2005 National Electrical Code Optional Residential Electrical Load Calculation For Single Family Residences Only

This document is a residential electrical load calculation worksheet for single family homes. It provides sections to calculate the load for general lighting, small appliances, laundry, cooking appliances, dryers, fixed appliances, heating/air conditioning, and then totals the loads to determine the minimum required service size in amps. Spare capacity and grounding requirements are also included in the final calculations.

Uploaded by

dilipgm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
550 views

2005 National Electrical Code Optional Residential Electrical Load Calculation For Single Family Residences Only

This document is a residential electrical load calculation worksheet for single family homes. It provides sections to calculate the load for general lighting, small appliances, laundry, cooking appliances, dryers, fixed appliances, heating/air conditioning, and then totals the loads to determine the minimum required service size in amps. Spare capacity and grounding requirements are also included in the final calculations.

Uploaded by

dilipgm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

2005 NATIONAL ELECTRICAL CODE

OPTIONAL
RESIDENTIAL ELECTRICAL LOAD CALCULATION
FOR SINGLE FAMILY RESIDENCES ONLY

Owner Prepared by

Address

General Lighting Load Sq. Ft. x 3 VA (a) = VA

Small Appliance Circuits at 1500 VA x (Minimum of 2) (b) = VA

Laundry Circuit at 1500 VA x (Minimum of 1) (c) = VA

Electrical Cooking Appliances at nameplate rating (d) = VA

Dryer Load per National Electrical Code Table 220-54 (e) = VA

Fixed Appliances – Use 100% of the nameplate rating


Microwave 1500 VA x = Food Center 600 VA x =
Compactor 1200 VA x = Disposal 600 VA x =
Dishwasher 1200 VA x = ____VA x =
Water Heater 4500 VA x = ____VA x =
Central Vacuum 1800 VA x = Appliance Subtotal (f) = VA

Total for all lighting and appliance loads (a)+(b)+(c)+(d)+(e)+(f) (g) = VA

Total (g) VA – 10,000 VA = VA x .40 (40%) (h) = VA

Heating/Air Conditioning Calculation


By nameplate ratings of heat pumps or Heat Strips for Heat Pumps
AC compressors VA x = VA
VA x = VA VA x = VA
VA x = VA Split System FAUs
VA x = VA VA x = VA
VA x = VA
By Rule of Thumb Total Tons of Cooling
X 2000 VA = VA Total of all HVAC equipment (i) = VA

Plus 10,000 VA at 100% (j) = 10,000 VA

Plus 4800 VA spare for new house only per CLV Ordinance (k) = 4,800 VA

Grand Total (h)+(i)+(j)+(k) (l) = VA

Minimum required ampacity (l) = VA divided by 240V = Amps

Service Size Grounding Electrode Conductor

Revised 04/07 cp: SFD Residential Electrical Load Calculation Option