1 System Configuration....................................................................................................... 3
2 External Devices Selection .............................................................................................. 6
3 Communication Settings .................................................................................................. 7
4 Setup Items .................................................................................................................... 18
5 Supported Devices......................................................................................................... 24
6 Device Code and Address Code.................................................................................... 28
7 Error Messages.............................................................................................................. 29
1
MODBUS TCP Master Driver
Introduction
This manual describes how to connect the Display and the External Device (target PLC).
In this manual, the connection procedure is described in the sections identified below:
1 System Configuration
) "1 System Configuration" (page 3)
This section lists the types of External
Devices and SIO that you can connect.
3 Communication Settings
) "3 Communication Settings" (page 7)
This section shows setting examples for
communicating between the Display and
the External Device.
4 Setup Items
) "4 Setup Items" (page 18)
This section describes communication
setup items on the Display.
Set the Display's communication settings
in GP Pro-EX or in offline mode.
Operation
1 System Configuration
Setting
Driver CPU Link I/F SIO Type
Example
Setting
140 CPU 651 50
------ Example 4
140 CPU 651 60
(page 13)
Connection Configuration
• 1:1 Connection
• 1:n Connection
External
Device
• n:1 Connection(PremiumSeries)
*1 *2
Maximum 4 units
HUB
*1 You can connect max 1 unit of TSXP571**/TSXP572**, max 3 units of TSXP573**, max 4 units of
TSXP574**.
*2 Number of connecting units is the unit number when connecting the Display only. Number of connecting
Display will be limited by the number of other External Devices which is connected by Ethernet.
HUB
*1 Number of connecting units is the unit number when connecting the Display only. Number of connecting
Display will be limited by the number of other External Devices which is connected by Ethernet.
Setting
Driver CPU Link I/F SIO Type
Example
Setting
Network interface on
FCN NFCP100-S00 Example 5
CPU
Ethernet (page 15)
Connection Configuration
• 1:1 Connection
• 1:n Connection
External
Device
• n:1 Connection
*1
Maximum 4 units
HUB
*1 Number of connecting units is the unit number when connecting the Display only. Number of connecting
Display will be limited by the number of other External Devices which is connected by Ethernet.
3 Communication Settings
This section provides examples of communication settings recommended by Pro-face for the Display and the
External Device.
When you use the External Device, use GP-Pro EX and the ladder software to set as below.
Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Set IP address on the External Device for IP address in Device-specific settings.
• You need to set the IP address of the Display in its offline mode.
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Please refer to the manual of the ladder software for details on other settings.
Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.
[Equipment Configuration]Tab [Max Query] tab
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Set the IP address of the External Device under [Individual Device Settings].
• You need to set the IP address of the Display in its offline mode.
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Please refer to the manual of the ladder software for details on other settings.
Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Set the IP address of the External Device under [Individual Device Settings].
• You need to set the IP address of the Display in its offline mode.
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Please refer to the manual of the ladder software for details on other settings.
Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Set the IP address of the External Device under [Individual Device Settings].
• You need to set the IP address of the Display in its offline mode.
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Please refer to the manual of the ladder software for details on other settings.
Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Set the IP address of the External Device under [Individual Device Settings].
• You need to set the IP address of the Display in its offline mode.
SD_CMDBSE_BS_OPEN
SD_CMDBSE_BS_OPEN
TRUE REQ VALID TCP_VALID
UNIT#5 TIMEOUT ERROR TCP_ERROR
Notes
• Check with the network administrator about the IP address. Do not duplicate IP addresses.
• Please refer to the manual of the ladder software for details on other settings.
4 Setup Items
Set up the Display's communication settings in GP Pro-EX or in the Display's offline mode.
The setting of each parameter must match that of the External Device.
)"3 Communication Settings" (page 7)
• You need to set the IP address of the Display in its offline mode.
Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.
[Equipment Configuration]Tab
IP Address
• Check with the network administrator about the IP address. Do not duplicate IP
addresses.
Port No. Use an integer from "1 to 65535" to enter the port No. of the External Device.
Unit ID Use an integer from 1 to 247 to enter the unit ID of the External Device.
Bit manipulation (set/
reset) to Holding Register Select how other bits in the same word are handled when you manipulate bits in the holding
Other bits in this register, from "Clear" or "Do not clear".
word
Check this item when you use the IEC61131 grammar for variables.
IEC61131 Syntax
If you check this item, select the address mode from [0-based] or [1-based].
Select the order of checking double word data from "Low word first" or "High word
Double Word word order
first".
Low Security Level Check this option to decrease the format check level.
Read
• If you check [Single Bit Manipulation in Coil/Discrete Input], set the max query using
1 to 2000.
Coil Set the number of max data for device [coil] that can be written for one communication,
Write using 1 to 800 bits.
Discrete Input Set the number of max data for device [discrete input] that can be read for one
communication, using 16 to 2000 bits.
Read
• If you check [Single Bit Manipulation in Coil/Discrete Input], set the max query using
1 to 2000.
Input Register Set the number of max data for device [input register] that can be read for one
Read communication, using 1 to 125 words.
Holding Register Set the number of max data for device [holding register] that can be read for one
Read communication, using 1 to 125 words.
Holding Register Set the number of max data for device [holding register] that can be written for one
Write communication, using 1 to 100 words.
• The number of the setup items to be displayed for 1 page in the offline mode depends on the
Display in use. Please refer to the Reference manual for details.
Communication Settings
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Equipment Settings] in offline mode.
Touch the External Device you want to set from the list that appears.
Device Setting
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Equipment Settings]. Touch the
External Device you want to set from the displayed list, and touch [Device].
(1/2)
IP Address
• Check with the network administrator about the IP address. Do not duplicate IP
addresses.
Port No. Use an integer from "1 to 65535" to enter the port No. of the External Device.
Unit ID Use an integer from 1 to 247 to enter the unit ID of the External Device.
Indicates how other bits in the same word are handled when you manipulate bits in the
Bit manipulation to HR holding register, by "Rest of bits in word are cleared" or "Rest of bits in word are not
cleared".(Not available to set in offline mode.)
Indicates the usage status of the currently set IEC61131 syntax by ON/OFF. (Not available
IEC61131 Syntax
to set in offline mode.)
Double Word word Indicates the currently set order of storing double word data displaying "Low word first"
order or "High word first". (Not available to set in offline mode.)
Indicates whether the format check level is decreased by ON/OFF. If decreased, ON is
Low Security Level
displayed. (Not available to set in offline mode.)
(2/2)
5 Supported Devices
The following table shows the range of supported device addresses. Please note that the actual supported range of
the devices varies depending on the External Device to be used. Please check the actual range in the manual of
your External Device.
Premium/Quantum Series
: This address can be specified as system data area.
32
Device Bit Address Word address Remarks
bits
or
Input Register ------ 300001 - 365536
*2
*1
400001,0 -
Holding Register 400001 - 465536
465536,15*3
*1 You can set the data storing order in word unit of 32-bit data in the Device Setting dialog box.
*2 Write disabled.
*3 An access method at the time of Bit Set varies depending on the [Rest of the bits in this word] setting of
[Device Setting].
- Clear.............................
- Do not clear .................400001,00 - 465536,15
FCN/FCJ Series
: This address can be specified as system data area.
32
Device Bit Address Word address Remarks
bits
300001.00 - or *3
Input Register 300001 - 309999
309999.15
400001.00 -
Holding Register 400001 - 409999 *1
409999.15 *4
*1 You can set the data storing order in word unit of 32-bit data in the Device Setting dialog box.
*2 The device access range of the External Device is specified as 1 to 9999, that of the Display, however, as up
to 9984, since the Display device is accessible in 16-bit units.
*3 Write disabled.
*4 An access method at the time of Bit Set varies depending on the [Rest of the bits in this word] setting of
[Device Setting].
- Clear.............................
- Do not clear .................400001,00 - 409999,15
• FC15/FC16 are used for writing. FC05/FC06 are used for the External Devices that do not support
the function codes mentioned on the left.
• The addresses 100000 and 300000 cannot be accessed using IEC61131 syntax.
• If you apply IEC61131 syntax to a project that has a discrete input or input register already set, the
addresses become "-Undefined-".
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Use device code and address code when you set "Device Type & Address" for the address type of the data display
or other devices.
Premium/Quantum Series
Device Code
Device Device Name Address Code
(HEX)
FCN/FCJ Series
Device Code
Device Device Name Address Code
(HEX)
7 Error Messages
Error messages are displayed on the screen of the Display as follows: "No. : Device Name: Error Message(Error
Occurrence Area)". Each description is shown below.
Item Description
No. Error No.
Name of the External Device where an error has occurred. Device/PLC name is the title of
Device Name
the External Device set with GP-Pro EX.(Initial value [PLC1])
Error Message Displays messages related to an error that has occurred.
Displays the IP address or device address of the External Device where an error has
occurred, or error codes received from the External Device.
• Refer to your External Device manual for details on received error codes.
• Refer to "Display-related errors" in "Maintenance/Troubleshooting Guide" for details on the error
messages common to the driver.