Seismic Load Manual Calculation
Seismic Load Manual Calculation
For slab:
Dead load of slab= 30 x 20 x 0.15 x 25= 2250 KN
For Beam:
Self-weight of beam= 0.3 x 0.4 x 25= 3 KN/m (per meter)
Clear dimension of longitudinal beam= 5-0.2-0.2=4.6m
Clear dimension of Transverse beam= 5-0.2-0.2=4.6m
No. of longitudinal beam= 6 x 5=30
No. of transverse beam= 4 x 7= 28
Self-weight of longitudinal beam=3 x 4.6 x 30=414 KN
Self-weight of transverse beam=3 x 4.6 x 28=386.4 KN
Total self- weight of both beam = 414+386.4=800.4 KN
For walls:
Self-weight of wall= 0.23 x 20=4.6 KN/m2
Self-weight of longitudinal wall=4.6 x 4.6 x 30=634.8 KN/m
Self-weight of transverse wall=4.6 x 4.6 x 28=592.48 KN/m
Total self- weight of both wall = 634.8+592.48=1227.28 KN/m (per meter height)
For columns:
No. of columns= 35
Self -weight of column= 0.4 x 0.4x 25 x 35= 140 KN/m (per meter height)
Now,
Seismic weight= Dead load+ percentage of Live load
Dead load of roof = self-weight due to ( slab+ Beam+ Column+ Wall)
= 3630+800.4+(140 x3.5/2)+[1227.28 x (3.5-0.4)/2]
=6577.684 KN
Seismic weight of roof= Dead load + Live load
= 6577.684+0=6577.684 KN
Also,
Dead load of floor= self-weight due to ( slab+ Beam+ Column+ Wall)
= 2730+800.4+ (140 x3.5)+[1227.28 x (3.5-0.4)]
= 7824.968 KN
Live load on floor= 1200 KN
Seismic weight of floor= Dead load + Live load
= 7824.968 + 1200=9024.96 KN
EL in X-Direction:
T = 0.09h / √d
= 0.09 x 17.5 / √30
= 0.28 sec
• The building is located on medium soil and for 0.28 sec time period, value of Sa/g= 2.5
• For seismic zone V, the zone factor Z is 0.36.
• Being an office building, the importance factor, I, is 1.
• Building is required to be provided with special moment resisting frames. Hence, the
response reduction factor, R, is 5.
EL in X-Direction:
T = 0.09h / √d
= 0.09 x 17.5 / √20
= 0.35 sec
The building is located on medium soil and for 0.28 sec time period, value of Sa/g= 2.5
Therefore, for this building the design seismic force in Y-direction is same as that in the X-
direction.