Interactive Solutions Tool

High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

IA/NG Use this interactive document to:


Intelligent Software
& Analysis Tools 1. Understand processes and technical concepts
2. Become aware of Emerson’s full capabilities
IA/NG 3. Illustrate Emerson’s featured products and
DVC value
1-A
SIS
LS Customers Pain
DVC
1-B
When pressure relief valves (PVR) are not
appropriate, many industry codes require SIL
S
rated protection of downstream equipment
through isolation of the pressure source
S
Reasons for Pain
PT PT PT
ZLS ZLS
101-A 101-B 101-C High pressure release is impossible or
impractical

FC FC Environmental protection is mandated


FBV 1-A FBV 1-B

Facility / Asset updates require flare capacity


expansion
Full HIPPS Simple to Installation
Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

Full Service Vendor


There are many challenges engineering, building,
installing and operating a HIPPS, to ensure that
the system will provide the required safety
throughout the lifetime of the installation.
Emerson has a one-stop-shop solution for HIPPS,
which is not limited to providing best in class
products, but also includes the resources
necessary to support all phases of a HIPPS
lifecycle. Emerson products and services will
ensure compliance with functional standards and
jurisdictional requirements and are configured to
minimize systematic failures.
Emerson has developed a global process for
compliant HIPPS design including the
development of SRS, verification, test and
calibration records to ensure all requirements of
IEC 61511 / ISA 84 have been met.

Full HIPPS Simple to Installation


Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

Experience in Valve & Actuation Systems


Emerson’s experience with hundreds of HIPPS
applications means that we recognize that
operating the large mechanical forces in a
controlled manner is imperative. We understand
that shut down of the final element depends
heavily on the design and selection of the correct
valve and actuator and the speed of the
shutdown are critical.
Proven experience with fast closing, critical valves
and actuators include:
· Local, Regional and Global Integration
· All type of Valves and Actuators
· SIL Rated Designs Available
· Full Lifecycle Support Capabilities

Full HIPPS Simple to Installation


Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

Simple to Highly Engineered Solutions


Emerson’s product designs are the result of
decades of experience. Our engineers are
equipped with the latest software tools to
provide products that range from simple on-off
valves to fully integrated HIPPS solutions
encompassed by product, documentation,
verification and validation services.
We are committed to delivering proven products
that are thoroughly tested to ensure they comply
with industry standards and maintain the highest
safety ratings. Many of our products are certified
to global performance standards by respected 3rd
party organizations.
· Complete range of products
· Engineered and fully tested HIPPS
systems
· On-off valves and actuators
· Proven services

Full HIPPS Simple to Installation


Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

Consulting Capability
Once the over pressure hazards have been
identified and a risk mitigation factor established,
developing the Safety Requirements
Specification (SRS) becomes the heart of every
successful HIPPS Project.
Emerson’s consultants and engineers are
experienced in the methods for pre-feed
engineering, data gathering, SIL analysis, and are
expert at the process of developing the important
SRS documents.
Being in the unique position to have all products
in our portfolio plus many years of experience
integrating HIPPS systems, our staff of engineers
and safety consultants can complement your
development team.
• Pre-FEED Engineering
• SIL Verification Analysis
• Development of the SRS
• Experienced Safety Consultants

Full HIPPS Simple to Installation


Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

Regional Project Execution Capability


Emerson has developed a global network of
automation service facilities including system
engineering and design, integration to provide a
full suite of lifecycle services.
Executing projects in different world areas can be
challenging and introduces an increased risk of
project failure if not handled correctly. This is why
Emerson’s integration centers utilize a common
SIS processes that has been developed in full
compliance with IEC 61511 / ISA 84.
· Globally consistent process
· Consistent HIPPS designs
· Elimination of systematic failures
· Full suite of lifecycle services

Full HIPPS Simple to Installation


Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

Certification and Testing


Certification of the final element to the required
Safety Integrity Level (SIL) is often difficult
because it is only part of the Safety Instrumented
Function (SIF).
Emerson’s engineers are experienced in the
validation and verification of SIL rated systems
and the procedures that ensure the HIPPS system
fully meets the requirements defined in the SRS.
In addition, Emerson has the capability to
performance test the Final Element of the
Automated Valve Assembly and can certify the
valve to any specified application criteria.
· Expertise to design and integrate complex
systems
· Certification to the overall SIL rating
· Performance Testing of Final Elements
IEC61511 / ISA 84 Safety Lifecycle · Global process for HIPPS design

Full HIPPS Simple to Installation


Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

Installation & Commissioning


Correct installation and commissioning of the
HIPPS is critical for the safety function. Selecting a
supplier with experienced resources and proven
capability to handle the full scope of the project
including an integrated site acceptance test is
important.
Emerson engineers also have the experience and
resource to provide validation services anywhere
in the world, ensuring that your HIPPS system will
function as designed for the life of the facility.
· Comprehensive Lifecycle Services
· Globally Resourced
· Experienced Resources

IEC61511 / ISA 84 Safety Lifecycle

Full HIPPS Simple to Installation


Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

Lifecycle Services
Implementation of a HIPPS requires that the
integrity of the automation system be
maintained for the lifespan of the facility. The
system functionality must be reliable to ensure its
operation under all operating conditions to
protect your assets and the people who work in
the facility.
Key to this is accessing the right resources
necessary to keep your plant performing
optimally and achieve your business goals.
Emerson’s Lifecycle Services will assist you in
managing the total cost of ownership by
providing the proactive maintenance resources
that help to plan and implement a long-term
lifecycle strategy for reliability and risk
management.
· Local, Factory Trained Resource
· Experience with all Automated Valve
Assemblies
· Ensures Highest System Reliability

Full HIPPS Simple to · Manage the total cost of ownership


Installation
Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

HIPPS System Description


Logic Solver

Educational Services
Educational Services focuses on training our
customers on Emerson products and the HIPPS
solutions we provide to ensure they have a
working knowledge of product capabilities, as
well as safe use and proper maintenance and
repair procedures.
Emerson’s world class training program enables
customers to maximize their product investment
and extend the reliability of Emerson products
under all operating conditions throughout the
lifetime of the asset.
· Training for all Emerson products
· Operational testing programs
· Maintenance procedures training
· Local & web-based training available

Full HIPPS Simple to Installation


Consulting Project Certification Lifecycle Educational
Service Systems Complex and
Capability Execution and Testing Commissioning
Support Services
Vendor Experience Solutions

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Overpressure Logic
Protection
SolverSystem Types

IA/NG Since each over pressure protection system is


Intelligent Software focused on a unique application, the
& Analysis Tools
requirements and architecture must be
thoroughly analyzed and defined based upon
IA/NG applicable codes and standards. The main
categories of over pressure protection systems
DVC
include:
1-A
SIS · High Integrity Pressure Protection System - HIPPS
LS
DVC
1-B
· Shut Down Valve - SDV / ESDV
· Blow Down Valve - BDV

S · On-Off Isolation Valve - XV


· Self-Contained Hydraulic ESD
S

PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Shut Down Blow Down


HIPPS Isolation Valve Hydraulic ESD
Valve Valve

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Overpressure Logic
Protection
SolverSystem Types

IA/NG High Integrity Pressure Protection System - HIPPS


Intelligent Software
& Analysis Tools When it is impractical to apply a mechanical
pressure relief device, the HIPPS can be used to
provide the “last line of defense,” to prevent
IA/NG vessel or pipeline rupture. These systems are
DVC designed to isolate high operating pressure so
1-A using a performance-based life-cycle approach in
SIS their design is essential.
LS
DVC
A SIL rated HIPPS design is typically used to
1-B
mitigate risk if the pressure within a vessel or
pipeline that has the potential to exceed 116% of
the rated design pressure.
S
The main components of a HIPPS are designed for
S fault tolerance and include:

PT PT PT
· Pressure sensors
ZLS ZLS
101-A 101-B 101-C · Logic solver
· Fail-safe actuators
FC
FBV 1-A
FC
FBV 1-B
· Emergency shutdown valves
· Online diagnostics and partial-stroke test
components

Shut Down Blow Down


HIPPS Isolation Valve Hydraulic ESD
Valve Valve

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Overpressure Logic
Protection
SolverSystem Types

Shut Down Valve (SDV / ESDV)


A shut down valve is an actuated valve designed
to isolate the flow of a hazardous fluid or
hydrocarbon gas upon detection of a dangerous
event and provides protection against possible
IA/NG
harm to people, equipment or the environment.
DVC As shutdown valves often form part of a safety
instrumented system, they are primarily
associated with the Oil & Gas industry and
required by law on any equipment placed on an
S offshore drilling rig to prevent catastrophic
events.
· Suitable for remote and critical service
applications
· Can utilize pneumatic, hydraulic or
electro-hydraulic actuators
ESDV · Valve and actuators typically require SIL
Fail to close
compliance

Shut Down Blow Down


HIPPS Isolation Valve Hydraulic ESD
Valve Valve

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Overpressure Logic
Protection
SolverSystem Types

Blow Down Valve (BDV)


As the term blowdown implies, the purpose of
the valve is to immediately depressurize the
equipment in the event of specific process upsets
by sending the unwanted gases to flare. A BDV is
IA/NG
typically specified as a tight shut-off valve
configured to “fail-safe” by specifying that the
actuator’s spring will open the valve if the
electrical signal or upon the loss of instrument air.
Blowdown valves are emergency on-off valves
S activated by a signal from the Emergency
Shutdown (ESD) system rather than direct
initiation by over pressure sensors in the
protected equipment.
· Designed for tight shut-off
· Configured fail-safe
BDV · Initiated by SIS
Fail to open

Shut Down Blow Down


HIPPS Isolation Valve Hydraulic ESD
Valve Valve

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Overpressure Logic
Protection
SolverSystem Types

On-Off Isolation Valve and Actuator (XV)


The On-Off Isolation Valve ensures reliable on/off
service by maintaining process and production
safety at all times.
IA/NG Pneumatic, hydraulic and electric actuators can
be used to automate a variety of ball, triple offset
butterfly, butterfly, and other quarter-turn
devices. Typical actuator applications include
safety-related areas in nuclear service, gas
turbines, and auxiliary emergency shut off valves.
S
· Provides reliable on/off service
· Pneumatic, hydraulic and electric
actuators
· Used to automate quarter-turn valves
· Used as auxiliary emergency shut off
XV valves

Shut Down Blow Down


HIPPS Isolation Valve Hydraulic ESD
Valve Valve

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Overpressure Logic
Protection
SolverSystem Types

Self-Contained Hydraulic ESD


A self-contained hydraulic system is often
deployed for ESD applications in remote locations
where a power source is either not available or
not reliable.
When armed, the system is designed to remain
dormant until a violation of the user configurable
pressure setpoint is detected. A reliable pressure
switch will release the hydraulic pressure and a
mechanical spring will move the linear or rotary
valve to the fail-safe position.
· Suitable for remote and critical service
applications
· Simplified fail-safe design, with few parts
for increased reliability
· Eliminates the need for plant air,
electricity or nitrogen backup
· Control can be mounted onto standard
hydraulic actuators

Shut Down Blow Down


HIPPS Isolation Valve Hydraulic ESD
Valve Valve

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

System
LogicJustification
Solver

IA/NG Many codes and standards which define the use


Intelligent Software of a HIPPS require that the system be “as safe as,
& Analysis Tools
or safer than”, a conventional relief valve design.
These standards also imply that the
IA/NG implementation of a SIS should be based on the
DVC safety lifecycle defined by IEC 61511 / ISA 84
1-A standards which apply the concept of Safety
SIS Integrity Level, or SIL, to measure the amount of
LS
DVC risk reduction that a HIPPS system is capable of
1-B providing.
In comparison, a pressure relief valve will have a
probability that it will fail to open when a demand
S
occurs; so the justification for the use of HIPPS
must include an analysis of its Probability of
S
Failure on Demand (PFD) which is directly
PT PT PT
proportional to the system SIL rating.
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Regulatory Reduce Equipment


Reduce OPEX Reducing Risk MOC Analysis
Compliance CAPEX Protection

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

System
LogicJustification
Solver
Can HIPPS be Used?
Environmental & Regulatory Compliance
The justification must thoroughly document the
Is
vessel service YES
HIPPS cannot be used to hazards and identify all potential over pressure
replace PRV or Reduce
air, water, or steam?
Flare Loading
scenarios. It also requires that the design,
operation, maintenance, and testing to ensure
standard’s compliance is documented.
NO

Define Standards &


In addition, a rigorous testing and maintenance
Regulatory Requirements program must be achieved and must be
understood by all management, operations, and
Define Over Pressure Detailed Design
maintenance personnel.
Scenarios
All of this activity related to the design must be
Installation & documented in the SRS including:
Develop Safety Commissioning
Requirements Spec · Reasons for using HIPPS
YES
Operation
· Applicable standards
Conceptual
Design · All over pressure scenarios
NO
Maintain & Test
· SRS requirements defined
Verify SIL Meets · Risk mitigation level
Requirements

Regulatory Reduce Equipment


Reduce OPEX Reducing Risk MOC Analysis
Compliance CAPEX Protection

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

System
LogicJustification
Solver

Reducing CAPEX
The primary reduction in project cost from the
use of a HIPPS is the reduction of flare and
pressure relief manifold size when adding new
equipment to existing facilities.
Significant cost savings can also be realized by
minimizing the process downtime related to
equipment that will release pressurized product
into the header.
A HIPPS system can often be installed with
minimal process downtime when compared to a
flare system expansion project and provides the
following cost benefit:
· Eliminates need for resizing of the flare
and / or relief manifold
· Reduced process downtime
· Reduces the volume and number of
flaring events
· Cost of manual testing decreased

Regulatory Reduce Equipment


Reduce OPEX Reducing Risk MOC Analysis
Compliance CAPEX Protection

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

System
LogicJustification
Solver

Lowering Operational Cost


Installation of an Emerson HIPPS solution reduces
the labor to comply with the testing and
inspection requirements for mechanical over
pressure relief systems.
Other benefits include the reduction in the
volume and number of flaring events which has
become increasingly important as regulatory
agencies impose greater restrictions and
penalties on emissions and flaring events.
· Eliminates manual testing of PRV’s
· Reduces manual testing errors
· Automated recording of PST & trip events
· Extends time between proof tests

Regulatory Reduce Equipment


Reduce OPEX Reducing Risk MOC Analysis
Compliance CAPEX Protection

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

System
LogicJustification
Solver

Reducing a Plant's Risk Profile


Installation of the HIPPS system lowers the
potential of an over pressure event and can help
to eliminate releases to the environment thereby
reducing the plants risk profile.
Mitigation of risk is extended to the protection
equipment and includes:
· Safely combust the gases relieved during
an over pressure event
· Enhances PRV Functions
· Augments Flare System Protection
· Flare Load Mitigation

Regulatory Reduce Equipment


Reduce OPEX Reducing Risk MOC Analysis
Compliance CAPEX Protection

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

System
LogicJustification
Solver

Protect Downstream Assets


While these mechanical relief systems are still
widely available, regulatory restrictions are
becoming more restrictive especially when the
process fluid is flammable or toxic.
To overcome the challenge of protecting
downstream equipment and the environment,
facility operators are selecting Emerson’s HIPPS
technologies which allow them to:
· Protect Personnel
· Protect the environment
· Reduce the facility risk level
· Protects low pressure rated assets
· Operate under high pressures or flow
rates

Regulatory Reduce Equipment


Reduce OPEX Reducing Risk MOC Analysis
Compliance CAPEX Protection

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

System
LogicJustification
Solver

Management of Change Analysis


As pressure relief is one of the primary
applications necessitating PSM, any change to an
asset and / or procedure within a facility
represents the potential requirement to
reevaluate the integrity requirements of the
existing HIPPS.
This analysis can be prompted by:
· Operating Issues
· Regulatory Changes
· Near-Miss Investigations
· Changes in Mechanical Integrity
· Physical Asset Modifications

IEC61511 / ISA 84 Safety Lifecycle

Regulatory Reduce Equipment


Reduce OPEX Reducing Risk MOC Analysis
Compliance CAPEX Protection

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Solution
LogicEngineering
Solver

IA/NG There are many challenges that come with


Intelligent Software designing, analyzing, building and testing a HIPPS
& Analysis Tools
system.
Not only can Emerson supply all the necessary
IA/NG equipment with certified failure data for all
DVC components, but also contribute to the HIPPS
1-A design, verification of the SIL, development of
SIS procedures and inspection plans that include
LS
DVC proof test processes to ensure the safety integrity
1-B is maintained throughout the safety life cycle.
· Emerson - one stop solution supplier
S · Solutions Engineering to reduce HIPPS
complexities
S
· Integrated systems help ensure safety
PT PT PT integrity levels
ZLS ZLS
101-A 101-B 101-C · Products compliant to IEC 61508
· System designed in accordance with IEC
FC FC 61511 / ISA S84 standards
FBV 1-A FBV 1-B

SIL
Engineering Smart HIPPS Installation Field Testing Safety
Reduce Reduce Assembly
Reduce Reduce Verification
/ System Product and Procedures
Reduce OPEX Requirement
Reduce OPEX Reduce OPEX
OPEX OPEX andOPEX
Testing OPEX
Commissioning
Compliance
Integration Selection Manual Specification Report

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Solution
LogicEngineering
Solver

Engineering & System Integration


To achieve the desired level of protection, it is
essential that the design ensures all elements of
the HIPPS system will operate as designed when a
demand occurs.
Utilizing Emerson as the HIPPS integrator will
ensure the combination of sensing elements,
logic solver and final control elements meet the
integrity, operability and maintainability that is
desired in a HIPPS system and defined in the
Safety Requirements Specification (SRS):
· Functionality, availability, survivability
· Assessment of system integrity
· Well defined reliability data
· Reaction and response times of sensor,
logic solver and final elements
· Identifies and describes all credible
process and service conditions

SIL
Engineering Smart HIPPS Installation Field Testing Safety
Reduce Reduce Assembly
Reduce Reduce Verification
/ System Product and Procedures
Reduce OPEX Requirement
Reduce OPEX Reduce OPEX
OPEX OPEX andOPEX
Testing OPEX
Commissioning
Compliance
Integration Selection Manual Specification Report

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Solution
LogicEngineering
Solver

Smart HIPPS Product Selection


Component selection is a very important part of
designing a HIPPS system. Each product must be
SIL certified and selected so that no single device
can compromise the overall integrity target of
the HIPPS.
To become SIL certified under IEC 61508, the
supplier must demonstrate that the failure rate
and mode for each component in the product is
identified and minimizes the Probability of Failure
on Demand (PFD).
· The considerations for the PFD relate
directly to the SIL rating of the HIPPS and
include:
· Determining hardware failure rate
· Common mode failure percentage
· Proof test coverage
IEC61511 / ISA 84 Safety Lifecycle · Proof testing interval

SIL
Engineering Smart HIPPS Installation Field Testing Safety
Reduce Reduce Assembly
Reduce Reduce Verification
/ System Product and Procedures
Reduce OPEX Requirement
Reduce OPEX Reduce OPEX
OPEX OPEX andOPEX
Testing OPEX
Commissioning
Compliance
Integration Selection Manual Specification Report

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Solution
LogicEngineering
Solver

Assembly & Testing


Testing should demonstrate the system meets
the well-defined requirements of the Safety
Requirements Specification. Testing of a HIPPS
system not only consists of operational tests, but
also includes testing throughout the
manufacturing, commissioning and start-up
processes.
Testing often includes:
· Design validation test
· Factory acceptance tests
· Integrated factory acceptance test
· On-Site pre-commissioning tests
· Operational proof testing
· Site acceptance test
· HIPPS performance tests
IEC61511 / ISA 84 Safety Lifecycle

SIL
Engineering Smart HIPPS Installation Field Testing Safety
Reduce Reduce Assembly
Reduce Reduce Verification
/ System Product and Procedures
Reduce OPEX Requirement
Reduce OPEX Reduce OPEX
OPEX OPEX andOPEX
Testing OPEX
Commissioning
Compliance
Integration Selection Manual Specification Report

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Solution
LogicEngineering
Solver

Installation & Commissioning


This is final step in the process and one of the
most important as the testing should ensure that
the system was not damaged in shipment and
that all parts of the system were installed
correctly and the system performs as defined in
the SRS.
· Proof testing and site acceptance test
verifies operation of sensor, logic
controller and final element
· Validates installation and commissioning
procedures were complete
· Verifies all conditions of the SRS are met

IEC61511 / ISA 84 Safety Lifecycle

SIL
Engineering Smart HIPPS Installation Field Testing Safety
Reduce Reduce Assembly
Reduce Reduce Verification
/ System Product and Procedures
Reduce OPEX Requirement
Reduce OPEX Reduce OPEX
OPEX OPEX andOPEX
Testing OPEX
Commissioning
Compliance
Integration Selection Manual Specification Report

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Solution
LogicEngineering
Solver

Field Testing Procedures Manual


The objective of periodic testing is to maintain
the SIL rating of the system while minimizing any
disruption to the process.
Emerson can document a recommended field
testing procedure that complements the
automated partial stroke and SOV component
testing and ensures the integrity of the safety
function throughout its lifetime.
Also, by utilizing proper valve design, the pipeline
can be pig inspected to avoid the disruption and
cost of removing the valve during the
maintenance process.
A comprehensive field test procedure can be
supplied with system to:
· Minimize process disruptions
· Confirm system integrity
IEC61511 / ISA 84 Safety Lifecycle · Maximize system uptime
· Ensure safety integrity levels

SIL
Engineering Smart HIPPS Installation Field Testing Safety
Reduce Reduce Assembly
Reduce Reduce Verification
/ System Product and Procedures
Reduce OPEX Requirement
Reduce OPEX Reduce OPEX
OPEX OPEX andOPEX
Testing OPEX
Commissioning
Compliance
Integration Selection Manual Specification Report

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Solution
LogicEngineering
Solver

Safety Requirement Specification Development


Once the over pressure hazards have been
identified and a risk mitigation factor established,
the SRS becomes the heart of every successful
HIPPS Project.
Emerson’s engineers can complement your
development team and are experienced in the
methods for pre-feed engineering, data
gathering, and SIL analysis.
Our engineers and safety consultants are expert
at the process of developing the important SRS
documents which include.
· Project Description
· Functional SIS Requirements
· HIPPS System Requirements
· Basis of Design

IEC61511 / ISA 84 Safety Lifecycle · SRS Data

SIL
Engineering Smart HIPPS Installation Field Testing Safety
Reduce Reduce Assembly
Reduce Reduce Verification
/ System Product and Procedures
Reduce OPEX Requirement
Reduce OPEX Reduce OPEX
OPEX OPEX andOPEX
Testing OPEX
Commissioning
Compliance
Integration Selection Manual Specification Report

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Solution
LogicEngineering
Solver

SIL Verification
SIL Verification is the process of verifying that the
design of the Safety Instrumented Function (SIF)
meets the targeted SIL Requirement. The object
is to certify 4 basic criteria:
· Operational & Functionality
· Independent of the Control System
· Document Design Requirements
· Meets Target SIL

IEC61511 / ISA 84 Safety Lifecycle

SIL
Engineering Smart HIPPS Installation Field Testing Safety
Reduce Reduce Assembly
Reduce Reduce Verification
/ System Product and Procedures
Reduce OPEX Requirement
Reduce OPEX Reduce OPEX
OPEX OPEX andOPEX
Testing OPEX
Commissioning
Compliance
Integration Selection Manual Specification Report

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Pressure Sensing
Logic SolverLoops

IA/NG Replacing switches with transmitters is your first


Intelligent Software step toward reducing undetected failures.
& Analysis Tools
Emerson’s smart sensors, including Rosemount™
pressure devices, go beyond detecting
IA/NG component failures. They evaluate the
DVC performance of the complete measurement
1-A system, extending diagnostics outside of the
SIS transmitter to provide process diagnostics and:
LS
DVC
· Detect over pressure scenarios
1-B
· Meet Functional Safety Requirements

S
· Improved System Reaction Time
· SIL & Redundancy Requirement
S

PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Rosemount
Reduce OPEX
3051S Pressure
ReduceManifold
OPEX

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Pressure Sensing
Logic SolverLoops

IA/NG Rosemount™ 3051S Pressure Transmitters


Intelligent Software
& Analysis Tools The ability to accurately measure pressure
reliably is a key dynamic in HIPPS applications.
When over pressure occurs, your system must
IA/NG respond immediately in order to initiate the
DVC pressure protection system response in time to
1-A protect your downstream equipment. The 3051S
SIS can detect plugged impulse line via SMART
LS
DVC diagnostic (using HART), allowing DeltaV SIS to
1-B take appropriate action and increasing the
Diagnostic Coverage of the HIPPS.
Pressure, level and flow applications are all
S
covered by Rosemount Pressure Transmitters.
S · Plugged Impulse Line Detection

PT PT PT
· Proven Accuracy, 0.025% of span
ZLS ZLS
101-A 101-B 101-C · Process Intelligence
· Advanced Diagnostics
FC FC
FBV 1-A FBV 1-B
· SIL 3 Capable

Rosemount
Reduce OPEX
3051S Pressure
ReduceManifold
OPEX

Click on the tabs to navigate through this section Rosemount Website


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Pressure Sensing
Logic SolverLoops

IA/NG Emerson Pressure Manifold


Intelligent Software
& Analysis Tools The pressure manifold is an important part of any
high integrity solution, ensuring that the safety
integrity level of the HIPPS is maintained, even
IA/NG when transmitters are isolated for test. To
DVC provide this safety, the manifold must have an
1-A interlock system that ensures only one
SIS transmitter can be isolated at a time. It should
LS
DVC also include a Double Block & Bleed function that
1-B allows the operator to safely shut off pipeline
pressure and isolate for testing.

S
· Provides personnel protection
· 1 central or 3 individual tap configuration
S
· Reduce common cause failures
PT PT PT
ZLS ZLS · Suitable for use in SIL3
101-A 101-B 101-C
· Ensures PT isolation

FC FC
FBV 1-A FBV 1-B

Rosemount
Reduce OPEX
3051S Pressure
ReduceManifold
OPEX

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Logic Solver
Logic Solver

IA/NG In a HIPPS, the logic solver is responsible for


Intelligent Software activation of the appropriate signal outputs
& Analysis Tools
based on preconfigured logic conditions and /or
inputs from pressure sensing devices.
IA/NG Purpose designed safety systems which are SIL 3
DVC certified are typically used as a logic solver and
1-A consists of a Central Processing Unit (CPU) and a
SIS redundant / fault tolerant I/O interface designed
LS
DVC for safety-related applications.
1-B
Shutdown logic should be embedded in the CPU
and automatically initiated based upon well-
defined criteria. HIPPS activation should require
S
no external intervention or acknowledgement.
S

PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Reduce
DeltaVOPEX
SIS

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types Testing

Logic Solver
Logic Solver

IA/NG DeltaV SIS™ CHARMS Safety Logic Solver


Intelligent Software
& Analysis Tools In a Logic Solver is not only there to processes the
logic based shutdown configuration
programmed to memory but must be able to
IA/NG monitor the considerable number of diagnostic
DVC tests that are continuously occurring throughout
1-A the life of the system.
SIS
LS In addition, the DeltaV SIS Safety Logic Solver
DVC
eliminates single point of failures and includes the
1-B
ability for periodic final element and solenoid
testing which can extend time between proof
tests.
S
· Continuous loop diagnostics
S
· Integral partial stroke testing
PT PT PT
ZLS ZLS
· Fast Pulse SOV Testing
101-A 101-B 101-C
· Flexible integration
· SIL3 capable
FC FC
FBV 1-A FBV 1-B

Reduce
DeltaVOPEX
SIS

Click on the tabs to navigate through this section DeltaV SIS Website
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Due to the complexity of HIPPS, compared with


Intelligent Software conventional pressure relief systems, operators
& Analysis Tools
fear losing control during scheduled test. This
often results in tests being incomplete or not
IA/NG carried out at all, impacting the required safety
level of the system. A solution with proof test
DVC
procedures and automated partial stroke testing
1-A
(PST) will ensure this is handled correctly and
SIS
LS extend the integrity of the system between proof
DVC
tests.
1-B
· Ensure system operation and integrity.

S
· Reduce manual test cost and errors,
· Minimizes costly process disruptions
S
· Collects & records diagnostic data
PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Valve Operating
Actuators Controls Valves
System

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Valve Operating System


Intelligent Software
& Analysis Tools Final Elements are split between the Valve and
the Operating System. The valve is designed to
maintain the pressure integrity of the pipeline,
IA/NG whereas the operating system is often energized
DVC by a separate, external power source.
1-A
The VOS consist of an actuator and the control
SIS
LS components, with options for electric, pneumatic
DVC
or hydraulic operation. The controls will be
1-B
connected to the DCS or SIS, depending on the
function and SIL requirement of the VOS.
S · VOS can be pneumatic, hydraulic or
electrically driven
S
· Control the valve from DCS or SIS
PT PT PT
ZLS ZLS
· Position feedback, PST and diagnostics
101-A 101-B 101-C should be included
· Wired or wireless interface to DCS can be
FC FC supplied
FBV 1-A FBV 1-B

Valve Operating
Actuators Controls Valves
System

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Valve Actuators


Intelligent Software
& Analysis Tools Actuators are designed to drive valves, either for
rotary or linear movement. They can be
energized by Pneumatic, Hydraulic or Electrical
IA/NG drives, each depending on the specifics of the
DVC application and the requirements of the control
1-A valve.
SIS
LS · Air Driven Pneumatic actuators are the
DVC
most common type of valve control and
1-B
the actuator mechanism and control
component must have seamless
S
integration to provide reliable actuation

Click to learn more about Pneumatic Actuators


S

PT PT PT
ZLS ZLS
· Hydraulic actuators are often used when
101-A 101-B 101-C fail-safe valve control is critical, as the
non-compressible control fluids allow
precise control during shutdown
FC FC
FBV 1-A FBV 1-B Click to learn more about Hydraulic Actuators

· Electric is only used for on/off, but can be


Valve Operating augmented by an Electro Hydraulic
Actuators Controls Valves Operator to provide a fail-safe operation
System
Click to learn more about Electro Hydraulic Actuators

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Pneumatic Actuators


Intelligent Software
& Analysis Tools Pneumatic actuators utilize compressed air to
operate a valve and are the most commonly used
actuator. The big advantage of pneumatic
IA/NG actuators is that compressed air is easily available
DVC in most sites and they are quick to respond with
1-A shutdown times as low as 1- 2 seconds. This
SIS makes them a perfect fit in many HIPPS
LS
DVC applications. Emerson has a variety of pneumatic
1-B actuators to fit most process applications and
they can be supplied with various certifications
including SIL 3.
S
· Ideal for applications requiring fast
closure speed
S
· Can be either spring return or double
PT PT PT acting
ZLS ZLS
101-A 101-B 101-C
· Piston type scotch-yoke actuators are
most common
FC FC
FBV 1-A FBV 1-B
· Modular design increases the safety,
reliability and product life

Click to learn also about Hydraulic Actuators


Valve Operating
Actuators Controls Valves Click to learn also about Electro Hydraulic Actuators
System

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Hydraulic Actuators


Intelligent Software
& Analysis Tools Hydraulic actuators convert fluid pressure into
motion and most commonly provided with a
scotch-yoke piston style actuator. Hydraulic
IA/NG operated actuators work well in high pressure
DVC situations because they can exert force necessary
1-A to overcome the pressure of the process
SIS liquids. Emerson offers actuators suitable for use
LS
DVC in the demanding applications of a SIL
1-B environment such as HIPPS.
· Excellent for applications where high
S
torque is required
· Ideal for applications requiring accurate
S control and speed

PT PT PT · Fail-safe features close or open under ESD


101-A 101-B 101-C
ZLS ZLS
conditions
· Commonly use scotch-yoke or piston
style actuator
FC FC
FBV 1-A FBV 1-B
Click to learn also about Pneumatic Actuators

Click to learn also about Electro Hydraulic Actuators


Valve Operating
Actuators Controls Valves
System

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Electro Hydraulic Actuators


Intelligent Software
& Analysis Tools The Electro-Hydraulic Operator (EHO) is a self-
contained, quarter-turn, valve actuator designed
for critical shutdown applications where reliability
IA/NG is paramount. The EHO utilizes a dependable
DVC spring-return actuator for the fail-safe stroke
1-A combined with an integral hydraulic power pack
SIS and electronic control module. Emerson’s EHO is
LS
DVC complete and designed for the toughest
1-B conditions where remote ESD with built in
preventative and reactive measures are required.

S
· Self-contained, no hydraulic supply
required
S · Reliable in high pressure applications

PT PT PT · High accuracy and speed


ZLS ZLS
101-A 101-B 101-C · Compliments electric actuation as fail-
safe option
FC FC · Solar powered and ideal for remote
FBV 1-A FBV 1-B locations

Click to learn also about Pneumatic Actuators


Valve Operating
Actuators Controls Valves Click to learn also about Hydraulic Actuators
System

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Controls
Intelligent Software
& Analysis Tools Control of the Final Element is crucial for the
correct fail-safe function in case of an emergency.
The design of the controls can be pneumatic,
IA/NG hydraulic or electric and should be designed to
DVC incorporate the required redundancy.
1-A
The valves operational controls can also be
SIS
LS designed to increase the diagnostic coverage of
DVC
the entire Final element:
1-B
· Digital Valve Controllers (DVC) for
shutdown and partial stroke testing (PST),
S to uncover the dangerous failures in the
Final Element and controls
S
· Single or Redundant Solenoids will
PT PT PT
provide reliable shutdown, but can also
101-A 101-B 101-C
ZLS ZLS
be tested for functionality while in service
· High flow shutdown components can be
integrated in PST to verify functionality
FC FC
FBV 1-A FBV 1-B · Asset Management Software (AMS) is
used to monitor device alerts in the
system and predict failures before they
occur
Valve Operating
Actuators Controls Valves
System

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Specialized Valves for HIPPS


Intelligent Software
& Analysis Tools One of the most critical parts of a HIPPS system is
the valve. The valve must be reliable and ready to
perform when needed and under all operating
IA/NG conditions.
DVC
In order to make the certification process for a
1-A
safety shutdown system, especially a HIPPS
SIS
LS system, easier it is important you select a valve
DVC
supplier that has third party safety evaluations for
1-B
SIL 3. Achieving such a certification validates that
the supplier can demonstrate a history of
producing reliable products that preform when
S
needed.
S Emerson has a full line of valves to solve the most
demanding safety shutdown applications.
PT PT PT
101-A 101-B 101-C
ZLS ZLS · SIL 3 certificated products
· Demonstrated history of
producing safety shutdown systems
FC FC
FBV 1-A FBV 1-B · Valves for most any process application
· Zero leakage capabilities
· Easily automated or supplied as complete
Valve Operating system
Actuators Controls Valves
System
Click to learn about Ball Valves

Click to learn about Triple Offset Valves

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Ball Valves


Intelligent Software
& Analysis Tools A ball valve is an excellent choice for an over
pressure shutdown system. A ball valve is high
reliable, quick to close, piggable, and pressure
IA/NG drops are minimized. Ball valves are available
DVC from 1/2” to over 60” and in pressure classes up
1-A to 4500#. Quality ball valves offer bi directional
SIS sealing with zero leakage. Ball valves can be
LS
DVC easily automated to meet HIPPS requirements.
1-B
· High reliability – can achieve SIL 3
· Zero leakage capable
S
· Wide range of sizes
S · Piggable

PT PT PT · Easily automated
ZLS ZLS
101-A 101-B 101-C

Click to learn also about Triple Offset Valves

FC FC
FBV 1-A FBV 1-B

Valve Operating
Actuators Controls Valves
System

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Final Elements
Logic Solver

IA/NG Triple Offset Valves


Intelligent Software
& Analysis Tools A highly reliable valve is crucial in a safety
shutdown system. A triple offset valve (TOV)
proves to be an excellent choice due to the
IA/NG virtually maintenance-free design and long
DVC service life.
1-A
Unlike butterfly and gate valves whose seats are
SIS
LS chafed with every stroke, the design of the TOV
DVC
provides a non-rubbing, open/close operation.
1-B
Additionally, its torque-assisted seal assures tight
shut-off and uniform contact without wear which
S translates to better performance over a longer
life.
S
· Low maintenance
PT PT PT
ZLS ZLS
· Triple offset minimizes wear
101-A 101-B 101-C
· Zero leakage sealing
· Cost effective automation
FC FC
FBV 1-A FBV 1-B · High reliability – can achieve SIL 3

Click to learn also about Ball Valves


Valve Operating
Actuators Controls Valves
System

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

On-Line System
Logic Testing
Solver

IA/NG Due to the complexity of HIPPS compared with


Intelligent Software conventional pressure relief systems, operators
& Analysis Tools
fear losing control during scheduled test. This
can result in tests being postponed or not carried
IA/NG out at all, potentially impacting system safety
integrity.
DVC
1-A A solution with detailed proof test procedures
SIS and automated SOV / PST testing will ensure this
LS
DVC is handled correctly and confidently.
1-B
· Ensure system operation and integrity
· Reduce manual test cost and errors
S
· Minimize costly process disruptions
S · Collects and records diagnostic data

PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Pressure
ReduceSensor
OPEX Test Logic
Reduce
Solver
OPEX
Test SOV
Reduce
Pulse
OPEX
Test Partial
Reduce Stroke
OPEX
Test

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

On-Line System
Logic Testing
Solver

IA/NG Redundant Pressure Transmitters


Intelligent Software
& Analysis Tools The HIPPS System integrity depends on the
accuracy and reliability of the pressure
transmitters to initiate the shutdown sequence.
IA/NG
The 3051S Pressure Transmitter runs continuous
DVC
diagnostic checks to ensure that the certified SIL
1-A
3 capable integrity is maintained.
SIS
LS In addition, the DeltaV SIS complements the
DVC
1-B HART enabled pressure transmitter and provides
deviation monitoring and safety loop testing;
from sensor, to logic solver.
S
· Continuous HART diagnostics
S · Built in transmitter test

PT PT PT
· Integral loop test verifies loop wiring and
101-A 101-B 101-C
ZLS ZLS
transmitter output
· Can detect plugged impulse line

FC FC
FBV 1-A FBV 1-B

Pressure
ReduceSensor
OPEX Test Logic
Reduce
Solver
OPEX
Test SOV
Reduce
Pulse
OPEX
Test Partial
Reduce Stroke
OPEX
Test

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

On-Line System
Logic Testing
Solver

IA/NG Safety Logic Solver Test


Intelligent Software
& Analysis Tools The DeltaV SIS CHARMS Safety Logic Solvers
eliminate the single point of failure and
continuously monitors system diagnostics and
IA/NG tests the health of each SIS loop.
DVC
The DeltaV SIS provides integrated monitoring
1-A
for the complete safety loop; from sensor, to
SIS
LS logic solver, to final control element and provides
DVC
test notifications so your SIS integrity remains
1-B
stable for a longer period of time.
· Automatic proof test notifications
S
· 61508 and 61511 compliant
S · Constant loop health diagnostics

PT PT PT · Maintains SIS integrity


ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Pressure
ReduceSensor
OPEX Test Logic
Reduce
Solver
OPEX
Test SOV
Reduce
Pulse
OPEX
Test Partial
Reduce Stroke
OPEX
Test

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

On-Line System
Logic Testing
Solver

IA/NG Solenoid Operated Valve Testing


Intelligent Software
& Analysis Tools It is critical to ensure the entire final element is
available during a safety demand, even when
proof test intervals are extended with the help of
IA/NG online partial stroke tests. Including the solenoid
DVC operated valve (SOV) in online testing can help
1-A diagnose dangerous failure modes between proof
SIS tests.
LS
DVC
The Fisher FIELDVUE DVC6200 SIS digital valve
1-B
controller can be used to monitor the health of an
external SOV:
S · Logic Solver briefly pulses the SOV

S
· DVC monitors SOV to detect pressure
drop across SOV
PT PT PT
ZLS ZLS
· Pulse speed ensures the final control
101-A 101-B 101-C element does not move
· Utilizes on-board pressure sensors to
FC FC record the pressure drop across the SOV
FBV 1-A FBV 1-B
· Applies time/date stamp to support
recordkeeping requirements

Pressure
ReduceSensor
OPEX Test Logic
Reduce
Solver
OPEX
Test SOV
Reduce
Pulse
OPEX
Test Partial
Reduce Stroke
OPEX
Test

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

On-Line System
Logic Testing
Solver

IA/NG Partial Stroke Testing


Intelligent Software
& Analysis Tools HIPPS requires partial stroke testing to safely
extend the time between proof test intervals.

IA/NG The results are improved system performance


and valve diagnostic capability. Many customers
DVC
also appreciate the reduction in testing time and
1-A
initial investment cost while minimizing spurious
SIS
LS trips.
DVC
1-B · SIL 3 capable safety shutdown
· Automated Valve PST
S · Spurious trip avoidance
· Integral position transmitter
S

PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Pressure
ReduceSensor
OPEX Test Logic
Reduce
Solver
OPEX
Test SOV
Reduce
Pulse
OPEX
Test Partial
Reduce Stroke
OPEX
Test

Click on the tabs to navigate through this section Emerson Expert Website Article
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG Emerson has a complete portfolio of high


Intelligent Software integrity components that can be used in the
& Analysis Tools
design of a HIPPS system.
All of our products are rated best in class and
IA/NG include embedded diagnostics that help to
DVC minimize systematic failures and ensure
1-A compliance with functional standards throughout
SIS the system lifecycle.
LS
DVC
Rosemount™ Pressure Transmitters
1-B
Bettis™ Actuators
Fisher™ / Virgo™ Valves
S
Fisher FIELDVUE® Digital Valve Controllers
S ASCO® Solenoid Valves
PT PT PT
Topworks™ D-ESD Switchbox
ZLS ZLS
101-A 101-B 101-C DeltaV SIS™ CHARMs Safety Logic Solver
AMS Suite: Intelligent Device Manager
FC FC AMS ValveLink™ Snap-on™ Software
FBV 1-A FBV 1-B
Fisher Regulator Technologies

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG Rosemount™ 3051S Pressure Transmitters


Intelligent Software
& Analysis Tools The ability to accurately measure pressure
reliably is a key dynamic in HIPPS applications.
When over pressure occurs, your system must
IA/NG respond immediately in order to initiate the
DVC pressure protection system response in time to
1-A protect your downstream equipment. The 3051S
SIS can detect plugged impulse line via SMART
LS
DVC diagnostic (using HART), allowing DeltaV SIS to
1-B take appropriate action and increasing the
Diagnostic Coverage of the HIPPS.
Pressure, level and flow applications are all
S
covered by Rosemount Pressure Transmitters.
S · Plugged Impulse Line Detection

PT PT PT
· Proven Accuracy, 0.025% of span
ZLS ZLS
101-A 101-B 101-C · Process Intelligence
· Advanced Diagnostics
FC FC
FBV 1-A FBV 1-B
· SIL 3 Capable

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section Rosemount Website


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG Bettis Actuators


Intelligent Software
& Analysis Tools Long-term reliability and speed of operation are
both important aspects of HIPPS. Bettis actuators
are fully capable of meeting the fast closing
IA/NG speeds required in liquid and gas applications. In
DVC addition to its compatibility with a wide range of
1-A devices for any application, Bettis Actuators are
SIS proven to operate in the harshest conditions for
LS
DVC many years, with maximum reliability.
1-B
· Design reduces inventory costs
· PED 97/23/EC compliant
S
· Water ingress and corrosion protection
S · Field serviceable configuration

PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section Bettis Actuators Website
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG Fisher / Virgo Valves


Intelligent Software
& Analysis Tools Virgo ball valves and triple offset valves are
designed using the latest engineering tools
including Pro-E, Computational Fluid Dynamics
IA/NG (CFD), and Finite Element Analysis (FEA) to ensure
DVC our products are safe, reliable and perform as
1-A specified.
SIS
LS Our design and manufacturing is validated with
DVC
an industry leading in-house test facility. Not only
1-B
do we ensure Virgo products are made according
to exceptional quality standards, our facility can
certify that our products are compliant to the
S
latest standards and regulations.
S

PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section Fisher Valves Website Virgo Valves Website
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG Fisher FIELDVUE Digital Valve Controllers


Intelligent Software
& Analysis Tools Using Fisher FIELDVUE DVC6200 SIS digital valve
controller you can safely extend the time
between final element proof tests by using partial
IA/NG stroke testing (PST). By accessing built-in
DVC diagnostic capabilities, operators can identify
1-A stuck valves, pressure droop, friction changes and
SIS
other common valve issues without taking the
LS valve and your process offline. With vital
DVC
diagnostics, facilities can be confident that the
1-B
final control element will perform when needed.
· Safety function priority
S
· SIL 3 capable shutdown
S · Spurious trip avoidance
PT PT PT · Robust linkage-less design
ZLS ZLS
101-A 101-B 101-C
· Easily verify and record final element
performance
FC FC · Integral SIL 2 capable position transmitter
FBV 1-A FBV 1-B reduces valve hardware needs

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section FIELDVUE DVC Website
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG ASCO Solenoid Valves


Intelligent Software
& Analysis Tools Solenoid valves operating in remote locations for
HIPPS applications require reliable low-power
operation and the ability to endure voltage
IA/NG surges.
DVC
ASCO solenoid valves can deliver higher
1-A
performance ratings for less power. This means
SIS
LS less maintenance and power consumption for
DVC
remote applications and increased reliability all-
1-B
around.
· Low power capabilities
S
· Optimized flow for greater throughput
S · Redundant solenoid assembly solutions

PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section ASCO Valves Website
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG TopWorx D-ESD Switchbox


Intelligent Software
& Analysis Tools SIL-3 Capable Emergency Shutdown (ESD) Valve
Controller that provides a complete partial stroke
test (PST) solution with unique features and
IA/NG functionality that enables local partial stroke
DVC testing of final control element without
1-A disrupting or shutting down the process, a fully
SIS integrated solution with all controls in a single
LS
DVC housing.
1-B
· Local PST capability
· Pass/Fail indication
S
· Feedback to logic solver
S · Diagnostics

PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section TopWorx Website


Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG DeltaV SIS CHARMS Safety Logic Solver


Intelligent Software
& Analysis Tools Traditional process safety systems for HIPPS
functions were designed for large central systems
with large I/O counts. If the central unit failed, all
IA/NG the safety loops fail, and caused a huge focus on
DVC the logic solver.
1-A
The DeltaV SIS CHARMS Safety Logic Solvers
SIS
LS eliminate the single point of failure and
DVC
continuously monitors and tests health of all SIS
1-B
loops. In addition, DeltaV SIS is an integral part of
final element testing which can extend time
between proof tests.
S
· Comprehensive diagnostics
S
· Reduced engineering
PT PT PT
ZLS ZLS
· Streamlined proof tests
101-A 101-B 101-C
· Simplified compliance
· Flexible integration
FC FC
FBV 1-A FBV 1-B · SIL3 capable

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section DeltaV SIS Website
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG AMS Suite: Intelligent Device Manager


Intelligent Software
& Analysis Tools AMS Device Manager delivers the HIPPS system
with the ability to perform on line tests that helps
to avoid unplanned shutdowns and avoids a
IA/NG reduction of system integrity over time.
DVC
It gives your maintenance and operations
1-A
personnel the ability to work smarter. Based on
SIS
LS real-time condition data from your intelligent
DVC
field devices, AMS can give your plant staff the
1-B
diagnostic alerts they need to respond quickly
and make informed decisions on whether to
maintain or replace field devices.
S
· Real-time analytics and reporting
S
· Safety asset performance protection
PT PT PT
ZLS ZLS
· Supports online testing
101-A 101-B 101-C
· Identifies bad actors before shutdown
· Predictive intelligence improves reliability
FC FC
FBV 1-A FBV 1-B

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section AMS Suite Website
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG AMS ValveLink Snap-on Software


Intelligent Software
& Analysis Tools ValveLink Software is used for easy setup,
calibration, configuration, and diagnostics with
Fisher FIELDVUE DVC digital valve controllers and
IA/NG provides real-time notifications of current and
DVC potential instrument problems when used with
1-A the Performance Diagnostics.
SIS
LS Advanced diagnostics allow for insight of valve
DVC
performance, or degradation that would
1-B
otherwise go unseen. It can be used as an
excellent preventative maintenance tool and
provides insight into your valves.
S
· Complete valve diagnostics
S
· Initial valve and rebuild baselines
PT PT PT
ZLS ZLS
· Actionable alerts
101-A 101-B 101-C
· Partial / full stroke SIS testing
· Valve health monitoring
FC FC
FBV 1-A FBV 1-B

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section AMS Valve Link Website
Interactive Solutions Tool
High-Integrity Pressure Protection Systems (HIPPS)

Overpressure
Overpressure On-Line
HIPPS
HIPSS System System Solution Pressure Performance
Featured
Protection
Protection Logic Solver Final Elements System
Description Justification
Challenges Engineering Sensing Loops Validation
Products
System Types
System Types Testing

Featured Products
Logic Solver

IA/NG Fisher Regulator Technologies


Intelligent Software
& Analysis Tools Pneumatic actuators in HIPPS applications require
a high quality, precision supply of air or gas for
consistent, reliable operation.
IA/NG
Fisher filter regulators are engineered to remove
DVC
debris and to eliminate supply gas leakage. The
1-A
integrated filtration system optimizes the quality
SIS
LS of supply gas to increase HIPPS system reliability.
DVC
1-B · Sour Gas Service Capability
· Easy Maintenance
S · Rugged Compact Design

S
· No Air Loss
· Smart Bleed
PT PT PT
ZLS ZLS
101-A 101-B 101-C

FC FC
FBV 1-A FBV 1-B

Rosemount Fisher /
Bettis ASCO AMS Fisher
Pressure Virgo Fisher DVC Topworx DeltaV SIS AMS Suite
Actuators Solenoids ValveLink Regulators
Transmitters Valves

Click on the tabs to navigate through this section Filter Regulators Website