Reference Book: Building Code Requirements For Structural Concrete (ACI 318M-14)

The document provides material properties and design load values for structural concrete design including: 1) Concrete with a compressive strength of 30MPa and rebar with yield strengths of 390MPa and 235MPa are specified. 2) Dead loads include floor finishes ranging from 1.1-1.8 kN/m^2, wall loads of 4.3-2.4 kN/m^2. 3) Live loads range from 0.96-4.8 kN/m^2 for uses like offices, corridors, and roofs. Impact and lateral loads are also defined.

Uploaded by

Peter Son
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
85 views

Reference Book: Building Code Requirements For Structural Concrete (ACI 318M-14)

The document provides material properties and design load values for structural concrete design including: 1) Concrete with a compressive strength of 30MPa and rebar with yield strengths of 390MPa and 235MPa are specified. 2) Dead loads include floor finishes ranging from 1.1-1.8 kN/m^2, wall loads of 4.3-2.4 kN/m^2. 3) Live loads range from 0.96-4.8 kN/m^2 for uses like offices, corridors, and roofs. Impact and lateral loads are also defined.

Uploaded by

Peter Son
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

A.

Material Properties

Reference Book: Building Code Requirements for Structural Concrete (ACI 318M-14)

o Concrete Compressive Strength

 Compressive strength of concrete (cylinder): 30 MPa for flexural members


 Compressive strength of concrete (cylinder): 30 MPa for compressive members

o Rebar

 Rebar Yield Strength (Main bar) : fy = 390 MPa


 Rebar Yield Strength(Confinement bar ) : fy = 235 MPa

o Concrete Unit Weight :


 c = 24.0 kN/m3

o Rebar Unit Weight :


 s = 78.5 kN/m3
o Modulus of Elasticity of Concrete : Ec = 4700√f'c (ACI Section 19.2.2)
 Flexural members, (f'c=30MPa) : Ec = 25740 MPa
 Compressive members, (f'c=30MPa) : Ec = 25740 MPa
o Modulus of Elasticity of Steel : Es = 200000 MPa

B. Design Loads

Reference Book: ASCE 7-10 Minimum Design Loads for Buildings and Other Structures

1. Dead loads (Super DL)


o Floor finish/ floor topping/ MEP/ floor suspending

a. Ceramic tile(19mm) and mortar(25mm) : 1.10 kN/m² (Table C3-1)/page 402


b. Mechanical duct allowance : 0.19 kN/m² (Table C3-1)/page 401
c. Suspended metal lath and gypsum plaster : 0.48 kN/m² (Table C3-1)/page 401
d. Plastering one sides : 0.24 kN/m² (Table C3-1)/page 401
e. Waterproofing membranes at top roof
(Bituminous, gravel-covered) : 0.26 kN/m² (Table C3-1)/page 402

Super DL, Sum (N: = a) : 1.10 kN/m², use for ground floor
Super DL, Sum (N: a + b + d) : 1.53 kN/m², used for room, corridor
Super DL, Sum (N: a + b + d +e) : 1.79 kN/m², used for roof floor
Super DL, Sum (N: a + d) : 1.34 kN/m², used for staircase
o Walls

a. Clay brick wall 200 mm { = 3.78kN/m² }: (Table C3-1)/page 403, including


plastering both sides { = 0.24kN/m² x 2 }: (Table C3-1)/page 401: 4.26kN/m²

b. Clay brick wall 100 mm { = 1.87kN/m² }: (Table C3-1)/page 403, including


plastering both sides { = 0.24kN/m² x 2 } (Table C3-1)/page 401: 2.35kN/m²
2. Live loads
o Residential, Office
a. Private room corridors serving them : 1.92 kN/m² (Table C4-1)/page 414
b. Office room : 2.40 kN/m² (Table 4-1) page 17
c. Public room and corridors serving them : 4.79 kN/m² (Table 4-1)/page 18
d. Dining room, Restaurant and Cafeteria : 4.79 kN/m² (Table 4-1) page 17
e. Gymnasiums : 4.79 kN/m² (Table 4-1) page 18
f. Swimming pool, Steam and Sauna : 4.79 kN/m² (Adopt: Gymnasiums)
g. Space room for MEP : 3.83 kN/m² (Adopt: Storage room)
h. Storage : 3.83 kN/m² (Table C4-1) page 414
i. Lobby (Assembly areas) : 4.79 kN/m² (Table 4-1) page 17
j. Terrace space (at roof floor) : 4.79 kN/m² (Table 4-1) page 19
k. Top roof floor (roof live load at top) : 0.96 kN/m² (Table 4-1) page 18
l. Stair and exit way : 4.79 kN/m² (Table 4-1) page 18
m. Garage/passenger cars (1.92kN/m²)
, impact factor increase 75% : 1.92 x 1.75 = 3.36kN/m²
(ASSTHO-LRFD 2012)/TABLE 3.6.2.1-1
page 3-31
n. Lift LL, impact factor increase 100% : 1000kg: (10kN x 2 = 20kN), specify
(C4.6_Impact Loads)/page 409.
o. Elevator: weight of actual equipment (fixed service equipment is treated as a dead
load instead of live load). : 7.18 kN/m² (Table C4-1)/page 414
p. Maintenance (curved roof live load) : 0.58 kN/m² (Section4.8.2) page 15
q. Load on handrail (horizontal or vertical) : 0.73 kN/m (Section4.5.1) page 14

3. Other loads

o Water (water tank) as a dead load: (2.3.2 Basic Combinations)/page 07 : 10kN/m³


o Lateral earth pressures for brick wall, where load factor of 1.6 as live load (2.3.2 Basic
Combinations)/page 07.
 Soil density, s : 20kN/m³ (geological investigation)
o Wind speed: 70-110 mph (30 – 50 m/s). Use 75 mph (33.5 m/s or 120 Km/h) is the
lowest level of storm wind.
 Exposure Type :B
 Topographical Factor, Kzt : 1.0
 Gust Factor, G (Rigid building) : 0.85
 Directionality Factor, Kd : 0.85
 Design Wind Load Case
 All Case: Case1, Case2, Case3 and Case4 (12 Set)