Department of Electrical Engineering EE351: Electrical Machines - Lab Manual
Department of Electrical Engineering EE351: Electrical Machines - Lab Manual
Signature: __________________________________
Introduction
In this lab students will be study the three phase transformer system. The three phase
electric power is a common method of alternating current, electric power generation,
transmission and distribution. It is a type of polyphaser system and is the most common
method used by electrical grids worldwide to transfer power. It is also used to power large
motors and other heavy loads.
A three-wire three-phase circuit is usually more economical than an equivalent two-wire
single phase circuit at the same line to ground voltage because it uses less conductor
material to transmit a given amount of electrical power.
Objective
1. To learn how to appropriately model three-phase transformers and transformer banks.
2. To understand phase relationship in Y- connection.
3. To understand and master the connection of three phase transformer banks.
Before a three-phase transformer is put into service, the phase relationships must be
verified. For a wye configuration, the line voltages at the secondary windings must all
be /3 times greater than the corresponding phase voltages. If not, winding connections
must be reversed. To verify that phase relationships are correct for a wye configuration,
the voltage between two windings (EAB) is measured as shown in Figure 4-3(a) to
confirm that it is /3 times greater than the line-to-neutral voltage across either winding
(for example EAN). The voltages between the third winding and the others (EBC and
ECA) are then measured to confirm that they are also /3 times greater than the phase
voltage (EAN), as shown in Figure 4-3(b).
For a delta configuration, the line voltages at the secondary windings must all be equal.
If not, winding connections must be reversed. To verify that phase relationships are
correct for a delta configuration, the voltage across two series connected windings
(ECA) is measured as shown in Figure 4-4(a) to confirm that it equals the voltage across
either winding (EAB and EBC). The third winding is then connected in series, and the
voltage across the series combination of the three windings is measured to confirm that
it is zero before the delta is closed, as shown in Figure 4-4(b). This is extremely
important for a delta configuration, because a very high short-circuit current will flow
if the voltage within the delta is not equal to zero when it is closed.
Figure 4-4: Delta voltage equals to zero [1]
Procedure
1. Connect the Three-Phase Transformer module in the delta (source)-Wye (load)
configuration shown in Figure 4-5. [2 marks]
Figure 4-5: Delta configuration source with Wye resistive load [1]
2. Use meter input to measure the voltages and record the results. After recording the
measurements.
[6 marks]
𝐸1−2=___400V___ 𝐸1−6=___0V___ 𝐸1−3=___400V___
𝐸3−5 =___400V___ 𝐸3−4 =___400V___ 𝐸3−6 =___400V___
3. Is the sum of the three line voltages indicated by the meter 𝐸𝑅1 +𝐸𝑅2 + 𝐸𝑅3
approximately equal to zero? [2 marks]
a. Yes √b. No
4. Measure the currents, voltage and power in each phase on the secondary side of the
transformer? [10 marks]
7. Is the sum of the three phase voltages indicated by the meter 𝐸𝑅1 +𝐸𝑅2 + 𝐸𝑅3
approximately equal to zero? [2 marks]
a. Yes b. No
8. Measure the currents, voltage and power in each phase on the secondary side of the
transformer? [2 marks]
9. Repeat all the steps from point 1 to point 8 in the LVVL simulation software and
attached screen shots of all the tasks you perform in the LVVL software.
10. Connect the Three-Phase Transformer module in the delta (source)-Wye (load) and
paste its screen shot here. [2 marks]
11. Use meter input to measure the voltages and record the results. After recording the
measurements.
[6 marks]
𝐸1−2=___228.9____ 𝐸1−6=___0____ 𝐸1−3=___228.9____
𝐸3−5 =___396.9____ 𝐸3−4 =____396.9____ 𝐸3−6 =___229.0____
12. Is the sum of the three line voltages indicated by the meter 𝐸𝑅1 +𝐸𝑅2 + 𝐸𝑅3
approximately equal to zero? [2 marks]
a. Yes b. No
13. Measure the currents, voltage and power in each phase on the secondary side of the
transformer? [10 marks]
14. Connect the Three-Phase Transformer module in the wye-wye configuration and paste
here screen shot. [2 marks]
𝑬𝑺 (V) 𝑹𝟏 (Ω) 𝑹𝟐 (Ω) 𝑹𝟑 (Ω)
15. Use meter input to measure the voltages and record the results. After recording the
measurements.
[6 marks]
𝐸1−2=___230_____ 𝐸1−6=____230____ 𝐸1−3=____398.3____
𝐸3−5 =___398.2_____ 𝐸3−4 =____230____ 𝐸3−6 =___229.9_____
16. Is the sum of the three line voltages indicated by the meter 𝐸𝑅1 +𝐸𝑅2 + 𝐸𝑅3
approximately equal to zero? [2 marks]
a. Yes b. No
17. Measure the currents, voltage and power in each phase on the secondary side of the
transformer? [10 marks]