designation are
indicated, provide products complying with the following:
A. [Accessible ]Electric Water Cooler EWC-[#]: Where plumbing fixtures of this designation
are indicated, provide products complying with the following:
3. Fixture Type: [Bubbler.] [Bilevel bubbler.] [Bubbler with hot-water faucet.] [Bottle.]
[Bubbler with remote chiller.] <INSERT OTHER>
4. No. of Bubblers or Stations: [One.] [2.] [3.] <INSERT OTHER>
5. Fixture Unit Capacity: <INSERT CAPACITY CHILLED WATER>
6. Fixture Cabinet Material: [Stainless steel.] [Enameled steel.] [Vinyl-covered steel.]
<INSERT OTHER>
7. Fixture Color or Finish: <INSERT COLOR OR FINISH>
8. Fixture Mounting: [Wall.] [Free standing.] [Semirecessed.] [Recessed.] <INSERT
OTHER>
9. Wall Grille: [Stainless steel.] [Enameled steel.] <INSERT SIZE>
10. Supply: DN10 copper tubing with gate, globe, or ball valve. <INSERT OTHER>
11. Water Filter: [Manufacturer's standard.] [Cartridge type for 254 mm cartridge with
stainless-steel or plastic housing, fittings, and mounting bracket. Include replaceable,
activated-carbon, wound-fiber, or pleated cartridge with 10-micron removal rating.]
12. Cast-Brass Trap{s}: [DN32,] [DN40 by DN32,] cast-brass trap, with slip-joint inlet,
[cleanout,] [DN32,] [DN40,] pipe nipple to wall, and wall flange.
13. Supply Insulation Kit{s}: [Molded, soft-plastic covering for supply from wall to
fixture with removable covering for stop and handle.] [Shaped, cushioned-jacket
plastic covering with self-sticking fastening system for supply stop and riser to
fixture.] Include manufacturer's standard fasteners, straps, and adhesives. <INSERT
COLOR IF REQUIRED>
14. Drain Insulation Kit[s]: [Molded, soft-plastic covering for drain piping from fixture
to wall.] [Shaped, cushioned-jacket plastic covering with self-sticking fastening
system for drain piping and trap.] Include manufacturer's standard fasteners, straps,
and adhesives. <INSERT COLOR IF REQUIRED>
15. Fixture Support: [Type I,] [Type II, bilevel,] vertically adjustable, hanger-plate,
water-cooler, chair carrier with [steel-pipe] [heavy-duty, rectangular-steel,] upright
members, bearing plate[s], and feet. <INSERT OTHER>
16. Reinforcement: [Fabricate to enclose mounting box.] <INSERT SPECIFIC
REQUIREMENTS, IF APPLICABLE>
B. Wheelchair Electric similar to Water Cooler EWC[ ]) except cooler is provided with 686
mm minimum knee clearance from front bottom of unit to floor and 914 mm maximum
spout height above floor. Bubblers shall also be controlled by push levers, by push bars, or
touch pads one on each side or one on front and both sides of the cabinet
4. Toilet Seat:
5. Faucet:
a. <INSERT PRODUCT NAME>
17. Faucet Construction: [Center set with inlets on 102 mm centers,] [Center set with
central inlets,] [Widespread with inlets on 203 mm centers,] [Single-inlet,] [cast
brass,] [cast-brass underbody and brass escutcheon,] [nonmetal (plastic) underbody
and plastic or brass escutcheon,] [and with pop-up waste.] [and without pop-up
waste.] <INSERT OTHER>
18. Faucet Valve Operation: [Manual, ON-OFF.] [Manual, adjustable, self-closing,
metering.] [Electric, hard wired, sensor actuation, automatic.] <INSERT OTHER>
19. Faucet Mounting Position: [Centered on fixture deck.] [Counter, centered on fixture.]
[Centered on fixture backsplash.]
20. Faucet Components: Include the following:
system for supply stops and risers to fixture.] [Shaped, cushioned-jacket plastic
covering with self-sticking fastening system for hot-water supply stop and riser to
fixture.] Include manufacturer's standard fasteners, straps, and adhesives. <INSERT
COLOR IF REQUIRED>
31. Drain Insulation Kit: [Molded, soft-plastic covering for drain piping from fixture to
wall.] [Shaped, cushioned-jacket plastic covering with self-sticking fastening system
for drain piping and trap.] Include manufacturer's standard fasteners, straps, and
adhesives. <INSERT COLOR IF REQUIRED>
32. Fixture Support: Vertically adjustable, cast-iron, [elevated-type,] water-closet carrier
with combination support and waste fitting assemblies and tiling frame or setting
gage. Include additional faceplate and coupling for water closet at wide pipe space.
Compact-type carrier for back-to-back water-closet installation is prohibited.
33. Fixture Support: [Vertically adjustable, chair carrier with support plate or device
matching fixture mounting; steel-pipe upright members; and feet.] <INSERT
OTHER>
34. Reinforcement: <INSERT SPECIFIC REQUIREMENTS, IF APPLICABLE>
END OF SECTION 15440