Equipment Used To Implement Automatic Transfer System (ATS) - EEP
Equipment Used To Implement Automatic Transfer System (ATS) - EEP
Equipment Used To Implement Automatic Transfer System - ATS (on photo: Robotic Parking Systems Generator
Transfer Switch; credit: parkithere.wordpress.com)
The following is a list of commonly encountered variations regarding the automatic transfer system
equipment //
1. Switchboard or Switchgear?
2. Logic Platform (PLC)
3. Circuit Breaker Control and Interlocking
4. User Interface
i. Discrete Controls (switches, indication lights)
ii. Touch screen
1. Switchboard or Switchgear?
The power equipment used to facilitate the transfer, for low voltage systems, is commonly either a UL 891
switchboard or ANSI C37.20.1 low voltage power switchgear. Which is used is dependent upon the system design
and where in the over-all power system the equipment is located, however the following general guidelines apply:
For automatic transfer “higher” in the system (closer to the service), ANSI low voltage switchgear is generally
preferred due to is compartmentalization and the use of drawout low voltage power circuit breakers, which have
short-time withstand capabilities.
An alternative is a “hybrid” UL 891 switchboard which uses drawout insulated-case circuit breakers with
characteristics similar to low voltage power circuit breakers, but with less compartmentalization.
For automatic transfer “lower” in the system (farther from the service), a UL 891 switchboard may suffice. However,
drawout circuit breakers should be considered even if a UL 891 switchboard is used.
The automatic transfer logic may be supplied by either discrete control relays or a programmable logic controller
(PLC), as shown in Figure 1.
In times past, this was generally a choice of flexibility (the PLC) vs. robustness (discrete relays). In recent years,
however, PLC’s have undergone significant improvements in reliability and robustness, to the point that they are now
the preferred method for implementing automatic transfer scheme logic.
The flexibility given by the use of PLC’s lies in the fact that the automatic transfer logic is coded into
software, rather than hard-wired. This makes some on-the-fly changes, if required, possible without
hardware or wiring modifications to the equipment. It also allows more complex decision making logic to be
implemented without excessive wiring.
Discrete control relays, on the other hand, must be re-wired to make changes to the automatic transfer logic, and
more complex logic generally requires more control relays and wiring.
Another advantage of a PLC is its ability to communicate digitally with
external devices. This makes more sophisticated user interfaces possible, as will
be discussed below. It also allows remote access to the transfer system if
required.
Interlocking is the restriction of operation of devices, usually for safety reasons. For an automatic transfer system, the
most common interlocking required is interlocking to prevent out-of synchronism paralleling of power sources (or
prevention of paralleling at all in many cases).
When the automatic transfer system logic is provided by a PLC, this interlocking
may be implemented in a hard-wired fashion, that is, outside of the PLC or as
part of the PLC program.
Automatic Transfer Switch Panel (photo credit: petersonpower.com)
In general, use of hard-wired interlocking is preferred, to allow an extra measure of safety should the PLC
fail. Similarly, manual control for automatically operated circuit breakers may be implemented in a hard-wired fashion
or via the PLC. It is generally recommended that at least the circuit breaker tripping function be implemented outside
the PLC.
Manual control for automatically-operated circuit breakers is generally implemented via an external control switches,
with the manual close control (and often trip control) on the circuit breaker access-restricted via a cover to force use
of these control switches.
4. User Interface
This is the most customizable part of the automatic transfer system equipment. In general, two options are available:
1. Discrete controls or
2. Touch screen
Discrete controls take the form of control switches and pilot lights mounted on the equipment. An example of this
is given in Figure 2:
Figure 2 – User Interface – Discrete Controls
In Figure 2, “AUTO”, “MANUAL”, and “AUTO FAIL” pilot lights indicate the three modes of operation described in
earlier published article.
A keyed auto/manual mode selector gives control of the operating mode, a keyed automatic retransfer on/off switch
provides a means to enable or disable automatic retransfer, and a keyed preferred source selector allows either
power source to be considered as the normal source.
The use of keyed switches should be carefully evaluated to insure that the end-user achieves the maximum
benefit from such an arrangement.
In addition to the controls shown in Figure 2, the following are also commonly available:
Like discrete relay control logic, discrete controls must be planned to the last detail early in the specification process
and provide limited flexibility for change.
Touch screen
When a PLC is used for the automatic transfer logic, a touch screen is an option for the user interface. A touch
screen can provide a wealth of detail regarding the automatic transfer system status, and adjustability in several
areas which aren’t typically available with discrete controls.
1. An active mimic single line diagram which changes color to denote energization of system components
2. Source available indicators
3. Breaker status indicators,
4. A transfer system status summary
5. The ability to change numerical settings such source failure, dead bus, and source restore timers
6. Quick manual transfer of the system from one source to the other in manual mode
7. An event log which captures automatic transfer events for diagnostic purposes.
Such sophisticated control is simply not feasible with discrete controls, but is easily achieved with a
touch screen.
Touch screen control interfaces for automatic transfer systems do usually include at least one discrete switch and
indicators, namely the auto/manual mode selector and its associated indicators.
The use of multiple user interfaces is possible. Such an arrangement may be desirable due to the need for remote
control of the system. In planning such an arrangement, careful consideration should be given to the number of
interfaces and which interface overrides if control is attempted by more than one interface at a time.
Reference // Critical-Power Automatic Transfer Systems – Design and Application Bill Brown, P.E., Jay Guditis,
Square D Critical Power Competency Center
About Author
Edvard Csanyi
Edvard - Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears
and LV high power busbar trunking (<6300A) in power substations, commercial buildings and industry fascilities.
Professional in AutoCAD programming. Present on Google+