Fault Current Calculator

This document provides calculations to coordinate the settings of protective relays on a feeder line. It lists inputs like the feeder load current, fault current ranges, and relay characteristics. The outputs include the pick-up current settings for the low current and high current elements of the relay, as well as time delay settings to ensure proper grading between the relay and upstream protective device.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
75 views

Fault Current Calculator

This document provides calculations to coordinate the settings of protective relays on a feeder line. It lists inputs like the feeder load current, fault current ranges, and relay characteristics. The outputs include the pick-up current settings for the low current and high current elements of the relay, as well as time delay settings to ensure proper grading between the relay and upstream protective device.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Relay Coordination - PSM and TMS calculator

Inputs
1 Feeder Load Current 35 Amps

2 CT installed on feeder - Primary 60 Amps

3 CT secondary current 1 Amps

4 Minimum fault current 8000 Amps

5 Maximum fault current 12000 Amps

6 Relay error 0.075

7 CT error 0.1

8 CT over shoot 0.05

9 CT interrupting time 0.17

10 Safety factor 0.33

Low Current setting - I >


1 Times current setting 0.58

2 Over Load Current 34.8 Amps

3 Over load current setting 0.58

4  Plug setting of Relay (PMS) 0.58

5  Plug setting multiplier ( PSM) 229.89


1.114885
6 Operating time of Relay for Normal Inverse 1.22

7 Time delay of relay(TMS) 0.10 Sec

8 Actual operating Time of Relay (t>) 0.12 Sec

9 Grading time of Relay 0.55 Sec 0.025

10 Operating time of upstream relay 0.70 Sec

High Current setting - I>>

1  Plug setting of Relay 1.4


Pick up setting of over current relay 1.4

Plug setting multiplier ( PSM) 95.24

2 Time Delay (TMS)  0.1

3 Curve is selected NI

Operating time for normal inverse curve 1.47 1.095409

Actual operating time of delay 0.15 Sec

Grading time of relay 0.575

Operating time of upstream relay 0.72 Sec


Conditions

1 PMS (I >) 0.58 Must be greater than equal to 0.8

2 0.125< 133.3333

0.114885

0.575
0.095409