01 FloWatch System Architecture PDF
01 FloWatch System Architecture PDF
System Architecture
FLOWATCH MULTI PHASE FLOW METER
(System architecture)
Dp transmitter:
•Typical calibration range for Dp is 0 to 4000 mbar. MPFM operating
envelope is calculated for max Dp 3000 mbar.
•We keep extra 1000 mbar to measure the high instantaneous Dp generated
by the eventual liquid/gas slugs and avoid Dp readings saturation.
•Typical accuracy for the Dp transmitter is 0.075% of the calibrated span.
•The Dp transmitter is connected to the FlowComputer trough traditional 4
to 20 mA signal transmission.
• Typical damping for the 4-20 mA analogue
output is 0.2 second only, to keep fast responce
on signal transmission to the Flow Computer.
• The Dp transmitter is normally HART
protocoltype, we mainly use ABB or Yokogawa.
FLOWATCH MULTI PHASE FLOW METER
(System architecture)
Sensor (FEB):
• It is connected trough coaxial cables to the capacitance and conductance electrodes
trought the pins.
•It receive power from Flow Computer cabinet and execute the capacitance /conductance
measurments continuously
• It send continuously the measurements to Flow Computer by fast serial communication.
•It has a built in processor
with dedicated logic which
decide the measurement
method, CAPACITANCE or
CONDACTANCE to be used
according to live
measurements.
•Only one of the two
methode at the time can
be used
FLOWATCH MULTI PHASE FLOW METER
(System architecture)
Pressure transmitter:
• Measures the pressure inside the MPFM which is used for correction of fluids properies and
PVT parameters and to report readings to STD condition.
•Pressure transmitter is typically ABB or Yokogawa, HART protocol type.
•Typical accuracy for the Pressure transmitter is 0.075% of the calibrated span
•Typical calibration range is 0 to 1000 psi for sensors ANSI 600 class.
FC SW status lamp
(normally ON= running)
(blinking= Alarm)
Flow Computer
Power distribution
terminals
Exi barriers
Power rectifier
FLOWATCH MULTI PHASE FLOW METER
(System architecture)
Digital I/O module
Flow Computer part description (EXD): Used for:
Flow Computer RS 232 port: -Push button control
- Receive continuously data package from the FEB, -Serial port communication for modbus
CAP/COND
It is mandatory to
respect the module
hardware configuration
order. Differently the
calculation SW will not
run
It is mandatory to
respect the module
hardware configuration
order. Differently the
calculation SW will not
run
24 Vdc power
from rectifier
FLOWATCH MULTI PHASE FLOW METER
(System architecture)
Modbus serial
communication RS 232 to RS
485 converter (H3):
To wireless
Antenna
FLOWATCH MULTI PHASE FLOW METER
(System architecture)
Local display, RUN/ALARM lamp and
push button control system: