0% found this document useful (0 votes)
172 views1 page

Series VE - VEFT - V - VFT PowerSafe TempComp PDF

The document provides float voltage specifications for Hawker Powersafe VE, VE FT, V, and V FT valve regulated lead acid batteries. It states that the float voltage at 20°C is 2.28V per cell and provides a table adjusting the float voltage according to temperature from 0°C to 40°C. It also specifies that the voltage should be adjusted by +3mV/°C for temperatures below 20°C and -3mV/°C for temperatures above 20°C.

Uploaded by

Fernando Lopez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
172 views1 page

Series VE - VEFT - V - VFT PowerSafe TempComp PDF

The document provides float voltage specifications for Hawker Powersafe VE, VE FT, V, and V FT valve regulated lead acid batteries. It states that the float voltage at 20°C is 2.28V per cell and provides a table adjusting the float voltage according to temperature from 0°C to 40°C. It also specifies that the voltage should be adjusted by +3mV/°C for temperatures below 20°C and -3mV/°C for temperatures above 20°C.

Uploaded by

Fernando Lopez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

HAWKER S.A.R.L.

Rue A. Fleming – Z.I EST – BP 962


62033 Arras Cedex - France
Tel : +33 (0)3 21 60 25 25
Fax : +33 (0)3 21 73 16 51
E mail : [email protected]
www.enersys.com

STATEMENT
We, HAWKER SARL Arras, hereby certify that :
The float/charge voltage for Powersafe VE, VE FT, V, V FT ranges (valve regulated
lead acid batteries) is 2.28Vpc at 20°c
It is required to adjust the float voltage according to the temperature as follows :

Temperature Float voltage range per cell


00°c 2.33-2.36 V
10°c 2.30-2.33 V
20°c 2.27-2.30 V
25°c 2.25-2.28 V
30°c 2.24-2.27 V
35°c 2.22-2.25 V
40°c 2.21-2.24 V

For battery charger with automatic temperature compensation, the


voltage/temperature compensation is + 3mV/°C/Cell f or a temperature lower than
20°C (the reference temperature being 20°C) and - 3 mV/°C/Cell for a temperature
higher than 20°C