Relay Setting Calculation For 0.415 KV Panel-Ecr-1 Variables-OC Settings - PCC-11
Relay Setting Calculation For 0.415 KV Panel-Ecr-1 Variables-OC Settings - PCC-11
PCC-11
Incomer 415 5000 1 SI 2 0.05 SI 0.6 0.5 SI 3.6 0.02
Incomer
1 System Data:
System Voltage 0.415 KV BC BC 415 5000 1 SI 1.8 0.04 SI 0.4 0.4 SI 3.6 0.02
Selected CT ratio 5000 /1A
Max. Load Current 3953 A
Rated Voltage 0.433 KV 1000
Sym. SC Cuurrent during 3
( Minimum Fault Lavel as per ETAP)
ph fault 63.34 KA
25% Fault level choosen to
reduce stress of the 15.835 KA ( Fault Current Set 25 % for BC)
100
system
15835 A
Max. Load Current 3953 A
Time In Sec.
CT ratio
Incomer
= 0.87
POC ( Pick of Current) = CTR * PS BC
= 4348.3 A
Proposed PSM = Fault current 1
POC
3.6
Proposed Time Setting:
0.1
Considering, NI curve as Per IEC 60255 -4 - Standard Inverse
ROT ( Relay Operating time) = 0.14
(PSM)^0.02 -1
= 5.3 s
Minimum Operating time of Breaker 20 ms 0.01
Grading Margine for next upstream breaker 100 ms 0.1 1 10 100 1000 10000 100000
Hence, Total Delay Operating time delay (DOTR) 0.12 S Fault MVA
TMS = DOTR
ROT
= 0.02
2 Setting Calculation for Instantanious OC (50)>>
Over
CTR Current Setting-1 Current Current Setting-3
Feeder Name Rated Volt.
Setting-2
Phase fault 50 Pick up secondary = 0.4 A Pri Sec. Curve PSM TMS(k) Curve PSM TMS(k) Curve PSM TMS(k)
PCC-11
Incomer 415 5000 1 SI 0.2 0.5 SI 5.60 0.03
Incomer
Pick up setting in the Relay = 0.4 x ln BC BC 415 5000 1 SI 0.15 0.4 SI 5.60 0.03
Time In Sec.
BC
Earth Fault setting of 75% of CT primary Current
= 3750
Considered
1
Earth Fault Pick up Secondary = 0.75 A
TMS = DOTR
ROT
= 0.03
B PCC-11 5000A ACB ( Incomer)
( Fault Current as per ETAP Report)
Relay Details: ABB MAKE REF 615 ( Catalouge is attached as Annex)
O/C (51)
1 System Data:
System Voltage 0.415 KV
Selected CT ratio 5000 /1A
Max. Load Current 3953 A
Rated Voltage 0.433 KV
Sym. SC Cuurrent during 3
( Minimum Fault Lavel as per ETAP)
ph fault 63.34 KA
25% Fault level choosen to
reduce stress of the 15.835 KA ( Fault Current Set 25% for Incomer)
system
15835 A
Max. Load Current 3953 A
Time In Sec.
5.6
Incomer
Proposed Time Setting:
BC
Considering, NI curve as Per IEC 60255 -4 - Standard Inverse
1
ROT ( Relay Operating time) = 0.14
(PSM)^0.02 -1
= 4.0 s
Minimum Operating time of Breaker 20 ms
Grading Margine for next upstream breaker 100 ms 0.1
Hence, Total Delay Operating time delay (DOTR) 0.12 S
TMS = DOTR
ROT
= 0.03
0.01
C PCC-12 5000A ACB ( Buscoupler)
0.1 1 10 100 1000 10000 100000
( Fault Current as per ETAP Report)
Relay Details: ABB MAKE REF 615 ( Catalouge is attached as Annex) Fault MVA
O/C (51)
1 System Data:
System Voltage 0.415 KV
Selected CT ratio 5000 /1A COORDINATION GRAPH - OC -PCC-21
Max. Load Current 3660 A
Rated Voltage 0.433 KV
Sym. SC Cuurrent during 3
( Minimum Fault Lavel as per ETAP)
ph fault 63.34 KA
25% Fault level choosen to
reduce stress of the 15.835 KA ( Fault Current Set 25 % for BC)
system
15835 A
Max. Load Current 3660 A
TMS = DOTR
ROT
= 0.02
2 Setting Calculation for Instantanious OC (50)>>
100
Time In Sec.
BC
Pick up setting in the Relay = 1.8 x ln
0.1
TMS = DOTR
ROT
= 0.03
D PCC-12 5000A ACB ( Incomer)
( Fault Current as per ETAP Report)
Relay Details: ABB MAKE REF 615 ( Catalouge is attached as Annex)
O/C (51)
1 System Data:
System Voltage 0.415 KV
Selected CT ratio 5000 /1A
Max. Load Current 3660 A
Rated Voltage 0.433 KV
Sym. SC Cuurrent during 3
( Minimum Fault Lavel as per ETAP)
ph fault 63.34 KA
25% Fault level choosen to
reduce stress of the 15.835 KA ( Fault Current Set 25% for Incomer)
system
15835 A
Max. Load Current 3660 A
PCC-13
Incomer 415 5000 1 SI 2 0.05 SI 0.6 0.5 SI 4.4 0.03
Incomer
System Voltage 0.415 KV
Selected CT ratio 5000 /1A BC BC 415 5000 1 SI 1.8 0.04 SI 0.4 0.4 SI 4.4 0.03
Max. Load Current 3236 A
Rated Voltage 0.433 KV
Sym. SC Cuurrent during 3
( Minimum Fault Lavel as per ETAP)
ph fault 63.34 KA 1000
25% Fault level choosen to
reduce stress of the 15.835 KA ( Fault Current Set 25 % for BC)
system
15835 A
Max. Load Current 3236 A 100
Time In Sec.
= 3559.6 A Incomer
Proposed PSM = Fault current BC
POC
4.4 1
Proposed Time Setting:
Time In Sec.
BC
Proposed PSM = Fault current (25% Fault Current choosen to reduce 0.01
POC stress of the system for BC) 0.1 1 10 100 Fault MVA 1000 10000 100000
5.6
Proposed Time Setting:
TMS = DOTR
ROT
= 0.03
F PCC-13 5000A ACB ( Incomer)
( Fault Current as per ETAP Report)
Relay Details: ABB MAKE REF 615 ( Catalouge is attached as Annex)
O/C (51)
1 System Data:
System Voltage 0.415 KV
Selected CT ratio 5000 /1A
Max. Load Current 3236 A
Rated Voltage 0.433 KV
Sym. SC Cuurrent during 3
( Minimum Fault Lavel as per ETAP)
ph fault 63.34 KA
25% Fault level choosen to
reduce stress of the 15.835 KA ( Fault Current Set 25% for Incomer)
system
15835 A
Max. Load Current 3236 A