MV Cable Insulation and VLF Test Report-Is1-C.b-circuit 1

This document summarizes the results of insulation and VLF testing of cables at Inverter Station IS1. It records the testing equipment used, date, cable information, test voltages and durations for insulation and VLF tests. The insulation tests showed resistance above 1GΩ and passed. The VLF tests at 44kV RMS with 0.1Hz frequency had leakage currents around 12mA and withstood the tests. Post-VLF insulation tests also passed.

Uploaded by

Ahmed Rabaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
339 views2 pages

MV Cable Insulation and VLF Test Report-Is1-C.b-circuit 1

This document summarizes the results of insulation and VLF testing of cables at Inverter Station IS1. It records the testing equipment used, date, cable information, test voltages and durations for insulation and VLF tests. The insulation tests showed resistance above 1GΩ and passed. The VLF tests at 44kV RMS with 0.1Hz frequency had leakage currents around 12mA and withstood the tests. Post-VLF insulation tests also passed.

Uploaded by

Ahmed Rabaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Test Type: MV Cable Insulation and VLF Test

Sector Number: ________________ Inverter Station Number: __IS1-C.B/Circuit


1_______________

Testing Equipment Used:


____________HVA60__________________________________________

Testing Equipment Serial Number:


_______GH5238.17E018_______________________________________

Date of Testing: ______17/01/2020__________ Time of Testing:


_________________________

Cable Type____________________ Number of Runs: ________________________

Insulation Test Voltage: 5000 Vdc Insulation Test Duration: 60 Seconds

Minimum Resistance: 1GΩ

VLF Test Voltage: 44kV RMS VLF Test Duration: 60 Minutes

VLF Test Frequency: 0.1Hz

From Inverter Station __ To Inverter Station __

Cable Insulation Test Before VLF

Measured
Cable 1 Cable 2 Test Voltage Pass/Fail
Value

Shield 5000Vdc
Phase L1-A
>10TOhm Pass
Shield 5000Vdc
Phase L2-A
>10TOhm Pass
Shield 5000Vdc
Phase L3-A
>10TOhm Pass

1
VLF Test

Leakage Withstands Test


Cable 1 Test Voltage Frequency
Current Pass/Fail

Phase L1-A 44kV RMS 0.1 Hz 12.2mA

44kV RMS 0.1 Hz


Phase L2-A Pass
12.2mA
44kV RMS 0.1 Hz
Phase L3-A
12.3mA

Cable Insulation Test After VLF

Measured
Cable 1 Cable 2 Test Voltage Pass/Fail
Value

Shield 5000Vdc
Phase L1-A
>10TOhm Pass
Shield 5000Vdc
Phase L2-A
>10TOhm Pass
Shield 5000Vdc
Phase L3-A
>10TOhm pass

VLF Tester Report to be attached.

Tested By: Witnessed By Verified By Approved By

Name/Company Eng.Ahmed Rabaa

Signature