Optimal Selection of Pmu Locations For Enhanced State Estimation in Smart Grid
Optimal Selection of Pmu Locations For Enhanced State Estimation in Smart Grid
560
last section of the paper presents the conclusions drawn between measurements and state variables is linear and
from the present work. a non-iterative least square solution may be used to de-
termine the system state [6]. The PMU provides a syn-
STATE ESTIMATION AND PHASOR chronized measurement of the voltage phasor at a bus
MEASUREMENT and the current phsors through the branches associated
incident on it. The measurements are synchronized via
The electric power system consists of a large number of the GPS signal with a frequency of about 30 samples
interconnected elements forming a geographically huge per second. Due to technical and economical constraints
and complex dynamic system. Because of its nature the it may not be feasible to install PMUs at every bus of
system experience disturbances of varying scale as the the system. However a system can still be made observ-
operating conditions change. A set of imminent disturb- able by placing PMUs only on few selected buses.
ances is referred to as contingencies. Power system se- Therefore the existing SE can be improved by using
curity is defined as the ability of the system to survive data from a few PMUs installed at critical locations.
plausible contingencies without interruption to the pow-
er supply. In order to maintain a normal secure opera- HYBRID STATE ESTMATION
tion it becomes mandatory to keep a watch on the power
system. The operating conditions of a power system at Hybrid State Estimator is used to estimate the states of a
any given instant can be determined if in addition to the system monitored by conventional and Phasor Meas-
network topology, the complex voltage phasor at every urement Units. As discussed in the previous section, one
system bus are known. Since the set of complex voltage of the remarkable properties of Synchrophasor meas-
phasors completely specifies the system, it is referred to urement is to convert non linear state estimator to a lin-
as the system state. State estimation function utilizes ear state estimator. This means that the relation between
telemetered measurements to generate an optimal esti- the measured quantities and the system state is linear
mate of the system state. and states can be calculated (rather than being estimat-
For reliable state estimation, it is necessary that ed) using measured data).
the number of measurements should be greater than the A hybrid SE may be implemented by utilizing either of
number of states. This condition is called the observa- the following two approaches:
bility criterion. Apart from providing an optimal state 1. Calculating the states using synchrophasor (PMU
estimate the estimator also detect and filter out gross based) measurements only and running conventional
errors in the measurement set (bad data detection) and state estimation by utilizing these calculated values.
detect the topology errors in the network configuration. This is a two step process.
Traditionally, the input measurements to the state 2. Mixing the synchrophasor measurements with con-
estimator were provided by the remote terminal units ventional measurements and estimating the system
(RTUs) at the substations. These measurements did not states while giving more weightage to Synchro-
contain the phase angles due to the difficulty associated phasor measurements.
with the synchronization of measurements. Consequent- The second approach has been utilized in the present
ly the phase angle was estimated with the slack bus as work.
reference. However with the advent of PMUs this diffi- The state estimation model is as follows:
culty can be removed as the PMU measures voltage and z = h(x) + v (1)
current phasors synchronized through GPS. where z is the mൈ1 vector of measurements provided by
It is expected that the availability of large SCADA (bus voltage magnitudes, branch active and
amounts of phasor measurements will completely reactive power flows, and bus active and reactive injec-
change the nature of SEs. A major advantage of obtain- tions) and by PMUs (bus voltage phasors and branch
ing complex measurements of voltages and currents is current phasors), x is the nx1 state vector (n = 2N൏m),
that the estimator equations will be linear and the esti- h(x) is a mൈ1 non linear vector function relating meas-
mation will not require iterations like the present esti- urements to states, and v is the mൈ1 measurement error
mator. This SE can be updated quite often maybe in vector. The errors are assumed to be independent and
seconds (rather than minutes today) and because all the uncorrelated, having a Gaussian distribution with zero
measurements are time stamped, the time skew of the mean E(v) = 0 and covariance matrix R = cov(v) = di-
measurements will always be known resulting in much ag(σ12…..σm2) where σi is the standard deviation of the ith
more accurate SE results. It will also be possible to ex- measurement. In this work a reference free non-linear
change these SE results among neighbouring power WLS state estimator has been used [7]. The SE algo-
operators or up to the next level control centre [5]. rithm considers traditional as well as synchronized
In the conventional SE, the relationship between phasor measurements and utilizes rectangular coordi-
measurements and state variables is non linear and it has nates for the first iteration and polar coordinates for the
to be linearised and then the solution to WLS problem is next iterations. The polar coordinate formulation of cur-
obtained by using iterative technique. However if a rent phasors is a better choice than the rectangular coor-
PMU is placed at every bus of the system the relation dinate formulation, because the magnitude and phase of
561
a phasor quantity as measured and computed in a PMU ୠ ୲୰୳ୣ is actual value of the b-th state variable achieved
are largely independent variables. from load flow.
In order to find out the optimal SE solution, the follow- N is number of system buses.
ing objective function of square errors is minimized: 2N – 1 is number of state variables.
J(x)=[ ܢെ ])ܠ(ܐTି܀ [ ܢെ ])ܠ(ܐ (2) In terms of variance MSE is given as
ଶିଵ ଶ
The normal equation that is solved in order to find out ൫ොୠ ୣୱ୲ ൯
the state estimation solution is
(7)
ʹ െ ͳ
۵൫ ܓ ܠ൯ο ܓܠൌ ۶ ܂൫ ܓ ܠ൯ି܀ ൣ ܢെ ܐሺ ܓ ܠሻ൧ (3) ୠୀଵ
Where, k is the iteration index, xk is the solution vector A 7-bus system of fig. 1 is used to obtain PMU loca-
ப୦ሺ୶ሻ tions for minimum state estimation error.
at iteration k, ۶ሺܠሻ ൌ ப୶ is the measurement Jacobi-
an matrix ሺ ൈ ሻǡ and ۵൫ ܓܠ൯ ൌ ۶ ܂൫ ܓ ܠ൯ି܀ ۶൫ ܓ ܠ൯ is CASE STUDY
the gain matrix ሺ ൈ ሻǤ
A seven bus test network as shown in fig. 1 is used to
PMU PLACEMENT CRITERION find out PMU locations for best state estimation solution
[7]. It is assumed that three PMUs are available for in-
A suitable criterion is essential for state estimation. stallation on the 7 bus network. It is assumed that PMUs
Considering which as the objective function for optimi- available have sufficient channel capacity to monitor all
zation algorithm, optimal placement of certain number the branches incident on a particular bus. Various com-
of PMUs is carried out. To evaluate the accuracy of a binations are possible for installation of these three
process, an indicator called Mean Square Errors can be PMUs. For all these combinations SE algorithm was run
used which is expressed as. and MSE was determined. The buses combinations and
σొ ౩౪ ି୶ ౪౨౫ ൯మ there corresponding MSE values are listed in table 1.
సభ൫୶
ൌ (4) It may be observed from table 1 that the minimum mean
square error is 0.099104 p. u. which is available when
The outputs of state estimation program, i.e. the esti-
mated state variables are obtained from the values of all the three PMUs are placed at branches 1, 6, and 7.
of the measuring devices through the Weighted Least Therefore the available PMUs should be placed at these
Squares method. On the other hand, for simulation stud- three branches to obtain best state estimation results.
ies according to the system planning scheme for state
estimation process, errors of measuring devices are ac-
quired randomly through normal distribution with a Bus Bus Bus
mean error equal to zero and then summed up with the
actual value of the desired variable, which is achieved
from load flow. Assuming Zmeas as the measured value
obtained from a measuring device and ZTrue as the actual
value of the measured quantity, the measured values, Bus Bus
with defining e as random measuring error, can be ex-
pressed as
୰୳ୣ ൌ ୫ୣୟୱ (5)
In system planning, therefore, one-time running of the Bus Bus
state estimation cannot be a proper indicator for evaluat-
ing the accuracy of state estimation for the placement
problem of PMUs. Hence, the MSE equation, as defined Power flow measurement
above, would not be an appropriate method for evaluat-
Power injection measurement
ing the accuracy of state estimation in the problem of
PMU placement. Thus, the average of squared state es-
timation errors should be utilized for minimizing the
error. In other words, the error of state estimation is Fig. 1 Seven bus test system.
random and its mean value is calculated using the itera-
tion process [8]. CONCLUSION
ୣୱ୲ ଶ
ଵ ଶିଵ ൫ୠǡ୧ െ ୠ ୲୰୳ୣ ൯ State estimation will form one of the most important
σୠୀଵ
ൌ ʹ െ ͳ (6) energy management functions to be enhanced in order
ͳͲͲͲ
୧ୀଵ to make the conventional grid smart. Inclusion of phasor
where measurements in the conventional state estimation will
ୠǡ୧ ୣୱ୲ is estimated value of the b-th state variable in the enhance its performance significantly. Due to high cost
i-th state estimation process. of phasor measurement units their optimal utilization is
mandatory. However most of the methods reported for
562
optimal PMU placement minimize the number of PMUs REFERENCES
and do not offer a criterion to choose PMU placement
locations if there are multiple solutions providing mini- [1] Amin M. (2007): ‘Preventing Blackouts’, Scientific
mum number PMUs. In the present work one such crite- American, pp. 60-67.
rion has been presented to decide the best locations for
the available PMU such that the state estimation error is [2] Collier S E (2009): ‘Ten steps to a smarter grid’,
minimized. IEEE Industry Applications. 16(2), pp. 62-8.
Branch combinations Mean square error (p.u.) [3] Terzija V.r, Valverde G., Cai D., Regulski P.,
5,6,7 0.1167 Madani V., Fitch J., Skok S., Begovic M. M.,
4,6,7 0.1089 Phadke A. (2011): ‘Wide-AreaMonitoring,
4,5,7 0.1206 Protection, and Control of Future Electric Power
4,5,6 0.1093 Networks’, Proceedings of the IEEE, 99(1), pp. 80-
3,6,7 0.1072 93.
3,5,7 0.1205
3,5,6 0.1093 [4] Manousakis M. N., Korres G. N., Georgilakis P. S.
3,4,7 0.1206 (2012): ‘Taxonomy of PMU placement
3,4,6 0.1090 methodologies’, IEEE Transactions Power System,
27(2), pp. 1070-1077..
3,4,5 0.1212
2,6,7 0.1085
[5] Bose A. (2010): ‘Smart transmission grids and their
2,5,7 0.1208
supporting infrastructure’, IEEE Transactions Smart
2,5,6 0.1077 Grid, 1(1), pp. 11-19.
2,4,7 0.1208
2,4,6 0.1081 [6] Ree J. D. L., Centeno V., Thorp J. S., Phadke A. G.
2,4,5 0.1214 (2010): ‘Synchronised phasor measurement
2,3,7 0.1197 applications in power systems’, IEEE Transactions
2,3,6 0.1086 Smart Grid, 1(1), pp. 20-27.
2,3,5 0.1198
2,3,4 0.1202 [7] Manousakis K. G. N and M. Nikolaos (2012): ‘A
1,6,7 0.0991 state estimator including conventional and
1,5,7 0.1280 synchronized phasor measurements’, Elsevier
1,5,6 0.1213 Computers and Electrical Engineering, 38(2), pp.
1,4,7 0.1271 294–305.
1,4,6 0.1118
1,4,5 0.1062 [8] Karami Z. A., Rajabi M. H., Abadi and Haji M. E.
1,3,7 0.1220 (2012), ‘Optimal Placement of a Defined Number of
1,3,6 0.1135 Phasor’, in Proc. IEEE 2nd Iranian Conference on
1,3,5 0.1067 Smart Grids (ICSG), Tehran, 2012.
1,3,4 0.1224
1,2,7 0.1195
1,2,6 0.1128
1,2,5 0.1053
1,2,4 0.1143
1,2,3 0.1165
2,6,7 0.1085
2,5,7 0.1208
2,5,6 0.1077
2,4,7 0.1208
2,4,6 0.1081
2,4,5 0.1214
2,3,7 0.1197
563