Venturi 1
Venturi 1
1.1 Introduction
Industrial flow measurements include measuring of flow rate of solids, liquids and gases. There are two
basic ways of measuring flow ; one on volumetric basis and the other on weight basis. Solid materials are
measured in terms of either weight per unit time or mass per unit time. Very rarely solid quantity is
measured in terms of volume. Liquids are measured either in volume rate or in weight rate. Gases are
normally measured in volume rate. In this chapter, the flow measurements of liquids and gases will be
discussed in detail rather than that of solids.
Fluids are classified into two types, namely incompressible and compressible. Fluids in liquid phase
are incompressible whereas fluids in gaseous phase are compressible. Liquid oc- cupies the same volume at
different pressures where as gases occupy different volumes at different pressures. This point has to be
taken care of while calibrating the flow meters. The measurements taken at actual conditions should be
converted either to Standard temperature (0°C) and pressure (760 mm Hg) base (STP base) or to Normal
temperature (20°C) and pres- sure (760 mm Hg) base (NTP base).
C-8\N-IND\CH-5-1
2 INDUSTRIAL INSTRUMENTATION
They are :
1. Mechanical type flow meters. Fixed restriction variable head type flow meters using
different sensors like orifice plate, venturi tube, flow nozzle, pitot tube, dall tube, quan- tity meters like
positive displacement meters, mass flow meters etc. fall under mechanical type flow meters.
2. Inferential type flow meters. Variable area flow meters (Rotameters), turbine flow
meter, target flow meters etc.
3. Electrical type flow meters. Electromagnetic flow meter, Ultrasonic flow meter, Laser
doppler Anemometers etc. fall under electrical type flow meters.
4. Other flow meters. Purge flow regulators, Flow meters for Solids flow measure- ment,
Cross-correlation flow meter, Vortex shedding flow meters, flow switches etc.
The working principle construction, calibration etc. of the above flow meters will be discussed in
the following sections.
V2 A2
A1
V1
Z1Z2
P1P2
Datum line
Fig. 1.1 Schematic representation of a one dimensional flow system with a restriction
C-8\N-IND\BOOK1-1
FLOW 3
Head—type flow measurement derives from Bernoulli’s theorem which states that in a flowing
stream, the sum of the pressure head, the velocity head and the elevation head at one point is equal to their
sum at another point in the direction of flow plus the loss due to friction between the two points. Velocity
head is defined as the vertical distance through which a liquid would fall to attain a given velocity. Pressure
head is the vertical distance which a column of the flowing liquid would rise in an open-ended tube as a
result of the static pressure.
In general, a one—dimensional flow system is assumed. The schematic representation of such a
system with a restriction in the pipeline is shown in Fig. 1.1.
1.4.1.1 Flow of Incompressible Fluids in Pipes
Section-1 is the position of upstream tap and Section-2 that for downstream. The terms T, A, , V, P
and Z represent Temperature, Area, Density, Stream velocity, Pressure and Central line elevation
respectively. If this elevation is quite small such that Z2 – Z1 is negligible, the Bernoulli’s equation for an
incompressible (1 = 2) frictionless and adaptive flow is written as
2 2
P1 V1 P2 V2
...(1.1)
2g 2g
where g = acceleration due to gravity, giving
2
V2
P1 – P2 = [1 – (V1/V2)2] ...(1.2)
2g
The continuity equation for this type of flow is
Q = A2V2 = A1V1 ...(1.3)
where Q = volume flow rate in m3/sec.
Combining equations (1.2) and (1.3) and manipulating, one gets
A2 µ y
Q=AV =
¡ va2 g (P P ) ¡ A
1 2 2 gh ...(1.4)
M 2
2 2
[1 (A 2 /A 1 )2 ]
¡µ ¡J
where Mva = 1 = Velocity approach factor
1–
j A yj
¡y
2 2
A 1
P1 – P2
h = Differential head.
This is equation for the ideal volume flow rate.
For actual flow conditions with frictional losses present, a correction to this formula is necessary.
Besides, the minimum area of flow channel occurs not at the restriction but at some point slightly
downstream, known as the ‘Venacontracta’. This in turn depends on the flow rate. While the tapping
positions are fixed, the position of maximum velocity changes with changing flow rate.
The basic equations are :
V = K1 Q h ...(1.5)
= K1A h ...(1.6)
W = K1A h P ...(1.7)
4 INDUSTRIAL INSTRUMENTATION
W = A12 ...(1.18)
2 gK . P1 . (P2 /P1)2/K (P2 /P1)(K 1)/K
Manometer, however, measures (P – KP ) 1and v1 not P2/P11,therefore, it is necessary to convert the
4 (P2 /P1)2/K
equation (1.18) such that W is a function 1of (P21 – P2). Write P2/P1 = 1 – x such that x = 1 – (P2/P1). In
general, for gas flow P2/P1 is very close to unity such that x is very close to zero.
Hence, (P2/P1)2/K 1 – (2/K) x = 1 – (2/K) + (2/K) (P2/P1)
(P2/P1)(K+1/K) 1 – (K + 1/K) + (K + 1/K) (P2/P1) ...(1.19)
using equation (1.19), equation (1.18) is modified to
2 g (P1 P2 )
w = CA 2 ...(1.20)
1
v1 [1 (P2 /P1)]
4 2/ k
For quick calculation an additional parameter known as the rational expansion factor Y is defined as
Compressible flow rate (mass) Incompressible
Y = flow rate (mass)
By determining the mass flow rate for incompressible fluids and multiplying with Y, flow rate for
compressible fluids can be found out and Y can be easily shown as
1 4 . K (P2 /P1)2/K . 1 (P2 /P1)(K–1)/K
Y= 1 4 (P2 /P1)2/K
...(1.21)
K1 1 (P2 /P1)
Instead of calculating Y from the equation (1.21) empirical relations are suggested which give good
results for limited (P2/P1) values, such as 0.8 1.0.
Y = 1 – [0.41 + 0.354] (P1 – P2/KP1) ...(1.22)
When the gas contains moisture, as further correction is required to account correctly for the
density of the vapour.
Pv {(Sv /S) 1}
M=1+ P ...(1.23)
where Pv = Vapour pressure (abs)
Sv = Vapour specific gravity referred to air at the same pressure and temperature S = Specific
gravity of the gas
P = Pressure of the gas.
The specific volume of the gas may be found from
yRT
V= P ...(1.24)
where y = compressibility factor
R = gas constant
The flow equation for gases is
The flow pattern and the sharp leading edge of the orifice plate (Fig. 1.3) which pro- duces it are of
major importance. The sharp edge results in an almost pure line contact be- tween the plate and the
effective flow, with the negligible fluid-to-metal friction drag at the boundary.
d D
F
t
Type-1 Type-2 Type-3
+ – + + –
–
Diagram of standard orifice Diagram of standard orifice Diagram of orifice plate with
plate with annular chambers plate with single taps pressure taps similar to
standard type
There are five common locations for the differential pressure taps :
(i) Flange taps
(ii) Venacontracta taps
(iii) Radius taps
(iv) Full flow or pipe taps and
(v) Corner taps.
(i) Flange taps. They are predominantly used for pipe sizes 50 mm and larger and the
centerlines are 25 mm from the orifice plate surface. They cannot be used for pipe size of less than 35 mm
diameter. Since the venacontracta may be closer than 25 mm from the orifice plate.
(ii) Venacontracta taps. These taps use an upstream tap located one pipe diameter upstream
of the orifice plate, and a downstream tap located at the point of minimum pressure. Venacontracta taps
normally limited to pipe size 150 mm or large depending upon the flange rating and dimensions.
(iii) Radius taps. d1 = D and d2 = 1/2 D. These are similar to venacontracta taps except that
downstream tap is located at one half pipe diameter. These are generally considered superior to the
venacontracta tap because they simplify the pressure tap location dimensions and do not vary with changes
in orifice ratio.
(iv) Pipe taps. Pipe taps are located 2.5 pipe diameters upstream (d1 = 2.5D) and 8 diameters
downstream (d2 = 8D) from the orifice plate. Because of the distance from the ori- fice, exact location is
not critical, but the effects of pipe roughness, dimensional inconsistencies and so on are more severe.
(v) Corner taps. These taps are similar in many respects to flange taps, except that the pressure
is measured at the ‘Corner’ between the orifice plate and the pipe wall. These are used for diameters of less
than 50 mm.
1.4.3 Venturi Tubes
Venturi tubes are differential pressure producers, based on Bernoulli’s Theorem. General per- formance
and calculations are similar to those for orifice plates. In these devices, there is a continuous contact
between the fluid flow and the surface of the primary device.
1.4.3.1 Classic Venturi Construction : [Long Form Venturi]
The classic Herchel Venturi tube is given in Fig. 1.7.
It consists of a cylindrical inlet section equal to the pipe diameter ; a converging conical section in
which the cross sectional area decreases causing the velocity to increase with a corresponding increase in
the velocity head and a decrease in the pressure head ; a cylindrical throat section where the velocity is
constant so that the decreased pressure head can be meas- ured ; and a diverging recovery cone where the
velocity decreases and almost all of the original pressure head is recovered. The unrecovered pressure head
is commonly called as head loss.
12 INDUSTRIAL INSTRUMENTATION
Convergent
Cylindrical entrance Throat
inlet
Divergent outlet
Annular chambers
Classic Herschel venturi with annular pressure chambers
Fig. 1.7 Classic Long form Venturi
The classic venturi is always manufactured with a cast iron body and a bronze or stain- less steel
throat section. At the midpoint of the throat, 6 to 8 pressure taps connect the throat to an annular chamber
so the throat pressure is averaged. The cross sectional area of the chamber is 1.5 times the cross sectional
area of the taps. Since there is no movement of fluid in the annular chamber, the pressure sensed is strictly
static pressure. Usually 4 taps from the external surface of the venturi into the annular chamber are made.
These are offset from the internal pressure taps. It is through these taps that throat pressure is measured.
Limitations
This flow meter is limited to use on clean, non-corrosive liquids and gases, because it is impossible
to clean out or flush out the pressure taps if they clog up with dirt or debris.
1.4.3.2 Short Form Venturi Tubes
In an effort to reduce costs and laying length, manufactures developed a second genera- tion, or
short-form venturi tubes shown in Fig. 1.8.
Throat
Inlet cone Outlet cone
Inlet
Short-form venturi tube
The pressure taps are located one-quarter to one-half pipe diameter upstream of the inlet cone and at
the middle of the throat section. A piezometer ring is sometimes used for differential pressure
measurement. This consists of several holes in the plane of the tap loca- tions. Each set of holes is
connected together in an annular ring to give an average pressure.
Venturis with piezometer connections are unsuitable for use with purge systems used for slurries
and dirty fluids since the purging fluid tends to short circuit to the nearest tap holes. Piezometer
connections are normally used only on very large tubes or where the most accurate average pressure is
desired to compensate for variations in the hydraulic profile of the flowing fluid. Therefore, when it is
necessary to meter dirty fluids and use piezometer taps, sealed sensors which mount flush with the pipe
and throat inside wall should be used.
Single pressure tap venturis can be purged in the normal manner when used with dirty fluids.
Because the venturi tube has no sudden changes in contour, no sharp corners, and no projections, it is often
used to measure slurries and dirty fluids which tend to build up on or clog of the primary devices.
1.4.3.3 Types of Venturi Tubes
Venturis are built in several forms. These include
1. a standard long-form or classic venturi tube (Fig. 1.7)
2. a modified short form where the outlet cone is shortened (Fig. 1.8)
3. an eccentric form [Fig. 1.9 (a)] to handle mixed phases or to minimize buildup of heavy
materials and
4. a rectangular form [Fig. 1.9 (b)] used in duct work.
Fig. 1.9
It is recommended that the use of straightening vanes upstream of the venturi to reduce the inlet
pipe length. The vane installation should have a minimum of 2 diameters upstream and 2 diameters
downstream before entering the venturi. There is no limitation on piping configuration downstream of the
venturi except that a value should be no closer than 2 diameters.
1.4.4 Flow Nozzle
1.4.4.1 Flange Type Flow Nozzle
The Flow nozzle is a smooth, convergent section that discharges the flow parallel to the axis of the
downstream pipe. The downstream end of a nozzle approximates a short tube and has the diameter of the
venacontracta of an orifice of equal capacity. Thus the diameter ratio for a nozzle is smaller or its flow
coefficient is larger. Pressure recovery is better than that of an orifice. Fig. 1.10 shows a flow nozzle of
flange type.
D
Nipple
threaded
at one end
2½ k min.
D d
k
Weld
1.4.4.3 Advantages
1. Permanent pressure loss lower than that for an orifice plate.
2. It is suitable for fluids containing solids that settle.
3. It is widely accepted for high pressure and temperature steam flow.
1.4.4.4 Disadvantages
1. Cost is higher than orifice plate.
2. It is limited to moderate pipe sizes.
3. It requires more maintenance. (It is necessary to remove a section of pipe to inspect or install
it).
1.4.5 Dall Tube
1.4.5.1 Construction And Working
It is a modified version of venturi tube. It produces large differential pressure with low pressure less
than the conventional venturi tube. The photographic view and schematic sketch of the dall tube are shown
in Fig. 1.12.
16 INDUSTRIAL INSTRUMENTATION
Throat connection
Upstream connection
Blow down
Pressure (impulse) cocks
pipe
Air vessels
Root
valves Slope not less
than 1:10
Equalising
valve
Meter of
motor transducer
Fig. 1.13 Pressure connections to meter below orifice for liquids and steam
C-8\N-IND\BOOK1-2
18 INDUSTRIAL INSTRUMENTATION
Blow-off
Fig. 1.14. Pressure connections to meter below orifice for Air and Gases.
Blow-off cocks
Air vessels
+ –
Fig. 1.15 Pressure connections to meter above orifice for liquids and steam
Fig. 1.16 Pressure connections to meter above orifice for air and gases
20 INDUSTRIAL INSTRUMENTATION
Approx. 40 mm bore
& 600 mm length
Dirt trap
Orifice
assembly
To meter
To meter
Lagging
They are also used in the metering of oils or tarry liquids, which are of low viscosity in the mains
due to high temperature ; but owing to atmospheric cooling in pressure pipes these become viscous and as
such make meter sluggish in response.
The sealing pots transmit the orifice pressures to a second and less viscous liquid, the separating
surfaces occurring in parallel bore of the sealing vessels and serving as friction less pistons. These are
usually connected very close to the mains. The sealing liquid must be non- corrosive and immiscible with
the fluid to be metered. It should preferably be of moderately low viscosity such as transformer oil, spindle
oil, kerosene, paraffin oil, glycerine etc.
Fig. 1.18 shows how installation of sealing pot is being made.
+ –
±
Equalising cock
Filling cock To meter
To meter
Test cock
Sealing liquid lighter than the measured medium
7. Drain legs should be installed at the meter when dirt and sediment exist in the connecting
lines.
8. Condenser chambers used for steam lines must be in level.
9. Sealing chambers used for corrosive fluids must be in level and should be vented. The proper
connections for several examples are given in Fig. 1.19
Gas
Steam
V1 , P 1
Stagnation point (V2 = 0)
Pressure P2
Fig. 1.20 Flow around a solid body
The simplest pitot tube consists of a tube with an impact opening of 3.125 mm to 6.35 mm diameter
pointing towards the approaching fluid. This measures the stagnation pressure. An ordinary upstream tap
can be used for measuring the line pressure.
Air flow
A common industrial type of pitot tube consists of a cylindrical probe inserted into the air stream, as
shown in Fig. 1.21. Fluid flow velocity at the upstream face of the probe is reduced substantially to zero.
Velocity head is converted to impact pressure, which is sensed through a small hole in the upstream face of
the probe. A corresponding small hole in the side of the probe senses static pressure. A pressure instrument
measures the differential pressure, which is proportional to the square of the stream velocity in the vicinity
of the impact pressure sensing hole. The velocity equation for the pitot tube is given by
v = Cp 2 gh ...(1.26)
where Cp is the pitot tube constant.
Fig. 1.22 shows a typical pitot tube which also shows the taps for sensing static pres-
sure.
Impact pressure
opening
For high-velocity flow streams, it is required to provide necessary stiffness and strength. A tube
inserted in a high-velocity stream has a tendency to vibrate and get broken. As a result, pitot tubes are
generally used only in low-to-medium flow gas applications where high accu- racy is not required.
1.4.7.2 Averaging Pitot Tube (Annubar)
To obtain a better average value of flow, special two-chamber flow tubes with several pressure
openings distributed across the stream are available, as shown in Fig. 1.23. These annular averaging
elements are called annubars. They consist of a tube with high- and low- pressure holes with fixed
separations.
1.4.7.4 Disadvantages
1. Poor accuracy.
2. Not suitable for dirty or sticky fluids and fluids containing solid particles.
3. Sensitive to upstream disturbances.
1.4.8 Differential Pressure Transmitters
The high performance differential pressure transmitter can be used to measure liquid, gas or steam
flow. It outputs a 4 to 20 mA DC signal corresponding to the measured differen- tial pressure.
In the variable head producers, the relationship between the flow rate and the differen- tial head
produced is expressed as
Q h ...(1.27)
As the above relationship is non-linear, it is necessary to make the current of the trans- mitters as a
linear one. For the purpose of linearising the current, the square root extractor, which may be built-in or
externally added, is used.
Fig. 1.24 shows the photographic view of high performance differential pressure transmitter. Fig.
1.25 shows the differential pressure transmitter with built-in square root extractor and Fig. 1.26 shows the
differential pressure transmitter with external square root extractor.
P ower supply
Fig. 1.25 Differential Pressure transmitter with built-in square root extractor.
P ower supply
Fig. 1.26 Differential Pressure transmitter with external square root extractor.
Fig. 1.27 shows the relationship between the power supply voltage and External load resistance.
Differential pressure transmitters normally require a DC voltage supply of 12 V to 42 V and
connected to various other circuits using two wires only. They are called two wire transmitters.
Sometimes the output signal is passed through a standard resistor, also called a conditioning resistor, of 250
to convert the 4-20 mA current signal into 1-5V DC voltage signal. The load independency of such a
standard transmitter may vary from 600 to 1500 . Improved version of such transmitters are called as
“Smart transmitters” with computer compatibility. It has flexibility to meet existing analog and emerging
digital requirements. It offers the familiarity of an analog transmitter with built-in BRAIN or HART
(Highway Addressable Remote Transducer) capability digital smart communication. Remote calibration,
span changing, zero adjustment are also possible.
28 INDUSTRIAL INSTRUMENTATION
600
E-10.5
R = 0.0236
Digital
External communication
load range
resistance
250
R ()
Fig. 1.27 Relationship between power supply voltage and external load resistance
Though the input signal conditioning circuits are different for different inputs, the main amplifier,
output circuit and communication facilities are same. Hence a transmitter can be used for universal inputs.
When combined with the HART communicator, it permits program- ming input signals, spans, and
parameters through two-way communication.
1.4.9 Quantity Meters
Quantity meters are used for the measurement of low flow rates in industries. These meters operate
by passing the fluid to be measured through the meter in separate and distinct increments of alternately
filling and emptying containers of known capacity. The number of times the container is filled and emptied
gives the quantity of flow.
1.4.9.1 Positive Displacement Meters
Positive displacement type flow meters are generally used for accurate measurement of steady flow.
These flow meters are working under the following principle.
Positive displacement meters split the flow of liquids into separate known volumes based on the
physical dimensions of the meter, and count them or totalize them. They are mechani- cal meters in that one
or more moving parts, located in the flow stream, physically separate the fluid into increments. Energy to
drive these parts is extracted from the flow stream and shows up as pressure loss between the inlet and the
outlet of the meter. The general accuracy of these meters is dependent upon minimizing clearances between
the moving and stationary parts and maximizing the length of the flowing path. For this reason, accuracy
tends to in- crease as size increases.
FLOW 29
Disc
Ball
Inlet Outlet
small piston strokes are chosen with minimum of friction. Accuracy of this flow meter is within 0.5%.
Outlet
Piston
Slide valve
Inlet
Trapped liquid
A
A A
B B
B
Trapped liquid
Position A Position B Position C
Flow
Rotor
output signal that varies linearly with volumetric flow rate over specified flow ranges. The entire fluid to be
measured enters the flow meter, then passes through a rotor. The fluid passing through the rotor causes it to
turn with an angular velocity that is proportional to the fluid linear velocity. Therefore, the volumetric flow
rate is linear within the given limits of flow rate.
Let us consider a typical Turbine flow meter shown in Fig. 1.34, which consists of a multibladed
rotor (turbine wheel) which is mounted at right angles to the axis of the flowing fluid. The rotor is
supported by ball or sleeve bearings on a shaft which is retained in the flow meter housing by a shaft-
support. The rotor is rotating freely about its axis.
Pick-up coil
Alnico magnet
Working
opening through which the fluid must pass. This area is generally readout as the position of a float or
obstruction in the orifice.
The effective annular area in area meter is nearly proportional to height of the float, plummet or
piston, in the body and relationship between the height of float and flow rate is approximately linear one
with linear flow curve as well as scale graduations.
Types of Variable Area Flow Meters
Area meters are of two general types :
1. Rotameters and
2. Piston type meter.
Rotameters. In this meter, a weighted float or plummet contained in an upright ta- pered tube, is
lifted to the position of equilibrium between the downward force of the plummet and the upward force of
the fluid in addition to the buoyancy effect of the fluid flowing past the float through the annular orifice.
The flow rate can be read by observing the position of the float.
Piston Type Meter. In this meter, a piston is accurately fitted inside a sleeve and is lifted by
fluid pressure until sufficient post area in the sleeve is uncovered to permit the pas- sage of the flow. The
flow is indicated by the position of the piston.
Fig. 1.35 shows the types of Variable area flow meter (a) Rotameter and (b) Piston Type meter.
(a) (b)
Fig. 1.35 Types of Variable area flow meter (a) Rotameter (b) Piston Type meter
36 INDUSTRIAL INSTRUMENTATION
Performance Characteristics
1. Linearity. The flow rate (volume) through a variable area meter is essentially pro- portional to
the area and, as a result, most of these meters have essentially equal-scale incre- ments. A typical indicating
rotameters scale is non linear by about 5%.
2. Differential. An important characteristic of the variable area meter is that the pres- sure loss
across the float is a constant. The overall differential across the meter will increase at higher flow rates
because of friction losses through the fittings.
3. Accuracy. The most common accuracy is ±2% of full scale reading. This increases
considerably with individual calibration and scale length. Repeatability is excellent.
4. Capacity. Variable area flow meters are the most commonly used means for measur- ing low-
flow rates. Full scale capacities range from 0.5 cm3/min of water and 30 std cm3/min of air in the smallest
units to over 1200 litres/min of water and 1700 m3/h of air in 8 cm height meters.
5. Minimum Piping Requirement. An area meter usually can be installed without regard to
the fittings or lengths of straight pipe proceedings or following the meter.
6. Corrosive or Difficult to handle liquid. These can often be handled successfully in an
area meter. They include such materials as oil, tar, refrigerants, sulphuric acid, black liquor, beverages,
aqua regia and molten sulphur. In general, if the nature of the fluid does not permit the use of a
conventional differential pressure type meter because the fluid is dirty, viscous or corrosive, certain area
meters have an advantage over other types of meters.
7. Pressure Drop. By placing very light floats in over sized meters, flow rates can be handled
with a combination of very low pressure loss (often 2.5 cm of water column or less) and 10 : 1 flow range.
Basic Equations
The following flow equations are developed based primarily on liquids. However, the resultant
working equations can be used equally well on gas service.
The variable area meter shown in Fig. 1.36 consists of a tapered metering tube and a float which is
free to move up and down within the tube. The metering tube is mounted verti- cally with the small end at
the bottom. The fluid to be measured enters at the bottom of the tube, passes upward around the float, and
out at the top.
When there is no flow through the meter, the float rests at the bottom of the metering tube where the
maximum diameter of the float is approximately the same as the bore of the tube. When fluid enters the
metering tube, the buoyant effect of the fluid lightens the float, but it has a greater density than the liquid
and the buoyant effect is not sufficient to raise it. There is a small annular opening between the float and the
tube. The pressure drop across the float increases and raises the float to increase the area between the float
and tube until the upward hydraulic forces acting on it are balanced by its weight less buoyant force. The
meter- ing float is ‘floating’ in the fluid stream. The float moves up and down in the tube in proportion to
the fluid flow rate and the annular area between the float and the tube. It reaches a stable position in the
tube when the forces are in equilibrium.
FLOW 37
Glass tube
Guide wire
Float
I
Sharp edge creates
Spherical uniform turbulence
at both high and
low Reynolds numbers
Viscosity-insensitive
Float shapes
C-8\N-IND\BOOK1-3
38 INDUSTRIAL INSTRUMENTATION
where Q = Flow
A2 = Area at section-2
To allow for factors not included in this analysis, however, a factor Cd, called the coefficient of
discharge, is introduced. Then Equation (1.31) becomes
Q = CdA2V2 ...(1.32)
Neglecting V1 in Equation (1.29) and combining Equation (1.29) and (1.32), the expression becomes
Q = C dA 2 ...(1.32A)
2 g (P1
Dropping V1 from Equation (1.29) is justified onP2the
) basis that the area A1 >> A2, causing V1 << V2.
To express the flow in volumetric units, since q = Q/, Equation (1.33) becomes
q=C A 2 g (P1 P2 ) ...(1.32B)
d 2
where q = flow in volumetric unit.
From the force equation at equilibrium condition,
P1[Df2/4] + Vf = P2 [Df2/4] + Vf f ...(1.33)
where Df and f are the diameter and density of float
from the equation (1.33), P1 – P2 = Vf (f – ) [4/Df2] ...(1.33A)
by substituting P1 – P2, flow q can be calculated as
D p2 D f 2 gVf ( f ) µ 2 2 y
q = Cd D f2 ¡µ A2
4
(D p – D f ...(1.37)
¡J
Rotameter-Elements
The term “Rotameter” was derived from the fact that floats originally were produced with slots to
give them rotation for the purpose of centering and stabilizing the float.
The essential elements of any rotameter are listed as follows. In addition to suitable inlet and outlet
connections, they comprise (1) a metering tube and (2) a float.
1. Metering Tubes. In modern practice, they are formed on a mandrel and annealed to prevent
internal stresses so that strong, uniform tubes result. This method also permit the forming of tubes with
greater reproducibility and interchangeability and forming special shapes, such as non conical tubes with
curved elements designed to spread out the graduations at the lower end of the range. It is possible to
modify the conical form slightly in order to give the exact linear relationship between aperture and float
position which is not quite achieved with a purely conical tube.
The most important special shape is a modified conical section having internal beading or lands
which serve to guide the float. Fig. 1.37 shows some types of glass rotameter tubes with ribs or beads for
float guides.
FLOW 39
Float
Top of
tube
Bottom of
tube
Advantages
1. Low cost.
2. Low pressure drop.
3. Rangeability is better.
4. It is suitable for small flow rates.
5. It is easily equipped with alarms and switches or any transmitting devices.
6. It also measures the flow rate of corrosive fluids.
7. There is an availability of viscosity-immune floats.
8. It can be used in some light slurry services.
Disadvantages
1. It is difficult to handle the glass tube type.
2. It must be mounted vertically.
3. It is not suitable for pulsating services.
40 INDUSTRIAL INSTRUMENTATION
D d
Spiders t
Flow Pressure Annular
measuring orifice space
holes
Fig. 1.39 Annular orifice plate installation
Construction. The target meter combines in a single unit an annular orifice and a force-balance
transducer. Output is either an electric or pneumatic signal proportional to the square of the flow. Target
meters are available in sizes from 1/2 to 8 inch pipe diameter. The annular orifice is formed by a circular
disk supported in the center of a tubular section having the same diameter. Flow through the open ring
between disk and tube develops a force on the disk proportional to velocity head (the square of the flow).
The disk is mounted on a rod pass- ing out through a flexible seal. The force on the disk is measured from
the rod outside the seal, using a standard force-balance transducer integrally mounted on the flow tube.
Applications. The target meter is applied in a number of fields for measurement of liquids,
vapours and gases. It allows unimpeded flow of condensates and extraneous material along the bottom of a
pipe and at the same time allows unimpeded flow of gas or vapour along the top of the pipe.
FLOW 41
Impeller
Fluid path
Restraining spring
Housing
which deflects through an angle which is proportional to the torque exerted upon it by the fluid, thus giving
a measure of mass flow.
1.4.11.4 Twin-Turbine Mass Flow Meter
Another angular-momentum-type device is the twin turbine mass flow meter. In this instrument
two turbines are mounted on a common shaft.
Fig. 1.41 shows a twin-turbine mass flow meter in which two turbines are connected with a
calibration torsion member. A reluctance type pick up is mounted over each turbine and a strong magnet is
located in each turbine within the twin-turbine assembly.
Pickup 1 Pickup 2
Turbine 1 Turbine 2
T Flow
Flexible coupling
L
C
A
Fig. 1.42 Gyroscopic Mass Flow meter
The gyroscopic mass flow meter can handle slurries in the medium pressure and tem- perature
ranges but its industrial use is very limited due to its high cost and inability to handle high flow rates.
1.4.11.6 Coriolis Mass Flow Meter
1.4.11.6.1 Measuring Principle
The measuring principle is based on the controlled generation of Coriolis forces. These forces are
always present when both translational and rotational movements are superim- posed.
Fc 2 m ( v. ) ...(1.46)
where Fc = Coriolis force
m = moved mass
= angular velocity and
= radial velocity in the rotating or oscillating system.
v
FLOW 45
The amplitude of the Coriolis force depends on the moving mass m, its velocity v in the system
and thus on the mass flow. Instead of a constant angular velocity , Coriolis sensor uses oscillation. In
another [called promoss F d m] sensors, two parallel measuring tubes con- taining flowing fluid oscillator
in anti phase, acting like a tuning fork. The Coriolis forces produced at the measuring tubes cause a phase
shift in the tube oscillations. This principle is illustrated in Fig. 1.43.
At zero flow, in other words when the fluid is at a standstill, the two tubes oscillate in phase (1).
Mass flow causes deceleration of the oscillation at the inlet of the tubes (2) and acceleration at the outlet
(3).
The phase difference (A-B) increases with increasing mass flow. Electrodynamic sen- sors register
the tube oscillations at the inlet and outlet.
System balance is ensured by the anti phase oscillation.
A
B
1 2 3
Fig. 1.43 Coriolis principle
The classic Coriolis-type mass flow meter Fig. 1.44 consists of a centrifugal-pump impeller wheel
and a vaned sensing wheel which acts as a turbine wheel to extract the angular momen- tum imparted to the
fluid by the impeller.
The torque measured is that required to impart to the fluid stream a Coriolis accelera- tion, and is
given by the expression
= w (R22 – R12) (m/t) ...(1.47)
where R2, R1 = outer and inner radii.
1.4.11.6.3 Features
1. Balanced dual-type system for universal use in a wide range of process conditions.
2. High vibration immunity.
3. Compact design, occupying very little space.
4. Measurement is independent of fluid properties.
5. Hygienic design in accordance with the latest requirement.
6. Guaranteed product quality.
7. Robust field housing (aluminium or stainless steel).
8. High accuracy.
Liquids : ± 0.15%
Gases : ± 0.50%.
1.4.11.6.4 Advantages
1. It is obstruction less.
2. It is insensitive to viscosity, pressure and temperature.
3. It can handle clean liquids, mixed fluids, multiphase fluids, foams, slurries and liq- uids with
entrained gases.
4. This can be used for fluctuating flows.
1.4.11.7 Thermal Mass Flow Meters
1.4.11.7.1 Types of Thermal Mass Flow Meters
Thermal flow meters can be divided into two categories :
1. Flow meters that measure the rise in temperature of the fluid after a known amount of heat has
been added to it. They can be called heat transfer flow meters.
2. Flow meters that measure the effect of the flowing fluid on a hot body. These instru- ments are
sometimes called hot wire probes or heated-thermopile flow meters.
Both types of flow meters can be used to measure flow rates in terms of mass, a very desirable
measurement, especially on gas service.
1.4.11.7.2 Heat Transfer Flow Meters
The equation of the heat transfer flow meter is based on :
Q = W CP (T2 – T1) ...(1.48)
where Q = Heat transferred (Cal/hr)
W = Mass flow rate of fluid (kg m/hr) CP =
Specific heat of fluid (Cal/kg m °C)
FLOW 47
Flow
Film
Upstream
temperature
sensor
measures Tf Heater
supplies
Q Downstream
temperature
sensor
measures Tw
Fig. 1.46 Thermal flow meter with external elements and heater
In this type of construction the heat transfer mechanism becomes more complicated and the
relationship between mass flow and temperature difference becomes non-linear and to overcome this non-
linear relationship, heated tube type is introduced.
1.4.11.7.4 Heated Tube-Type Mass Flow Meter
Fig. 1.47 illustrates the non-linear shift in T in a heated-tube-type flow meter, where the
asymmetricity of the temperature distribution increases with flow.
Thermocouples
TC-1TC-2
Tube
Transformer
Zero flow
Temperature of tube
Small flow
TC-1
TC-2
L/2 0 L/2
Length of tube
Fig. 1.47 Heated tube-type mass flow meter
FLOW 49
In this type of flow meter, when a fluid flows in a pipe, a thin layer (film) exists between the main
body of the fluid and the pipe wall. When heat is passing through the pipe wall to the fluid, this layer resists
the flow of heat. If the heater is sufficiently insulated and if the piping material is a good conductor, the
heat transfer from the heater to the fluid can be expressed as
Q = hA (Tw – Tf) ...(1.50)
where h = film heat transfer coefficient
A = Area of pipe through which heat is passing Tw =
Temperature of wall
Tf = Temperature of fluid.
The film heat transfer coefficient ‘h’ can be defined in terms of fluid properties and tube
dimensions.
These types of flow meters are best suited for the measurement of homogeneous gases and are not
recommended for applications where the process fluid composition or moisture content is variable. In order
for these flow meters to be useful in a system, both the thermal conductivity and the specific heat of the
process fluid must be constant.
1.4.11.7.5 By Pass-Type Designs
In order to make the heat-transfer-type flow meter suitable for the measurement of larger flow
rates, the by pass designs have been introduced which is shown in Fig. 1.48.
The thermal flow meter tubes in these bypass units are small capillary tubes, usually under 3 mm
diameter. Their small size is advantageous in minimizing the electric power re- quirement and also in
increasing their speed of response, but it necessitates the use of up- stream filters to protect against
plugging.
Meter
Meter
Laminar flow
element
Bypass Bypass
line orifice
Main
orifice
Flow tube
A
110 V C
60 ~
Indicator, recorder
or controller
accepts a flow measurement signal from any volumetric flow meter. Based on these two in- puts, the
microprocessor–based transmitter generates an output signal, which relates to mass flow.
Radiation
type density
sensor
Indicator
transmitter
Mass flow
output
Volumetric
flow meter
Gamma
source Detector
Magnetic
field Field coil
Fig. 1.51 Mass Flow meter combining a magnetic flow meter and a radiation—type densitometer
in a single unit
These units are usually comprised of a magnetic flow meter and a gamma-radiation- based
densitometer, all in a single unit with a microcomputer. This mass flow unit does not require compensation
for changes in process variables and is installed as a single, obstructionless mass-flow sensor. Its features
and materials of construction are similar to those of a magnetic flow meter, except that it is bulkier and
more expensive, due to incorporation of the radiation- type densitometer. Because the flow sensor is a
magnetic flow meter, the unit is also limited to being used on process fluids having at least 3.0 S/cm
conductivity.
52 INDUSTRIAL INSTRUMENTATION
located diametrically opposite to each other with their surfaces flush with the inside surface of the lining, so
that they do not disturb the flow pattern.
Thus the electro magnet is of the core type and consists of two saddle shaped copper coils. This
flow tube is rigidly located in the air gap and the laminated iron core, for focussing the magnetic field in a
direction at right angles to the flowing liquid, being positioned beneath the coils. At alternating electric
supply is used to energize electro magnet as a.c. supply avoids polarisation of the electrodes.
Thus the emf across the electrodes will be directly proportional to the velocity of flows of the
metered liquid and it will not be influenced by variations in the specific resistance of the liquid if there is no
current flow through it. For this purpose null balance potentiometer is used. A simplified circuit is shown in
Fig. 1.52.
A.C. supply
Indicator
Electro magnet
Flow tube Amplifier
Electrode
Transformer
Slide wire Reversable servo-motor
Electro magnetMechanical link
Current transformer
Zero adjustment
the coils are not energized and to take a second measurement when the coils are energized and the magnetic
field has stabilized. Fig. 1.53 shows some of the types of excitation offered.
2T
t
Tr
Ts
Fig. 1.53 Types of pulsed DC Coil excitation
In all of the pulsed DC approaches, the concept is to take a measurement when the coils are excited
and store (hold) the information and then take a second measurement of the in- duced voltage when the
coils are not excited. The voltage induced when the coils are energized is a combination of both noise and
signal. The induced voltage when the coils are not energized is noise only. Subtracting the noise
measurement from the signal plus noise yields signal only which is illustrated in Fig. 1.54.
Flow
signal
S1
Noise
S2
t1 t2 t1
Magnet Magnet
ON OFF
Time
t1 Magnet "ON" signal sampling time During interval t1 :
t2 Magnet "OFF" signal sampling time Signal voltage = S1 + S2
S1 Flow signal During interval t2 :
S2 Noise voltage Signal voltage = S2
Subtracting :
(S1 + S2) – S2 = S1
(Flow signal only)
The pulsed DC-type systems establish zero during each on-off cycle. This occurs several times
every second. Because zero is known, the end result is that pulsed DC systems are potential percent-of-rate
systems.
The AC type systems must be periodically re-zeroed by stopping flow and maintaining a full pipe in
order to zero out any voltage present at that time. The noise voltage can change with time, resulting in a
potential offset. Therefore AC-type systems normally are percent-of- full scale systems.
1.5.1.3 Dual-Frequency Excitation
Changing the method of excitation from line frequency (AC) to low frequency (DC) pro- vided
dramatic improvements in both the accuracy and the zero stability of electromagnetic flow meters. A
limitation of low frequency (DC) designs is their relatively low speed of re- sponse (0.2—2 sec) and their
sensitivity to measurement noise caused by slurries or low con- ductivity fluids.
The idea behind dual-frequency excitation is to apply both and thereby benefit from both of their
advantages : The zero stability of low-frequency excitation and the good noise rejection and high speed of
response of high-frequency excitation. This is achieved by exciting the magnetic field coils by a current
with such a compound waveform as illustrated in Fig.
1.55. One component is a low-frequency waveform, much below 50 Hz, which guarantees good zero
stability. The output generated by the low-frequency signal is integrated via a long time constant to provide
a smooth and stable flow signal.
Low frequency
Electrodes sampling Integrating circuit
+ Output
Magnetic Differentiating
flowmeter circuit
Magnet High
coil frequency
Low frequency sampling
Dual frequency
excitation
High frequency
Magnet coils
Meter electrode
Meter pipe Laminated
section iron core
voltage in the liquid ; the amplitude of the Fig. 1.56 Cutaway view of Electromagnetic flow meter
voltage is directly proportional to the liquid velocity. This voltage is conducted by the elec- trodes to a
separate converter which in effect is a precision voltmeter capable of accurately measuring the voltage
generated and converting that voltage to the desired control signals. These may be equivalent electronic
analog signals, typically (4-20) mA DC, or a frequency or scaled pulse output.
1.5.1.5 Limitations of electromagnetic Flow Meters
(a) The substance being measured must be conductive. Therefore, it can’t be employed for
metering the flow rate of gases and steam, petroleum products and similar liquids having very low
conductivity.
(b) To render the meter insensitive to variations in the resistance of liquid, the effective resistance
of the liquid between the electrodes should not exceed 1% of the impedance of the external circuit.
(c) It is a very expensive device.
(d) As the meter always measures the volume rate, the volume of any suspended matter in the
liquid will be included.
(e) To avoid any trouble which would be caused by entrained air, when the flow tube is installed in
a horizontal pipe-line, the electrodes should be on the horizontal diameter.
FLOW 57
(f) As a zero check on the installation can be performed only by stopping the flow, isolating valves
are required and a bypass may also be necessary through which the flow may be directed during a zero
check.
(g) The pipe must run full, in case regulating valves are installed upstream of the meter.
1.5.1.6 Advantages of Electromagnetic Flow Meter
(a) The obstruction to the flow is almost nil and therefore this type of meters can be used for
measuring heavy suspensions, including mud, sewage and wood pulp.
(b) There is no pressure head loss in this type of flow meter other than that of the length of straight
pipe which the meter occupies.
(c) They are not very much affected by upstream flow disturbances.
(d) They are practically unaffected by variation in density, viscosity, pressure and tem- perature.
(e) Electric power requirements can be low (15 or 20 W), particularly with pulsed DC-
types.
(f) These meters can be used as bidirectional meters.
(g) The meters are suitable for most acids, bases, water and aqueous solutions because the lining
materials selected are not only good electrical insulators but also are corrosion- resistant.
(h) The meters are widely used for slurry services not only because they are obstruction less but
also because some of the liners such as polyurethane, neoprene and rubber have good abrasion or erosion
resistance.
(i) They are capable of handling extremely low flows.
1.5.1.7 Disadvantages of EM Flow Meter
(a) These meters can be used only for fluids which have reasonable electrical conductivity.
(b) Accuracy is only in the range of ± 1% over a flow rate range of 5%.
(c) The size and cost of the field coils and circuitry do not increase in proportion to their size of
pipe bore. Consequently small size meters are bulky and expensive.
1.5.1.8 Applications of EM Flow Meters
This electromagnetic flow meter being non intrusive type, can be used in general for any fluid
which is having a reasonable electrical conductivity above 10 microsiemens/cm. Fluids like sand water
slurry, coal powder, slurry, sewage, wood pulp, chemicals, water other than distilled water in large pipe
lines, hot fluids, high viscous fluids specially in food processing industries, cryogenic fluids can be
metered by the electromagnetic flow meter.
1.5.2 Ultrasonic Flow Meters
1.5.2.1 Introduction
Pressure variations travel through a fluid at the velocity of sound relative to the fluid. If fluid is in
motion with certain velocity, then the absolute velocity of pressure disturbance propagation is the algebraic
sum of the two. The term ‘ultrasonic’ refers to the pressure differ- ences (usually are short bursts of sine
waves) whose frequency is above the range audible to human hearing which is 20 to 20000 Hz.
C-8\N-IND\BOOK1-4
58 INDUSTRIAL INSTRUMENTATION
1.5.2.2. Principle
The ultrasonic flow meter operates on the principle that the velocity of sound in a fluid in motion is
the resultant of the velocity of sound in the fluid at rest plus or minus the velocity of the fluid itself.
1.5.2.3 Types of Ultrasonic Flow Meters
(i) Transit time flow meters
(ii) Doppler Flow meter.
1.5.2.3.1 Transit Time Flow Meters
As the name implies, these devices measure flow by measuring the time taken for an ultrasonic
energy pulse to traverse a pipe section, both with and against the flow of the liquid within the pipe. Fig.
1.57 shows a representative transit time flow meter.
Transducer B
Flanged
Flanged
end
end
V L
Transducer A
Fig. 1.57 Transit-time flow meter
The time (tAB) for the ultrasonic energy to go from transducer A to transducer B is given by the
expression :
tAB = L/(C + V. cos ) ...(1.56)
The time (tBA) to go from B to A is given by
tBA = L/(C – V.cos ) ...(1.57)
where C is the speed of sound in the fluid
L is the acoustic path length in the fluid
and is the angle of the path with respect to the pipe axis.
By combining and simplifying, it can be shown that for V << C :
t = tBA – tAB = 2.L.V. cos /C2 ...(1.58)
It can be shown that :
V = L.t/2 cos tA2 = K t/tA2 ...(1.59)
where tA is the average transit time between the transducers.
Since the cross sectional area of the pipe section or ‘spool pipe’ is known, the product of area and
velocity will yield the volumetric flow rate.
FLOW 59
Alignment
hardware
Existing pipe
meter relies upon an ultrasonic signal traversing across the pipe ; therefore, the liquid must be relatively
free of solids and air bubbles. Bubbles in the flow stream generally cause more attenuation than solids and
so the flow meter can tolerate a large percentage of solids than bubbles.
Depending on the process fluid, proper transducer materials and protection must be chosen to
prevent transducer damage due to chemical action. Process temperature limitations must also be considered
for proper flow meter application.
Accuracy for a simple path flow meter is around 1 to 2% of rate depending upon design, velocity,
pipe size and process. Repeatability is typically about 0.5% depending upon velocity range and calibration.
To improve performance and accuracy for larger pipe sizes, some suppliers offer flow meters with
two, four or more pairs of transducers arranged to interrogate multiple acoustic paths. The cost of such
units is higher than that of a single path flow meter.
1.5.2.6 Doppler Flow Meters
This type of flow meter is based on Doppler principle. The transmitter of a Doppler flow meter
projects an ultrasonic beam at a frequency of about 0.5 MHz into the flowing stream and deflects the
reflected frequency. The difference between transmitted and reflected velocities is called the ‘beat
frequency’ and is related to the velocity of the reflecting surfaces (solid parti- cles and gas bubbles) in the
process stream.
1.5.2.6.1 Principle of Operation
As shown in Fig. 1.59, an ultrasonic wave is projected at an angle through the pipe wall into the
liquid by a transmitting crystal in a transducer mounted outside the pipe. Part of the energy is reflected by
bubbles or particles in the liquid and is returned through the pipe wall to a receiving crystal. If the reflectors
are travelling at the fluid velocity, the frequency of the reflected wave is shifted according to the Doppler
principle, in proportion to the flow velocity.
CT
Combining Snell’s law and Doppler equation, the flow velocity can be determined as follows if V <<
C.
V = f.Ct/(2.fo . cos ) = f.K ...(1.61)
where f = Difference between transmitted and received frequency.
fo = frequency of transmission
= angle of the transmitter and receiver crystal with respect to the pipe axis
Ct = Velocity of sound in the transducer.
As shown in equation (1.61), velocity is a linear function of f. Since the inside diameter (ID) of the
pipe is known, volumetric flow rate can be measured as a function of V and square of ID
Volumetric flow rate (Q) V.(ID)2 ...(1.62)
1.5.2.6.2 Construction
In the single transducer design, both the transmitter and receiver crystals are con- tained in a single
transducer assembly which is to be mounted on the pipeline. Alignment of the crystal is thus controlled by
the manufacturer. This approach is shown in Fig. 1.59.
In dual transducer design, the transmitter crystal and the receiver crystal are mounted separately on
opposite sides of the outside of the pipe. Alignment is maintained by a mounting assembly that maintains
the relative positions of the transducers as shown in Fig. 1.60.
A Doppler flow meter relies upon reflectors in the flow stream to reflect ultrasonic energy. There is
a lower limit for the concentration and size of solids or bubbles in the liquid that will give reliable, accurate
operation. The flow must be fast enough to keep the solids or bubbles in suspension.
The Doppler flow meters will operate independently of pipe material provided the pipe is sonically
conductive. Such pipes as concrete, clay and very porus cast iron absorb the ultrasonic energy and are not
suited for Doppler-type flow metering.
The maximum operating temperatures is about 100°C. The inaccuracy or error of the Doppler type
flow meter is about 3% of span. The error does vary with flow velocity, pipe size and flow meter
calibration. Repeatability is about 1% of full span.
1.5.3 Laser Doppler Anemometer Systems
Anemometers are used to measure air and gas flows in a variety of applications.
1.5.3.1 Principle of Operation
When sound or light is beamed into the atmosphere, the inhomogeneities in the air will reflect these
beams. The resulting Doppler shift in the returning frequencies can be inter- preted as an indication of
wind velocity.
1.5.3.2 Working
When laser-based Doppler anemometers are used, the intensity of the light scattered by the particles
in the air is a function of their refractive index and the size of the reflecting particles.
The Laser Doppler anemometer (LDA) is based on the Doppler effect. The Doppler shift of
frequency occurs as light is dispersed on the surface of moving particles. The shift in the frequency of the
light source (laser beam) is proportional to the velocity of the particles. The frequency shift is very small
(from 1 KHz upto a tenth of a MHz) in comparison with the light frequency and thus it can be directly
measured. Therefore, the arrangement using the inter- ference of the original and refracted lights is used.
This is called as ‘differential mode’ of LDA. Fig. 1.61 illustrates the LDA Principle.
The frequency ‘f ’ of electrical signals produced by a particle moving with velocity ‘V’ is given by
2 V sin / 2 µ 2 sin / 2 y V
f ¡ ¡
f = KV
µ J
where = Laser wavelength and = angle of the beam.
Beams from the laser source intersect each other in the measurement zone, where a set of
interference plates are formed. When particles pass through these, they generate optical signals with flash
frequencies which equal the Doppler frequency. This signal is scanned by the photo multiplier and is
analysed. The signal has several cycles, variable amplitude, and high frequency and background noise.
1.5.3.3 Applications
The use of this non contact measurement method is suitable for nearly all hydro dynamical and
aero dynamical velocity measurement applications.
FLOW 63
Photomultiplier V
Stop
Measuring
zone 125 m
V
Laser Lenses
assembly
Refracting Lens
prism
End fitting
Tube adaptor
Protection shield
Metering tube
Float
Tube adaptor
End fitting
Needle
valve
Meter body
The metering needle valves are usually multiple-turn units provided with long stems. The opening
around their needle-shaped plugs can approach capillary dimensions. The flow rate through these devices
is a function of not only the opening of the valve and the pressure differential across it, but also of both the
density and the viscosity of the purge media.
When the purge flow meter is combined with a differential pressure regulator, it be- comes a self-
contained flow controller which is illustrated in Fig. 1.63.
By adjusting springs #1 and #2 for a constant pressure difference of about 1.5 to 2 m of water, this
constant pressure drop (Pi – P0) is maintained across the flow control valve (V) and the purge flow is
thereby fixed. Fig. 1.63 describes a configuration in which the outlet pressure (P0) is constant and the inlet
pressure Pi is variable. Units are also available for bubbler and purge applications where the inlet pressure
Pi is constant and the outlet P0 is variable. In that case the constant pressure drop across the valve (V) is
maintained to equal (Pi – P0).
FLOW 65
Flow P0
outlet pressure
Tube
Spring 1
Diaphragm Float
Pi
Regulator
valve Flow control
valve (V)
Spring 2
Flow P inlet pressure
Fig. 1.63 Purge flow regulator consisting of a glass tube rotameter, and inlet needle valve, and
a differential pressure regulator
1.6.1.3 Applications
Purge flow controllers on gas service are usually provided with an accuracy of 5% full scale over a
range of 10 : 1.
1.6.2 Cross Correlation Flow Meter
1.6.2.1 Introduction
The oldest and simplest methods of flow measurement are the various tagging techniquies. Here a
portion of the flow stream is tagged at some upstream point and the flow rate is determined as a
measurement of transmit time. Variation of this technique include particle tracking, pulse tracking, dye or
chemical tracing, including the radioactive types.
1.6.2.2 Working Principle
Flow metering based on correlation techniques is similar in concept to the tagging or tracing
techniques because it also detects transit time. As illustrated in Fig. 1.64, any measur- able process variable
which is noisy can be used to build a correlating flow meter. The only requirement is that the noisy pattern
must persist long enough to be seen by both detectors ‘A’ and ‘B’ as the flowing stream travels down the
pipe. Flow velocity is obtained by dividing the distance between the identical pair of detectors by the transit
time.
The following process variables display persistent-enough noise patterns or fluctuations so that
cross-correlation flow meters can be built by using an identical pair of these sensors : Density, Pressure,
Temperature, Ultrasonics, Gamma radiation, Capacitive density and Conductivity. Several of the above
process variables such as temperature, gamma radiation and capacitive density have been investigated as
potential sensors for correlation flow meters.
66 INDUSTRIAL INSTRUMENTATION
One instrument has been developed utilizing the principle of ultrasonics cross-correlation to measure heavy
water flow. Others are available for paper pulp application using photometric sensors and for solids flow
measurements utilizing capacitance detectors.
m(t)
“A”
Upstream 20.4"
m(t) transducer (52 mm)
signal
Time t
Transit
time
T 10 to 20 × dia. (internal) inlet run
Downstream
transducer
n(t) “B” signal
Time t
Fig. 1.64 Cross-correlation flow metering Fig. 1.65 Installation requirements of cross-
correlation type solids flow meter
Fig. 1.65 shows installation requirements of cross-correlation type solids flow meter. When fully
developed, correlation flow metering can extend the ability to measure the flow not only into the most
hostile process environments, but also into areas of multiphase flow.
1.6.2.3 Advantages
The advantages of tagging techniques include the ability to measure the velocity of only one
component in a multi component flow stream without requiring calibration.
1.6.2.4 Applications
The applications of the cross-correlation flow meter include pumped paper pulp, pneu- matically
conveyed coal dust, cement, grain, plastic granules, chalk and chemical food stuffs.
FLOW 67
Inlet chute
Control gate
valve supply pressure vary, this feeder cannot maintain set gravimetric rate if the bulk den- sity of the
solids varies.
It should be noted that the basic principle involving the weighing of the entire feeder has been
applied in modern designs. Successful operation of these versions has been achieved by adding belt load
error detecting instrumentation and by actuating the control gate from an external power source. A
controller with reset function eliminates the set point error.
1.6.3.3 Belt Type Electromechanical Gravimetric Feeder
Fig. 1.67 describes the basic construction of the electromechanical gravimetric feeder. Here the belt
load is balanced by a mechanical beam and poise weight system which energizes one or other of two
clutches via a pair of mercury switches energized by a magnet attached to the beam. These clutches actuate
and establish the direction of travel of the gate-positioning
Gate actuator
and clutch unit Magnet-mercury switch
Belt load
belt load error detector
(Lowers gate) setpoint
(Raises gate) indicator
Rate setting
poise weight
Belt travel
totalizer
Belt drive Flexure supported
weigh decks
Output to
remote indicator
recorder or controller
Air supply
Pneumatic
relay
Balancing
piston
Flapper
and
nozzle
Tare weight
Belt drive
Another method of rate adjustment utilizes belt speed variation with belt load as con- trolled
constant. Still another involves variation of both belt speed and belt load wherein the rate signal is the
multiplicand of the belt speed and belt load measurement signals generated by the feeder.
1.6.4 Vortex Shedding Flow Meter
1.6.4.1 Vortex Shedding Phenomenon
When an obstruction (a non-streamlined object) is placed in the path of a flowing stream, the fluid is
unable to remain attached to the object on its downstream sides and will alter- nately separate (shed) from
one side and then the other. The slow-moving fluid in the bound- ary layer on the body becomes detached
on the downstream side and rolls into eddies and vortices,. Fig. 1.69. It is also noted that the distance
between the shed vortices is constant, regardless of flow velocity. This principle is called as Karman’s
principle.
d
V
ID
l
The distance between the Karman vortices (I) is only a function of the width of the obstruction (d)
and therefore the number of vortices per unit of time gives flow velocity (V).
Thermistor sensor
Flow
Other design modifications aim at compensating for background noise by using two detectors, of
which one is exposed to vortex forces and the other is not, and using their differ- ence as the measurement
signal.
Oscillator
preamplifier
Vortex generating strut
Fixed vortex Receiver
Thermistor generating strut
sensors
The meter’s good accuracy and digital linear output signal make its application over wide flow
ranges a practical proposition. The rangeability declines proportionally with in- creases in viscosity and
decreases in density, or reductions in the maximum flow velocity of the process. Vortex shedding meters
are therefore unsuitable for use of high-viscosity liquids.
1.6.5 Flow Switches
Flow switches are used to determine whether the flow rate is above or below a certain value. This
value (set point) can be fixed or adjustable. When the set point is reached, the response can be the
actuation of an electric or pneumatic circuit. When the flow switch is actuated, it will stay in that condition
until the flow rate moves back from the set point by some amount. This difference between the ‘set point’
and the ‘reactivation point’ is called the switch ‘differential’. The differential can be fixed or adjustable. If
the differential is small, the switch is likely to cycles it control circuit as the flow actuates around its set
point.
In certain applications, a manual reset feature is desirable. This will guarantee that once the switch
is actuated, it will not be allowed to return to its preactuation state until manually reset by the operator. This
feature is designed to require the operator to review and eliminate the cause of the abnormal flow condition
before resetting the switch variations.
1.6.5.1 Design Variations
1.6.5.1.1 Folding Paddle Switch
The least expensive and therefore the most widely used
are the various paddle type devices. One such device is illustrated
in Fig. 1.72. At ‘no flow’ the paddle hangs loosely in the pipe in
which it is installed. As flow is initi- ated, the paddle begins to
swing upward in the direction of the flow stream. This deflection
of the paddle is trans- lated into mechanical motion by a variety
of techniques including a pivoting cam, a flexure type, or a
bellows as- sembly. The mechanical motion causes the switch to
open or close. If a mercury switch is used, the mechanical mo-
tion drives a magnetic sleeve into the field of a permanent magnet
which trips the switch. A hermetically sealed switch will be
directly actuated by the permanent magnet as it moves up or
down according to the paddle movement. If a micro switch is
used, the translated motion will cause
direct switch actuation. The range and actuation point of paddle
switches can be changed and adjusted by changing
the length of the paddle. For any given pipe size, the ac- tuation Fig. 1.72 Folding paddle switch
flow rate decreases as the paddle length increases.
Paddle-type flow switches are sensitive to pipeline turbulence, pipeline variation and installation.
For these reasons, it is advisable to provide them with the equivalent of a 10 pipe diameter straight
upstream run, to use dampers if pipe vibration or pulsating flow is expected, and to readjust their settings if
they are to be mounted in vertical upward flow lines. The conventional paddle-type designs are incapable of
distinguishing low flow velocities from no- flow conditions. Therefore, if low flows are to be detected, the
folding circular paddle should be
74 INDUSTRIAL INSTRUMENTATION
used, which permits the full diameter paddle to fold back upon itself, to minimize pressure drop.
1.6.5.1.2 Swinging Vane Design
In smaller sized pipelines where it is desired to provide local flow indication, in addition to the flow
switch action, the variable area type flow switches can be considered. If the vertical upward flow
configuration of the rotameter design is not convenient from a piping layout point of view, the circular,
swinging vane design, shown in Fig. 1.73 can be considered.
PVC facing
both in the flow through and in the probe configuration. One design consists of a heater probe and two
sensor probes, connected in a wheatstone bridge. When the flow stops, an imbalance in the bridge circuit
occurs.
Resistance
temp, sensor
Pipeline
Active
sensor
Warm
convection
current carries
heat from the
heater to the
active sensor
Heater
Reference
sensor
Spring
Flow
Permanent
magnet Differential pressure
producing vane
externally adjustable
A bypass-type switch shown in Fig. 1.76 has an externally adjustable vane that creates a differential
pressure in the flow stream. This differential pressure forces a proportional flow through the tubing that
bypasses the vane. A piston retained by a spring is in the bypass tubing and will move laterally as flow
increases or decreases ; the piston’s movement activates a switch. Bypass flow switches can be used for
fairly low flow rates and their ability to be externally adjusted is a desirable feature.
1.6.6 Anemometers
The use of hot wire resistance transducer is to measure the flow rate of fluids by means of
measuring velocity of non conducting liquids. In open channels and closed pipes it can be conveniently
measured by suitably locating the hot wire filament.
1.6.6.1 Hot Wire Filament
Hot wire filament is usually made by wire of platinum or tungsten material. It is suit- ably mounted
in the flow channel by means of a support as shown in Fig. 1.77. The diameter of the wire may vary from 5
m to 300 m and the length is about half the diameter of the pipe. A smaller diameter gives a larger
resistance per unit length and less inertia but is also less capable of sustaining large fluid pressure. The
capability of its withstanding large pressure shocks is decided after actual testing. The hot wire element is
centrally located inside the pipe such that the axis of the wire is normal to the direction of fluid flow.
Hot wire filament
In Out
Flow pipe
1.6.6.2 Principle
In hot wire anemometers, the filament is heated initially by means of passing an elec- tric current.
This heated resistive filament mounted on a tube is exposed to air flow or wind, which is cooled because of
fanning effect. Depending on the velocity of air flow, the amount of cooling varies. The resistance of the
probe when it is hot is different from that when it is cooled. This difference in resistance or this variation in
resistance is converted into a voltage variation and thereby the flow velocity is converted into a voltage
variation.
C-8\N-IND\BOOK1-5
FLOW 77
connected to a battery voltage source in series with an adjustable resistor of a very large value (2K). The
voltage drop across the hot wire filament is measured by a high resistance millivoltmeter whenever the
bridge is brought to balance condition.
DC
amplifier
R1 R2
Rs
Rw R3
50
1.7.1 Introduction
Flow rate calibration depends on standards of volume and time or mass and time. Pri- mary
calibration is generally based on the establishment of steady flow through the flow meter to be calibrated
and subsequent measurement of the volume or mass of the flowing fluid that passes through in an accurate
time interval. If steady flow exists, the volume or mass flow rate may be inferred from such a procedure. As
in any other calibration, significant deviations of the conditions of use from those at calibration will
invalidate the calibration. Possible sources of error in flow meters include variations in fluid properties
(density, viscosity and tempera- ture), orientation of meter, pressure level, flow disturbance (such as
elbows, tees, valves etc) upstream to the meter.
1.7.2 Methods of Calibration of Flow Meter With Liquids
1.7.2.1 Dynamic Weighing (Gravimetric) Method
A commercial calibrator for precise primary calibration of flow meters using liquids is shown in
Fig. 1.83. These units use a convenient dynamic weighing scheme, and are available in different models to
cover the range from 0.5 to 70,000 kg/hr and have an overall accuracy of
± 0.1%. The sequence of the calibration procedure is explained below :
(a) Running operation before Test : Fig. 1.83(a)
Fluid contained in the reservoir is pumped through a closed hydraulic circuit. First, it enters the
filter and then the heat exchanger equipment, which controls temperature within
20°C. It then passes through the control valves, the meter under test, the back pressure valve, the weigh
tank, and then back into the reservoir.
Actuator
dump valve
Timer
Weigh
Back pressure beam
Control valve
Timer
Flow meter
being tested Actuator
Flow control
Heat exchanger
Filter
Pump
Reservoir
Fig. 1.83 (a)
82 INDUSTRIAL INSTRUMENTATION
Back pressure
Control valve Weigh
beam
Flow meter
being tested
Timer
Actuator
Flow control
Heat exchanger Tare weight
Filter
pump
Reservoir
Fig. 1.83 (b)
Weigh
Back pressure beam
Control valve
Timer
Flow meter Actuator
being tested
Flow control
Heat exchanger
Filter Dump valve
pump
Reservoir
Fig. 1.83 (c)
As the weigh tank fills, the weigh pan rises, tripping the timer actuator, and the electronic timer
begins counting in milliseconds, starting the actual weighing cycle. The preliminary fill balanced out by the
tare weight before actual weighing begins, permits a net measurement of
FLOW 83
the new fluid added after preliminary fill. The preliminary fill method permits the measurement of only a
portion of the cycle, eliminating the mechanical errors in the start and stop portions and allowing dynamic
errors to be self cancelling.
(d) Weighing cycle in Operation : Fig. 1.83(d)
The weighing cycle is continued as a precision weight is placed on the weigh pan, again deflecting
the beam. The uniquely designed cone shaped deflector at the inlet of the weigh tank permits the even
distribution of measured fluid.
Actuator
dump valve
Timer
Back pressure
Weigh
Control valve beam
Flow meter Timer
being tested Actuator
Precision
Flow control test weight
Heat exchanger
Filter
Dump valve
pump
Reservoir
Fig. 1.83 (d)
Weigh
Back pressure beam
Control valve
Timer
Flow meter Actuator
being tested
Flow control
Heat exchanger
Filter Dump valve
pump
Reservoir
Fig. 1.83 (e)
84 INDUSTRIAL INSTRUMENTATION
As the tank fills, the weigh pan rises, until it again trips the timer actuator, stopping the timer and
the indicating the time within a thousandth of a second. By combining the precision test weight with the
timed interval, the actual flow rate in kg/hr is easily and accu- rately determined. From these basic mass
units, other flow units can be accurately calculated.
(f) Emptying for Recycling : Fig. 1.83(f)
After the beam movement trips the timer, the weigh tank automatically empties in less than 25
seconds, even at maximum flow. The calibrator is now ready for the next flow setting. This fast recycling
cuts total calibrating time as much as 50%.
Actuator
dump valve
Timer
Weigh
Back pressure beam
Control valve
Flow control
Heat exchanger
Filter
pump
Reservoir
Fig. 1.83 (f)
through the prover either from left to right or from right to left. At either end of the prover there is a chamber
of enlarged diameter to receive the sphere at the end of each trip.
Hinged
closure Spring
buffer Sphere
Detector 2
Calibrated volume
Block-and-bleed
valve
Signal
cable
4-way
diverter
valve
Detector 1
Meter on
test
Flow
Fig. 1.84 Principle of the bidirectional pipe prover
Before starting the calibration run, the flow is allowed to by-pass the prover. At the start of a test,
the flow is directed through the prover in such a way that the sphere travels the whole length of the prover.
Soon after the start of its run, it passes a sphere detector, which operates an electrical gating circuit and
causes the electrical pulse from the meter on test to be counted. Near the end of the run, a second sphere
detector is operated which stops the count of pulses. The pulse count from the meter is then compared with
the known volume of the prover between sphere detectors, which has been determined from a previous
static calibration of the prover. Additional accuracy is gained by totalising the pulse counts and the prover
volumes during two successive runs one in each direction. Directional effects in the sphere detectors are
thus largely cancelled out.
The accuracy of the bidirectional prover is as high as ± 0.1% of flow rate and between
0.05 and 0.02% on total volume.
1.7.2.3 Master Meters Method
The simplest and cheapest way of calibrating a flow meter is to put it in series with another flow
meter of higher accuracy and to compare their readings. This can give reasonably accurate results over a
short period, provided that care is taken to install the two meters sufficiently far apart to ensure that the
downstream meter is not affected by the presence of the upstream meter. A serious disadvantage of the
method is that the performance of the master meter will gradually change with time ; consequently,
recalibration of the master meter will be needed at intervals.
86 INDUSTRIAL INSTRUMENTATION
Also if the master meter should suffer any kind of sudden mechanical wear, its perform- ance could
change in a very short period without the operator being aware of the fact. As a safeguard against this
happening, it is possible to use two master meters in series as shown in Fig. 1.85.
Master meter 1 Master meter 2 Meter on test
Flow
compare the performances of the two master meters. One master is used as the main calibra- tion device,
while the other master meter as a ‘super master meter,’ being used alternately with the first master meter on
infrequent occasions as a check that the master meter, remains unchanged. As soon as a change in the
performance of the master meter is observed it is removed for recalibration. When it is fitted back after
recalibration it is regarded as the super master meter, while the other meter becomes the master meter. This
situation remains until another recalibration is called for, when the roles of the two meters are again
reversed.
A well maintained master meter calibration system should provide accuracies of ± 0.2% on flow
rate and ± 0.1% or ± 0.5% on volume.
1.7.3 Methods of Calibrating Flow Meters With Gases
1.7.3.1 Soap Film Burettes
It is suitable only for low flow rates, since it is difficult to form a stable soap film across a burette of
more than about 50 mm diameter. The film is made to act as a frictionless ‘piston’ which travels freely with
the flowing stream of gas, so that the velocity of the film is a good indication of the velocity of the flowing
gas. Fig. 1.87.
Detector
Flow
Meter on test
Detector
Timer
Rubber bulb
Soap solution
Pulley
Cylinder
Gas
Counter weights
Meter on test
Fig. 1.88 Simplified schematic arrangement of bell prover system for calibrating small gas quan-
tity meters
Flow
25d D 8°
R = 2d
Fig. 1.89 Standard sonic venturi-nozzle
FLOW 89
It depends upon the fact that in the throat of a nozzle, the gas cannot travel faster than the speed of
sound. Provided the upstream pressure is sufficient to ensure that sonic velocity is actually reached, the
flow rate through the nozzle will therefore always have a fixed value for a given gas at a specified
temperature and pressure. The tapered section of the nozzle plays no part in controlling the flow rate ; its
function is merely to assist, in recovering some 90-95% of the initial pressure, thus conserving energy.
If a number of sonic venturi nozzles of various sizes are used in succession a gas flow meter can be
calibrated over a range of flow rates with them. When the highest possible accu- racies (about ± 0.5% on
flow rate) are called for it is usual for venturi—nozzles to be calibrated against a primary gas flow standard
before they are used as calibration devices. If slightly lower accuracies are acceptable their performance
can be predicted fairly reliably from a knowl- edge of their dimensions.
1.7.3.4 Gravimetric System for Gas-Meter Calibrator
The gravimetric calibration is a highly sophisticated and expensive device, but is regarded as the
best available primary system for calibrating secondary high-pressure gas flow standards. It can also be
used directly for the calibration of high-pressure gas meters. It is broadly similar in principle to the
gravimetric system with static weighing for liquids, but with one important difference. In the liquid system
the meter being calibrated is at upstream of the flow diverted, but in the gas system it is at downstream and
in a line venting to atmosphere. This enables the meter to be read under steady-state conditions, thus
overcoming the problem of diminishing flow rate, which occurs while the weighing vessel is being filled.
Diverter unit
Critical venturi-nozzle Meter on test
Ball valves
Inlet
(at constant
P and T)
Flow control valve
Disconnecting union
Weighing vessel
Weighbridge
flow rate during the diversion period. By varying the pressure upstream of the critical venturi- nozzle, a
fairly wide range of mass flow rates can be covered with this system, and by using several alternative
nozzles of different sizes, an almost unlimited range can be covered.
The accuracy of flow rate measurement in a system of this kind is between ± 0.5% and ± 0.2%.
1.7.3.5 PVT System
The PVT (Pressure-Volume-Temperature) method illustrated in Fig. 1.91 is used mainly as a
primary standard, to calibrate reference meters and sonic venturi nozzles which can there- after be used as
secondary calibration devices.
In this system, a storage vessel of known volume is charged with gas at high pressure. The pressure
and temperature of the gas in the vessel are first measured, then the gas is allowed to flow out through a
regulating sonic nozzle in series with the meter on test, and finally the pressure and temperature of the gas
in the storage vessel are measured again at the end of a measured period of time.
Temperature
measurement Pressure
measurement
Heat exchanger
selection based on the availability of flow meter and draw out a complete specification of the flow metering
application.
1.8.1 Factors to be Considered
There are many factors which are to be considered before drawing up specifications for a flow
meter. They are :
1. Measurement requirements
2. External conditions of the flow pipe
3. Internal conditions of the flow pipe
4. Properties of the flowing fluid
5. Installation and accessories and
6. Cost consideration.
Let us examine the above six factors in detail.
1.8.1.1 Measurement Requirements
The requirements of measurement can be addressed based on.
(a) The measured variable like point velocity, average velocity or volume rate.
(b) The range of operation. For wide range of operation, electromagnetic, ultrasonic, cross-
correlation, turbine type etc. are suitable.
(c) Cost computation. If it is for costing purpose, the meter should have low and consistent
uncertainty in measurement.
(d) Pressure head loss and maximum pressure of flowing fluid. For high pres-
sure fluids the meter body and inner construction should be sturdy.
(e) Accuracy, Precision and facilities available for maintenance.
(f) Speed of response. For fluctuating flow, response of the meter should be good with small
time constants.
(g) Calibration facilities and Installation.
1.8.1.2 External Conditions of the Flow Pipe
Before selection of a flow meter, it is important to examine the environment and the place where the
meter is going to get installed. The following points need to be considered.
(a) Approachability. It is better to know that once the meter is installed whether it is
accessible for removal, recalibration etc.
(b) It is important to note that the installation of the meter either in an air conditioned space or in a
place which is vulnerable for wide temperature variation.
(c) Humidity condition, vibration, hostile environment and water facility are the im- portant
parameters to be considered.
1.8.1.3 Conditions Internal to the Flow Pipe
The conditions internal to the pipe affect the accuracy of measurement of flow meters. Some of the
factors that affect the accuracy are protrusions, pipe bore, size, roundness, tough- ness, hydrodynamic noise
pulsations etc.
92 INDUSTRIAL INSTRUMENTATION
1. ORIFICE ± 2.0%
2. VENTURI ± 1.0%
3. NOZZLE ± 1.5%
4. PITOT ± 0.5%
5. EM ± 0.5%
6. UF ± 1.0%
7. CC ± 0.5%
8. VS ± 1.0%
9. ROTAMETER ± 2.0%
10. HOTWIRE ± 2.0%
11. GILFLOW ± 1.0%
12. NMR ± 0.5%
13. LDU ± 0.05%
14. PD ± 0.1%
15. TURBINE ± 2.0%
16. MASSFLOW ± 1.0%
C-8\N-IND\BOOK1-5
94 INDUSTRIAL INSTRUMENTATION
Range 5 : 1 to 12 : 1 4:1 10 : 1 to 15 : 1 10 : 1
Maximum 1 – 10 m 3 – 60 m 10 – 40 m Negligible
overall of of of
Pr. Loss H2O H2O H2O
Immunity Immunity
C- Table 1.2 Flow Meter Application Table FL
O
8\ W
N-
High Viscous
Larger Meter Pipes
Low pres. Gases
Hot Liquids
Solids in Liquid
Low Viscous
Hot Gases
IN
Gyogenic Fluids
Water
D\
B
O
Flow Meter Types
Appli- cations
O
K
1 Venturi
2 Orifice
3 Nozzle
4 Target
5 Rotameter
6 Spring Loaded Lower
Rotameter
7 Turbine
8 Bypass Rotameter
9 EM
10 UF
11 VS
12 Fluidic
13 Swirl
14 NMR
15 Mass
16 Hot wire
17 Insertion
18 CC
95
19 PD
96 INDUSTRIAL INSTRUMENTATION
Cd for d/D ratio is 0.5999 from the graph [BS : 1042 : 196]. Volumetric flow rate is calculated as
follows :
Q = CdMv.a A2 . m3/sec
2 gh
Q = 0.5999 × 1.032 × /4 (20 × 10–3)2 .
2 9.81 1890 10–3
= 1.184 × 10–3 m3/sec = 1.184 × 10–3 × 3600 = 4.262 m3/hr
Problem 3. Determine the nominal flow velocity V2 at the orifice having a diameter of 20 mm
kept in a pipe of 40 mm diameter. Reynolds number Ra is 105. Assume density of water
= 1000 kg/m3 and kinematic viscosity is 10–2 stokes. (cm2/sec).
C-8\N-IND\BOOK1-6
FLOW 97
Problem 5. Determine the volume flow rate of water through a pipe of 150 mm diam- eter when
measured by (i) an orifice plate of size 75 mm dia and (ii) Venturi tube of throat size 75 mm dia. The
differential pressure recorded is 250 pa. Assume the density of water is 1000 kg/m3.
Solution. Volume flow rate of water is calculated as follows.
d
1 Cd . 2
Q= 1 (d/D)4 2 gh
4
where h = P1 – P2/
(a) For orifice plate : Cd = 0.6
1 (75 103 )2
Q = 1 (1/2)4 0.6 (2 9.81 250)/1000
4
Mv.a. =
1
= 1.032
1 (1/2)4
(10 10 )
a= 2 = 7.85 × 10–3.
2
4
Substituting all the values in Equation (1),
(2 9.81 P)
0.02 = 1.032 × 0.98 × 7.85 × 10–3 ×
1000
(2 9.81 P)
0.02 = 7.939 × 10–3
1000
(2 9.81 P) = 2.52
1000
0.14 P = 2.52
P = 2.52/0.14 = 18
P = 324 kg/m2 = 0.0324 kg/cm2.
Problem 7. An incompressible fluid is flowing in a 300 mm pipe under a pressure head of 2
kg/cm2. Calculate the fluid velocity and volumetric flow rate.
Solution. Fluid velocity.
V = 2 gh
V=
2 9.8 (20) [1 kg/cm2 = 10 metres water head]
= 19.8 m/sec2.
Volumetric flow rate. Q = AV
d
where Area A= 2
4
d = (300 × 10–3) m
(300 103 )2
A= = 0.07 m2.
4
Q = 19.8 m/sec × 0.07 m2 = 1.38 m3/sec.
Problem 8. An incompressible fluid is flowing through an orifice plate with a flow coefficient of
0.6 causing a pressure drop of 400 mm of water column. Calculate the fluid velocity.
Solution. The fluid velocity measured by an orifice is given by an equation V = Cd
where Cd = 0.6 2 gh
g = 9.8 m/sec2.
h = (400 × 10–3) m
V = 0.6 2 9.8 400 103 = 1.68 m/sec.
100 INDUSTRIAL INSTRUMENTATION
Problem 9. A pitot tube with a coefficient of 0.98 is used to measure the velocity of water in a
pipe. The differential pressure head is 900 mm. What is the velocity ?
Solution. V = Cd 2 gh
where Cd = 0.98
g = 9.8 m/sec2
h = (900 × 10–3) m
V = 0.98 2 9.8 900 103 = 4.11 m/sec.
Problem 10. Determine the flow velocity necessary to produce a dip of 20 kPa from a pitot-static
velocity measurement when used (a) in water (b) in air.
Solution. Assume density of water = 1000 kg/m3 and Density of Air = 1.29 kg/m3.
Flow velocity = V = 2 gh/ 2P/
P = 20 kPa.
(i) When flowing fluid is water.
V= 2 20 103 /1000
(ii) When air is flowing, = 6.324 m/sec.
2P
Solution. Flow velocity = V =
P = 25 kN/m2
= 1026 kg/m3
2 12.5 103
= 1.290 = 139.21 m/sec = 501.16 km/hr.
FLOW 101
Problem 13. A rotameter uses a cylindrical float of 3.5 cm height, 3.5 cm dia and den- sity of
3900 kg/m3. The maximum inside diameter of the metering tube is 5 cm. Determine the maximum flow rate
handling capacity of the rotameter if the fluid is water.
Solution. The volume of the float
(3.5 102 )3
Vf = = 3.36 × 10–5 m3
4
Assume Cd = 0.6 (For water)
Dia of the float Df = (3.5 × 10–2) m
Inside diameter of the Pipe
Dp = (5 × 10–2) m
Volume of the float Vf = 3.36 × 10–5 m3
2
D p2 D f gVf ( f )
Volumetric flow Q = Cd .
2
Df
µ 0.05 2
0.035 2 y 9.8 3.36 105 (3.9 103 1 103 )
¡ ¡ 2 (1 103 )
= 0.6 × 0.035 J
µ
= 0.6 × 0.03642 × 1.499 103 = 0.6 × 0.03642 × 0.03872
= 8.4631 × 10–4 m3/sec.
Problem 14. Consider a rotameter float of volume of 520 mm3 with an included angle taper of 5°,
with an effective diameter of 15 mm and a vertical range of movement of 250 mm and is made from
aluminium of relative density 2.7. If the internal diameter of the measuring tube at the bottom is 18 mm.
Determine the range of flow if paraffin is used as a process fluid which has a relative density of 0.8.
Solution. Given Vf = [520 × 10–9] m3
Df = 15 mm
(15 103 )2 x
Af =
4
= 1.7671 × 10–6 m2
Cd = 1 5° 250 mm
From the figure x = 18 + 2 × 250 × tan 5
= 61.7 mm.
Case 1. When float is at the bottom, the flow through the
rotameter is minimum [Dp = 18 mm]
2
D p2 D f gVf ( f )
Qmin = 2
Df
µ (18 10 ) (15 10 3 ) 2
3 2 y 18 mm
= ¡ 15 10 3
¡J 9.8 520 109 (2.7 0.8)
2 0.8
µ
102 INDUSTRIAL INSTRUMENTATION
Problem 18. Calculate the induced emf in an electromagnetic flow meter due to the flow of a
conductive fluid in a pipe with inner diameter of 2.75 cm. The flux density B = 6 mV. sec/cm2 and volume
flow rate Q = 2500 cm3/min.
Solution. Quantity Flow rate Q = 2500 cm3/min
d
Area = 2 (2.75)2 = 5.94 cm2.
4 4
2500
Velocity = = 7.01 cm/sec.
60 5.94
Flux density B = 6 mV sec/cm2
6 103 V sec
= = 60 V sec/m2 = 60 Weber/m2.
(102 ) 2 m 2
Induced emf e = Blv = 60 × (2.75 × 10–2) × (7.01 × 10–2)
= 0.1156 V = 115.6 mV.
Problem 19. Determine the velocity of flow in an electromagnetic flow meter for the following
conditions. The flux density in the liquid has an average value of 0.08 Weber/m2. The diameter of the pipe
is 10 cm. The induced voltage of the electromagnetic flow meter is re- corded as 0.2 mV.
Solution. e = B lv
e 0.2 103
v= =
Bl 0.08 (10 102 )
= 0.025 m/sec = 2.50 cm/sec.
Problem 20. Consider an electromagnetic flow meter which is used to measure volu- metric flow
of a process fluid in a pipe of 60 mm dia. The velocity profile is symmetrical and can be assumed uniform.
The flux density in the liquid is 0.1 Wb/m2. The output from the flow meter is given to an amplifier of gain
1000 and impedance between the electrodes is 275 K. The input impedance of the amplifier is 275 K.
Find the average velocity of the liquid when the P-P voltage at the amplifier output is 0.3 V.
Solution. Diameter of the pipe = 60 mm.
Flux density = 0.1 Weber/m2.
Amplifier gain = 1000.
275 K
Amplifier
gain em
275 K
ei eo
em 1000
104 INDUSTRIAL INSTRUMENTATION