E&M UPS - 1 Sizing Calculation: S.N. Board Start Board/Load Finish

This document provides sizing calculations for two E&M UPS systems - UPS-1 and UPS-2. For UPS-1, the total connected load is 57.44 kW. With a 10% design margin and considering a 96% rectifier efficiency and 90% power factor, the required UPS rating is 73.1 kVA. A selection is made of two 80 kVA UPS units in parallel redundant configuration. For UPS-2, the total connected load is 25.00 kW. Sizing calculations are also provided but no UPS selection is stated.

Uploaded by

Manglesh Singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
91 views

E&M UPS - 1 Sizing Calculation: S.N. Board Start Board/Load Finish

This document provides sizing calculations for two E&M UPS systems - UPS-1 and UPS-2. For UPS-1, the total connected load is 57.44 kW. With a 10% design margin and considering a 96% rectifier efficiency and 90% power factor, the required UPS rating is 73.1 kVA. A selection is made of two 80 kVA UPS units in parallel redundant configuration. For UPS-2, the total connected load is 25.00 kW. Sizing calculations are also provided but no UPS selection is stated.

Uploaded by

Manglesh Singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

E UPS-1 2 Sizing Calculations JKC-GCC-MEP-SVN-180002-A6

E&M UPS -1 Sizing Calculation

Connecte
d Load in

MD Load

MD Load
Demand
Supply

in kVA
Status

Factor

Factor
Power

in kW
Class
kW
S.N. Board Start Board/Load Finish

1 ULDB - 1 PLAT.LVL. (SOUTH) 0.69 W VE 0.90 1.00 0.69 0.77


2 ULDB - 2 PLAT.LVL. (SOUTH) 0.89 W VE 0.90 1.00 0.89 0.99
3 ULDB - 5 CON. LVL. (SOUTH) 1.03 W VE 0.90 1.00 1.03 1.15
4 ULDB - 6 CON. LVL. (SOUTH) 1.28 W VE 0.90 1.00 1.28 1.42
5 ULDB - 7 COVER STREET. (SOUTH) 1.16 W VE 0.90 1.00 1.16 1.29
6 TLDB - 1 TUNNEL (UP / DOWN TUNNEL) 2.40 W VE 0.90 1.00 2.40 2.67
8 UPDB - 1 CON.LVL 9.00 W VE 0.90 1.00 9.00 10.00
UPS DISTRIBUTION PANEL - 1
9 UPDB - 2 CON.LVL (SOCKET+VAC SCADA) 5.00 W VE 0.90 1.00 5.00 5.56
10 PSD (WORKING) 27.99 W VE 0.90 1.00 27.99 31.10
11 AFC SYSTEM (SOUTH) 5.00 W VE 0.90 1.00 5.00 5.56
12 SIGNAGE DB - 1 PLAT.LVL. (SOUTH) 2.00 W VE 0.90 1.00 2.00 2.22
(TUNNEL SIGNAGE & STATION SIGNAGE)
13 SIGNAGE DB - 2 CON. LVL. (SOUTH) 1.00 W VE 0.90 1.00 1.00 1.11
Total Load 57.44 0.90 1.00 57.44 63.83

Power Demand 57.44 KW


Design Margin 1.10
Rectifier efficiency 96%
Power Factor 0.90

UPS Rating Reqired (KVA) = Power Demand x Design Margin 73.1 kVA
( Rectifier efficiency x Power Factor )

0 = 2 x 80 kVA
Selected UPS rating(design temperature at 40 C)

Note:- Based on the above loads, 01 set of 02 Nos. UPS of 80 KVA each have been considered in 100% parallel redundant,

MMRC / UGC-05 1
E UPS-1 2 Sizing Calculations JKC-GCC-MEP-SVN-180002-A6

E&M UPS -2 Sizing Calculation

Connected

MD Load

MD Load
Demand
Load in

Supply

in kVA
Power
Status

Factor

Factor
Class

in kW
kW
S.N. Board Start Board/Load Finish

1 ULDB - 3 PLAT.LVL. (NORTH) 0.71 W VE 0.90 1.00 0.71 0.79


2 ULDB - 4 PLAT.LVL. (NORTH) 0.54 W VE 0.90 1.00 0.54 0.60
3 ULDB - 8 CON.LVL. (NORTH) 1.39 W VE 0.90 1.00 1.39 1.54
4 ULDB - 9 CON.LVL. (NORTH) 1.38 W VE 0.90 1.00 1.38 1.53
5 ULDB - 10 COVER STREET 1.79 W VE 0.90 1.00 1.79 1.99
6 ULDB - 11 ANCILLARY BUILDING 1.49 W VE 0.90 1.00 1.49 1.65
7 TLDB - 2 TUNNEL (UP / DOWN TUNNEL) 2.20 W VE 0.90 1.00 2.20 2.44
8 UPS DISTRIBUTION PANEL - 2 UPDB - 3 CON.LVL (SOCKET+TVS SCADA) 25.00 W VE 0.90 1.00 25.00 27.78
9 UPDB - 4 CON.LVL (SOCKET+FIRE ALARM+M&E 14.00 W VE 0.90 1.00 14.00 15.56
10 SCADA) DB - 3 PLAT.LVL. (NORTH) (TUNNEL
SIGNAGE 2.00 W VE 0.90 1.00 2.00 2.22
SIGNAGE & STATION SIGNAGE)
11 SIGNAGE DB - 4 CON. LVL. (NORTH) 1.00 W VE 0.90 1.00 1.00 1.11
12 PSD (STAND BY) 27.99 W VE 0.90 1.00 27.99 31.10
13 AFC SYSTEM (NORTH) 5.00 W VE 0.90 1.00 5.00 5.56
Total Load 84.48 0.90 0.67 84.48 93.87

Power Demand 84.48 KW


Design Margin 1.10
Rectifier efficiency 96%
Power Factor 0.90

UPS Rating Reqired (KVA) = Power Demand x Design Margin 107.6 kVA
( Rectifier efficiency x Power Factor )

Selected UPS rating(design temperature at 400C) = 2 x 120 kVA

Note:- Based on the above loads, 01 set of 02 Nos. UPS of 120 KVA each have been considered in 100% parallel redundant,

MMRC / UGC-05 2