02 EasyIO FC20 User Reference v1.6 PDF
02 EasyIO FC20 User Reference v1.6 PDF
EasyIO FC 20 Series
User Reference
EasyIO FC20 User Reference v1.6
th
17 Jan 2018
Updated disclaimer and support channel emails addresses
Removed Sedona Workbench installation.
EasyIO FC20 User Reference v1.6
Disclaimer
Confidentiality Notice
The information contained in this document is confidential information of EasyIO Holdings Pte Ltd. Such
information and the software described herein, is furnished under a license agreement and may be used
only in accordance with that agreement.
The information contained in this document is provided solely for use by EasyIO Holdings Pte Ltd
employees, licensees, and system owners; and, except as permitted under the below copyright notice, is
not to be released to, or reproduced for, anyone else.
While every effort has been made to assure the accuracy of this document, EasyIO Holdings Pte Ltd is not
responsible for damages of any kind, including without limitation consequential damages, arising from
the application of the information contained herein. Information and specifications published here are
current as of the date of this publication and are subject to change without notice. The latest product
specifications can be found by contacting our corporate headquarters or support channel.
Trademark Notice
BACnet and ASHRAE are registered trademarks of American Society of Heating, Refrigerating and Air-
Conditioning Engineers. All other product names and services, mentioned in this publication, that are
known to be trademarks, registered trademarks, or service marks are the property of their respective
owners.
Disclaimer
The material in this manual is for information purposes only. The contents and the product it
describes are subject to change without notice. EasyIO Holdings Pte Ltd makes no
representations or warranties with respect to this manual. In no event shall EasyIO Holdings Pte Ltd be
liable for any damages, direct or incidental, arising out of or related to the use of this manual.
FCC Caution
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Contents
Introduction ....................................................................................................................................................6
Hardware Configurations ................................................................................................................................7
Power supply Connection ...........................................................................................................................7
RS485 Connection.......................................................................................................................................8
Jumpers Setting ........................................................................................................................................10
Digital Output Wiring Connection ............................................................................................................12
Universal Input Connection ......................................................................................................................13
Analog Output Connection .......................................................................................................................14
Buttons and Indications ................................................................................................................................15
Technical Support .........................................................................................................................................15
EasyIO FC20 User Reference v1.6
Introduction
The EasyIO FC Series is aimed at affordable ‘canned’ solutions for standalone applications, such as Roof
Top Units, Fan Coils, AHU’s, package units etc.
EasyIO FC20 Series controller comes with built in bootloader program. Built in bootloader program will
enable user to upgrade firmware without sending back to factory.
EasyIO FC20 do not have an Ethernet port.
It only has RS 485 serial port.
Firmware Upgrade is perform via direct serial connection to the controller.
EasyIO FC20 User Reference v1.6
Hardware Configurations
Power supply Connection
Both AC and DC can be used for EasyIO FC-20 controller. Refer to electrical specification for the working
range. In order to avoid damage on the controller input/output devices and RS485 connection, use
individual power supply for each controller. If a single power supply is used, make sure controller power
supplies are connected with the same polarity.
RS485 Connection
RS485 connection must be terminated at both ends with termination resistor, typically 120Ohms. It is
recommended to use shielded twisted pair wire (STP) for the wiring. Lightning protection circuit is
recommended to be installed at one end of the wiring. The controller should be wired in daisy chain
network topology as shown as image below. If wire branch can be avoided, keep it as short as possible,
and never connect more than one device to the wire branch.
Be careful if single power supply is used for all connected RS485 device, make sure all devices are
having the same ground connection. Make sure you are connecting the same wire for the same
terminal position, all “H” terminals connected to the same wire.
RS485 Connection
EasyIO FC20 User Reference v1.6
Port Number Protocol Communications supported Default Serial port settings Remarks
Port 1 Modbus OR BACnet Modbus Port 1 is used to perform;
( D1+ , D1- ) Protocol selection is done via DIP switch 1. Baud Rate : 19.2K - Firmware flashing. (FwTool.exe)
Parity : even - Virtual Device for program downloads. (FcVirtualDevice.exe)
DIP 1 = OFF = Modbus RTU Data Bit : 8 (Not editable) - Terminal mode for serial configurations editing. (FwTool.exe)
DIP 1 = ON = BACnet MSTP Stop Bit :1
BACnet
Baud Rate : 19.2K
Port 2 Only supports Modbus RTU Protocol Modbus If port 2 is configured Modbus Master RTU (Default)
( D2+ , D2- ) (Default). Baud Rate : 19.2K
Parity : even Port 2 is used to perform;
It supports Modbus Master as well if Data Bit : 8 (Not editable) - Virtual Device for program downloads. (FcVirtualDevice.exe)
configure via FC Virtual Tool. Stop Bit :1
EasyIO FC20 User Reference v1.6
Jumpers Setting
Below image shows the jumper setting for Universal Input, Analog Output, BACnet/Modbus Selection,
and the BACnet MSTP ID (1~127) or Modbus Serial ID (1~127).
The controller comes with BACnet and Modbus protocols selection. By default, Modbus protocol is
selected. To switch to BACnet protocol, toggle the ‘1’ of the dip switch to ON.
The remaining DIP switch ‘2’ ~ ‘8’ are for BACnet MSTP ID or Modbus Serial ID (address 0 is not available;
it will be set to 1) depending on DIP switch 1 selection.
Any changes to the DIP switch, a power cycle is needed.
117
EasyIO FC-20 has four general purpose isolated digital output connections (relay output). Each relay
output able to drive up to 1A 30VDC/ 48VAC load.
It does not output voltage or current. It is a dry relay contact.
EasyIO FC-20 has twelve non-isolated universal inputs. The universal input supports three type of analog
signal i.e. resistance, voltage and current transmitter via hardware jumper and internal register settings:
a) Resistance – The working range of resistance is 0 – 300K Ohms. If the input is configured as
Thermistor type, the system provides 8 customizable temperature lookup tables for resistance to
temperature translation. The commonly used Thermistor like 10K, 10K with Shunt, 1K Balco and 1K
Platinum are all supported
b) Voltage – Two selection of working range 0 – 5V and 0 – 10V. The minimum input impedance of
voltage input is 1 Mega Ohm.
c) Current – Two selection of working ranges 0 – 20mA and 4 – 20mA. The current input impedance is
less than 25 Ohm.
d) Pulse Input – Only UI1, UI2, UI3 and UI4 are capable of receiving high speed pulse. Minimum on time
pulse is 25ms and minimum off time is 25ms. Refer to image below.
Universal Input Connection
EasyIO FC20 User Reference v1.6
EasyIO FC-20 has four Analog Output connections. Each Analog Output can be configured to drive voltage
or current output via hardware jumper setting and internal register settings.
The working range for voltage is 0 – 10V and for current either 0 – 20mA or 4 – 20mA.
**We DO NOT recommend you to drive a relay directly from UO 0-10V mode as it is not design for it
and will damaged the AO. **
For voltage mode, the circuit able to drive load with a minimum impendence of 8,000 ohms.
For current transmitter, the circuit able to drive load impedance up to 800 ohm which is ideal for long
wire connection (up to 500 meter wire length).
Technical Support
For technical issue, please contact