Data Sheet 6AG1332-1SH71-4AA0: Input
Data Sheet 6AG1332-1SH71-4AA0: Input
Input
Input 1-phase AC
● Note Automatic range selection
supply voltage
● 1 at AC rated value 120 V
● 2 at AC rated value 230 V
input voltage
● 1 at AC 85 ... 132 V
● 2 at AC 176 ... 264 V
Wide-range input No
Overvoltage resistance 2.3 × Vin rated, 1.3 ms
Mains buffering at Vin = 93/187 V
Mains buffering at Iout rated, min. 20 ms; at Vin = 93/187 V
Rated line frequency 1 50 Hz
Rated line frequency 2 60 Hz
Rated line range 47 ... 63 Hz
input current
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.1 %
Static load balancing, approx. 0.2 %
Residual ripple peak-peak, max. 150 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 240 mV
product function output voltage adjustable No
Output voltage setting -
Status display Green LED for 24 V OK
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 6 s; 2 s at 230 V, 6 s at 120 V
Voltage rise, typ. 10 ms
Rated current value Iout rated 2.5 A
Current range 0 ... 2.5 A
supplied active power typical 60 W
short-term overload current
● on short-circuiting during the start-up typical 6 A
● at short-circuit during operation typical 6 A
duration of overloading capability for excess current
● on short-circuiting during the start-up 100 ms
● at short-circuit during operation 100 ms
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced 2
performance
Efficiency
Efficiency at Vout rated, Iout rated, approx. 83 %
Power loss at Vout rated, Iout rated, approx. 12 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), 0.3 %
max.
Safety
Primary/secondary isolation Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class I
leakage current
● maximum 3.5 mA
Degree of protection (EN 60529) IP20
Approvals
CE mark Yes
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation not applicable
Noise immunity EN 61000-6-2
environmental conditions
ambient temperature in horizontal mounting position 0 ... 60; with natural convection
during operation
ambient temperature during storage and transport -40 ... +85
installation altitude at height above sea level 6 000 m
maximum
ambient condition relating to ambient temperature - In case of operation at altitudes of 2000 - 6000 m above sea level:
air pressure - installation altitude Output power derating of -7.5 %/1000 m or reduction of the
ambient temperature by 5 K/1000 m
relative humidity with condensation acc. to IEC 100 %; RH incl. condensation/frost (no commissioning if
60068-2-38 maximum condensation is present), horizontal installation
chemical resistance to commercially available cooling Yes; incl. diesel and oil droplets in the air
lubricants
resistance to biologically active substances Yes; Class 3B2 mold, fungal, sponge spores (except fauna); class
conformity acc. to EN 60721-3-3 3B3 upon request
Mechanics
Connection technology screw-type terminals
Connections
● Supply input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
● Output L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
● Auxiliary -
width of the enclosure 70 mm
height of the enclosure 100 mm
depth of the enclosure 75 mm
required spacing
● top 20 mm
● bottom 20 mm
● left 0 mm
● right 0 mm
Weight, approx. 0.3 kg
product feature of the enclosure housing can be lined Yes
up
Installation Snaps onto DIN rail EN 60715 35x7.5/15, wall mounting
MTBF at 40 °C 1 492 537 h
other information Specifications at rated input voltage and ambient temperature +25
°C (unless otherwise specified)