Primary Heat Load 1st
Primary Heat Load 1st
CONTENTS
2. Literature Survey
3. Design
A-INTRODUCTION 24
A.1 Purpose 24
B. HVAC SYSTEM
B.1 Intent 25
B.3 Assumption 25
B.6ProposedSystemVentilation&Exhaust 31
Page |2
Introduction
Air conditioning is defined as a process, which cools (or heats), cleans, circulates,
freshness air controls its moisture content simultaneously.
The comfort feeding of people in an air conditioning plants depends upon following five
main factors:
(d) To provide sufficient air movement and air distribution in occupied space.
The human body requires adequate supply of oxygen to sustain combustion (food
digestion) like other machines, which convert chemical energy into mechanical work,
and dissipates carbon dioxide as exhaust gas. Each person requires nearly 0.65cu.m.
of O2 per hour under normal condition and produce 0.2 cu. m. of CO 2 so that the rise in
concentration of CO2 is an index of oxygen consumption.
The percentage of CO2 in atmosphere is nearly 0.6% and it is necessary to maintain this
percentage for proper functioning of respiratory system. When the percentage of CO 2 in
air exceeds above 2% the partial pressure of oxygen will be reduced to a value such
that the breathing becomes more difficult, Extreme discomfort exists when the
percentage of CO2 reaches 6% and unconsciousness occurs at 10% of CO 2. The
quantity of air-supply to an air-conditioned space should be maintained in such a way
that the percentage of CO2 should not exceed than minimum.
Page |3
The human body can be considered an engine, which converts thermal energy into
mechanical work with a thermal efficiency of 20% and remaining amount of heat is
dissipated to the atmosphere. The atmosphere surrounding the person must be capable
to absorb the heat dissipated by the person, otherwise discomfort exists. When the man
is not doing any external work, still he does sufficient internal work as pumping of blood
through the body and muscular work required for respiration.
If a space of 6 cu. m. is provided to each person and if there is no transfer of heat and
air from outside source, then the space temperature will rise through 0.15 0C for each kJ
of heat added to the space and rise temperature of 48% per hour would result as man
body dissipates 320kJ of heat per hour.
The moisture less from the body is nearly 50 grams per hour when the man is at rest.
The body ability to dispose of heat by evaporation to atmosphere decreases as the air
humidity increases. High humidity of air reduces the apparent freshness of air in
enclosed space in addition to difficultly in disposing of body heat. The ventilation system
must be capable to maintain the relative humidity below 70%.
Increased air velocity increases the heat transfer from the body by reducing the
thickness of air film adjacent to the body. The effect of increased velocity is to increases
the body heat loss and reduce the feeling of discomfort when the ambient air is at a
temperature lower than body surface temperature. The sensible heat transfer will be in
the opposite direction if the air temperature exceeds that of body temperature, so the
effect of the increases velocity is to increase the existing discomfort.
Secondly, increases velocity reduces the thickness of the layer of the saturated vapour
near the body surface and helps for evaporation. The heat loss by evaporation is
usually greater than the heating effect by convection, when the dew point temperature is
below 300C so the increased velocity is always advantageous. The Heat transfer will be
towards the body when the air is at high temp and at high relative humidity so increased
air velocity will create discomfort. Air velocity in the air conditioned space should not be
more than 6 to 9 m/min at 20 C and 9 to 15m/min at 22 C
Page |4
Table 1.1 comfortable ranges of air velocity and humidity with respect to room air temperature
20 0.04 0.12 35 65
21 0.04 0.14 35 65
22 0.05 0.17 35 65
23 0.07 0.21 35 65
24 0.09 0.24 35 65
25 0.12 0.32 35 65
26 0.16 0.40 35 65
Air motion alone has no meaning without proper air distribution. Air distribution is
defined as a uniform supply of air- conditioned system. Air motion without proper air
distribution is responsible for local cooling sensation known as draft the velocities less
than 8 m/min associated with temp differential of 1.5 C produce uncomfortable
drafty conditions.
The quality of air in regard to odour, dust , toxic gases and bacteria is considered for
defining the purity of air . The evaporation on the surface of the body add odours in the
air. There are many sources contributing the different odours to air – conditioned space
situated near the chemical, cloth and paper industries the smoke is objectionable due
to its bad effects on nose, eyes and hearts. It’s also unpleasant to the nonsmokers. The
removal of toxic gases is essential to avoid heavy irritation caused by them. The control
of bacteria is most important to prevent the bad effects of the bacteria on human health
and this is done by sterilization of air.
1.2.1 Importance
The purpose of air conditioning is to supply sufficient volume of clean air containing a
specific amount of water vapor and at temp capable of maintaining predetermined
Page |5
Properly air conditioned results in greater comfort to occupants when applied to public
places, offices and factories. Industrially it has many benefits including better control of
product quality texture and uniformity.
1.2.2 Applications:-
The applications of air conditioning applications are grouped in following two categories
Residences
Retail facilities
i. Small stores
ii. Variety stores
iii. Super markets
iv. Departmental stores
Places of assembly
i. Auditorium
ii. Sports complex
Domiciliary facilities
i. Hotels and motels
ii. Dormitories
Education facilities
Health facilities
Page |6
i. Hospitals
ii. Nursing homes
Transportation
Ships
i. Naval ships
ii. Merchants ships
Computer room
Textile processing
Nuclear facilities
Printing plant
Photographic applications
Industrial ventilation
2.1.1 Conduction
It is the mode of transmission of heat in which heat travels from hot part of the body to
its cold part, without any actual motion of heated particles. If we place two bodies one
hot another cold in contact with each other, we observe that the hot body gradually
Page |7
grows warmer. This happens because some of the heat energy from the body is
transferred to cold body.
2.1.2 Convection
Convection is transfer of heat by actual motion of material for example whenever a solid
body is exposed to a moving fluid or gas having a temperature lower than that of the
body, energy initially conducted from the solid, is carried or convected away by the fluid.
The heat is transferred by gross motion of matter. The hot air furnace, the hot water
heating system and the flow of blood in the body are the examples of convection.
Convection takes place in case of liquids or gases only.
If the fluid motion is caused by the difference in density that accompanies a change in
temperature, the convection current produced is referred to as natural convection. In
case if the fluid is caused to move by the action of a fan or pump, the current is
produced referred to as forced convection. Both of these are used in common heating
systems for home heating.
The radiations emitted by the sun are known as solar radiations. These radiations play
an important role in the estimation of cooling load. They are the following two types:
The solar radiation, which reaches the earth surface without changing its direction and
wavelength is known as direct or beam radiation, these radiation are in line with sun and
cast a shadow when interacted by an opaque object.
The solar radiation coming from all parts of sky’s hemisphere after scattering,
absorption and transmission is called diffused solar radiation.
Page |8
In actual practice, the various principles of heat transfer must be combined in order to
solve many problems. With insulated walls and pipes, convection occurs between inner
and outer surfaces and conduction occurs between the surfaces.
Consider the heat is flowing from the hot atmosphere to air conditioned room, the heat
flow can be calculated considering
(i) Heat flow from the hot atmosphere air to wall surface by convection.
(ii) Heat flow from the inner wall surfaces to inside air by convection.
hi = Heat transfer coefficient from the hot atmospheric air to the wall surface.
= K2 A (T2 – T3)/ X2
= K3 A (T3 – T4)/ X3
= h0 A (T4 – T0)
Q = ___________________T1 – T0 __________________________
Where 1/h A and 1/h A are known as surface resistances or convective resistances
where the other terms known as internal or conductive resistances and the addition of
all is known as total resistances. For reducing the heat gain or loss from the air
conditioned buildings, air gaps are generally provided, as air is very bad conductor of
heat.
Generally h1 and h2 are same and their values are quite small so that 1/h 1 A and 1/h2 A
become quite larger compared with the other resistances so that the total heat flow will
be considerably reduced with the use of air gaps.
Page |9
This is very common practice in all air conditioning system to prevent the flow of heat
from the atmosphere to room for summer air conditioning and from the room to the
atmosphere for winter air conditioning.
There are several different ways for classifying air conditioning system.
Any air conditioning system used in industrial units to control atmospheric conditions
mainly for the proper conduct of research and manufacturing operations. Air
conditioning system in paper mills, photo processing plants are of this type. The system
may have conditions comfortable to occupants or it may not be comfortable.
Winter air conditioning is maintaining temperature and humidity of air inside the space,
higher than of surrounding air. The air is heated and humidified before being delivered
to the conditioned space. This system will give conditions in the space comfortable for
winter.
Summer air conditioning system is maintaining temperature and humidity of air inside
the space normally below that of surroundings. The air is cooled and dehumidified
before being supplied to conditioned space.
2.4 PSYCHROMETRY
Psychrometry is the science involving thermodynamic properties of moist air and the
effect of atmospheric moisture on materials and human comfort.
The sum of all sensible and latent heat loads is known as ‘Room Sensible Heat
Load’(R.S.H) and the ‘Room Latent Heat’(R.L.H) respectively. The some of the RSH
and RLH is known as ‘Room Total Heat Load’(RTH) the ratio of the RSH to the RTH
(RSH/RTH) is known as the ‘Room Sensible Heat Factor’(RSHF).
Thus we have:
It is the “Effective room total heat load that determines the quality and temperature-
humidity condition of supply and the grand total heat load determines the capacity of the
refrigerant plant.
3. Design
The heat load estimation form is designed to arrive at these loads and the condition and
quality of dehumidified supply air needed.
Before understanding the use of the heat load estimation for, it is necessary to
remember the following ratios and terms.
1. SHF=SH/SH+LH=SH/TH
Where,
SH =Sensible heat
LH =Latent heat
TH =Total heat
2. RSH=RSH/RSH+RLH
Where,
P a g e | 12
Where,
Where,
Where,
6. Bypass of Air
Consider the cooling apparatus as a cooling coil in which chilled water is circulated or
as the cooling coil of the refrigerant plant. The air passing over the cooling coil and fins
gets cooled and dehumidified. All the air cannot come in contact with the cooling coil
and fins. Some air passing between the fins. We can say this part of the air "by passes"
the cooling surface of the cooling coil and comes out of the cooling apparatus at the
same condition as it entered. It mixes with that (1-BF) part of the air which on direct
contact with the cooling coil surface and fins, gets cooled and dehumidified thus giving a
condition of a mixing of cooled — dehumidified air and initial air. The amount of by-pass
depends upon:
TADP=11.110C
For calculating the total quality of dehumidified air ,following formula is used:
Then,
100641.78
Qda = =¿629.12 CFM
17.28 [ 22−11.11 ] [1−0.15]
P a g e | 14
1) Number of fins per cm inch on the coil (Gap between fins or finch of fin.)
2) Velocity of air over the coil.
3) Number of rows of coil pipe in the direction of air flow.
7. Bypass Factor
The ratio of the quantity of the bypass air to that of the total air passing through the coil
is known “By Pass Factor” (BF), The BF depend upon the fin pitch,velocity of air over
the cooling coil face and the number of row (coil tubes) in the direction of air flow.
The BF increases as the coil face (Air) velocity increases but decreases as the fin pitch
decreases and as the number of row increase.
By pass occurs in the air washer as well and here it affect the saturation efficiency.
As result of the bypass effect the room sensible and latent heat (The room total heat) go
up due to the addition of the sensible and latent heat of the bypass fresh air and
infiltration load where applicable. These new values are termed as “effective room
sensible heat” (ERSH), “Start effective room latent heat (ERLH) and “effective room
sensible heat factor” (ERSHF). This ratio becomes handy to derive at the supply air
quantity as it encompasses the effect of by pass and infiltration.
44°C + 22°C/ 2
P a g e | 15
= 32°C
For outside surface
= 42°C
T w= 32°C
ΔT = T o +T fo
= 42°C - 37°C
= 5°C
We know that,
PrandtI number,
Pr = µC p/K
Where,
µ = Coefficient of viscosity ( Ns/m2)
C p =Specific heat at 310 K (J/kg-K)
K = Thermal conductivity of air film (W/m-K)
∴ PR = 189.32x10-7x1.007x103
27.04 x 10-3 __________________________
PR = 0.705
Plotting the initial and final conditions at point 1 and point 2 respectively
On psychometric chart, the values of enthalpy are
h1 = 72.5 KJ/Kg
h2 = 46.0 KJ/Kg
hA = 67.0 KJ/Kg
And value of specific volume,
Vs = 0.91 m3/Kg
∴ Mass of infiltrated air per min,
Minf = Vinf / Vs = 1.672/0.91 = 1.81 Kg/min
∴ Sensible heat gain due to infiltrated air,
P a g e | 16
= 32.34 KJ/min
Qs(f.a) = 539 W
= 8.47 KJ/min
QL(f.a) = 141 W
P a g e | 17
When occupants are doing light work, sensible heat gain per person is 142 W and latent
heat gain per person is 42 W.
QS.O. = 5 x 142
= 710 W
QL.O. = 5 x 42
= 210 W
QO = QS.O. + QL.O.
= 710 + 210
= 920 W
QSH = 106232.99 W
= 10%× 106232.99
= 10623.3 W
Effective room sensible heat,
P a g e | 19
= 106232.99 + 10623.3
= 116856.29 W
A. INTRODUCTION
A.1 Purpose
The primary purpose of this report is to provide and describe a permanent record of the
building system. In addition to describing the system, the fundamental assumption used
for design is also outline temperature and humidity criteria noise limit water demand
usage, Power demand and usage, occupancy and lighting level. This information is
critical to ensure the contractor, other discipline, operator, and future designer
understand the assumption made and the limitation of the system without information,
one to guess at designer line of reasoning during this design process throughout the
design process, the basis need to be consistent with the process intent. This report is
based on the systematic design assumption and will be modified as the project progress
to the level of detail of design. The project intent is shown in the basis of design: the
designer transform the project intent and challenges into reality
VCTM College is the proposed project in Aligarh district of Uttar Pradesh with a total
buildup of workshop 20260 ft. sq. The VCTM college includes workshop and labs
P a g e | 20
The design report presented here however the design philosophy of only a part of it
which a WORKSHOP of approximately 20260 ft.sq.
B. HVAC system:
B.1 Intent:
Objective of HVAC is to provide thermal comfort to all areas of hotel for all occupants in
an efficient and cost effective manner. Temperatures and indoor air quality shall be
maintained in accordance with parameters as specified in the following section of Basis
of Design.
The design approach shall be sensitive to environmental issue. The main trust shall be
laid on energy conservation, safety and ease of maintenance and current progressive
technological developments. Building will be designed after understanding minute level
of detailing and requirement of thermal comfort.
B.3 Assumption:
This section of the basis of design documents specifies number used in the design of
the building. These assumptions are an essential part of making the transition from the
project intent to installed equipment and the course are guidelines for the designer and
contractor which are to be followed during the different stage of project.
P a g e | 21
Occupancy:
Architectural plans. For areas where capacity is not mentioned, it is assumed as per
NBC-Part-8, Building Services, and Section-3, Table 4 or ASHRAE 62.1-2007 table 6-1
2. 90.1-2007
3. 62.1-2007
4. Fundamentals-2005
5. HVAC application-2007
7. Refrigeration-2006
Safety codes:
Light
Floor Fres AC
/
S.N Area Occupanc h Air Dehum Loa
Floor / Space Eqpt.
O (SqFt y Nos (CFM (CFM) d
Load
) ) (TR)
(KW)
0.3/2.
2.1 Computer room 148 3 24 868.00 1.48
0
.
2.2 Telephone Exchange 72 2 12 347.00 0.69
14/1.0
.
2.4 General cashier 82 2 14 223.00 0.43
16/.25
1.0/2.
2.5 Account's office 496 9 80 1564.00 2.89
0
.
2.8 Training Manager 78 2 13 196.00 0.39
15/.25
.
2.11 Uniform issue 257 6 42 822.00 1.54
51/.25
.
2.12 Personnel office 127 3 21 594.00 1.05
25/.75
.
2.13 Personnel manager 97 2 16 456.00 0.80
19/.25
P a g e | 25
2.14 JR. Male locker room 720 15 1.44 415 2601.00 5.98
2.16 JR. & SR. Female locker room 253 6 0.5 385 1034.00 3.30
2.18 Executive Male locker room 103 3 0.2 200 588.00 1.79
2.0/2.
2.20 Staff canteen 655 27 315 2897.00 6.39
0
.
2.21 Exec. Asst. manager 85 2 14 351.00 0.63
17/.25
.
2.22 Banquet manager 83 2 14 258.00 0.49
16/.25
.
2.23 F & B manager 85 2 14 259.00 0.49
17/.25
.
2.24 Sales manager 108 3 18 390.00 0.73
21/.25
60.0
2.25 Banquet hall 3700 9 68 10200.0
0.84 0
2.26 Sales & Secretaries 405 310 5/2.0 400 1382.00 2.55
The proposed system composing VRV, for the School project as per the usage and
requirement of the building. We are proposing high efficiency magbearing screw chillers
for low maintenance and low electrical consumption. The advantage of magbearing
chillers is that there is no noise.
Toilet shall be ventilated at a rate of 15 air changes per hour and small toilets are
ventilated at 10 ACPH. Toilet doors shall have an undercut (or an air transfer grill) so
that some air from the cooled space shall pass through this undercut /air transfer grill
and exhausted out, using Inline Fan.
P a g e | 27