Nonsinusoidal Exciting Current: Power Transformers
Nonsinusoidal Exciting Current: Power Transformers
SURGE PHENOMENA
3.3
THE PER-UNIT SYSTEM
Power-system quantities such as voltage, current, power, and impedance are
often expressed in per-unit or percent of specified base values. For example,
if a base voltage of 20 kV is specified, then the voltage 18 kV is ð18=20Þ ¼
0.9 per unit or 90%. Calculations can then be made with per-unit quantities
rather than with the actual quantities.
One advantage of the per-unit system is that by properly specifying base
quantities, the transformer equivalent circuit can be simplified. The ideal
transformer winding can be eliminated, such that voltages, currents, and ex-
ternal impedances and admittances expressed in per-unit do not change when
they are referred from one side of a transformer to the other. This can be a
significant advantage even in a power system of moderate size, where hun-
dreds of transformers may be encountered. The per-unit system allows us
to avoid the possibility of making serious calculation errors when referring
quantities from one side of a transformer to the other. Another advantage of
the per-unit system is that the per-unit impedances of electrical equipment of
similar type usually lie within a narrow numerical range when the equipment
ratings are used as base values. Because of this, per-unit impedance data can
SECTION 3.3 THE PER-UNIT SYSTEM 109
be checked rapidly for gross errors by someone familiar with per-unit quanti-
ties. In addition, manufacturers usually specify the impedances of machines
and transformers in per-unit or percent of nameplate rating.
Per-unit quantities are calculated as follows:
actual quantity
per-unit quantity ¼ ð3:3:1Þ
base value of quantity
where actual quantity is the value of the quantity in the actual units. The base
value has the same units as the actual quantity, thus making the per-unit quan-
tity dimensionless. Also, the base value is always a real number. Therefore, the
angle of the per-unit quantity is the same as the angle of the actual quantity.
Two independent base values can be arbitrarily selected at one point in
a power system. Usually the base voltage VbaseLN and base complex power
Sbase1f are selected for either a single-phase circuit or for one phase of a three-
phase circuit. Then, in order for electrical laws to be valid in the per-unit sys-
tem, the following relations must be used for other base values:
SOLUTION The values of S base , Vbase1 , and Vbase2 are, from the transformer
ratings,
S base ¼ 20 kVA; Vbase1 ¼ 480 volts; Vbase2 ¼ 120 volts
Using (3.3.4), the base impedance on the 120-volt side of the transformer is
2
Vbase2 ð120Þ 2
Z base2 ¼ ¼ ¼ 0:72 W
S base 20;000
Then, using (3.3.1), the per-unit leakage impedance referred to winding 2 is
Zeq2 0:0525 78:13
Zeq2p:u: ¼ ¼ ¼ 0:0729 78:13 per unit
Zbase2 0:72
If Zeq2 is referred to winding 1,
2
N1 480 2
Zeq1 ¼ at2 Zeq2 ¼ Zeq2 ¼ ð0:0525 78:13 Þ
N2 120
¼ 0:84 78:13 W
The base impedance on the 480-volt side of the transformer is
2
Vbase1 ð480Þ 2
Zbase1 ¼ ¼ ¼ 11:52 W
S base 20;000
and the per-unit leakage reactance referred to winding 1 is
Zeq1 0:84 78:13
Zeq1p:u: ¼ ¼ ¼ 0:0729 78:13 per unit ¼ Zeq2p:u:
Zbase1 11:52
Thus, the per-unit leakage impedance remains unchanged when referred from
winding 2 to winding 1. This has been achieved by specifying
Vbase1 Vrated1 480
¼ ¼ 9
Vbase2 Vrated2 120
Figure 3.9 shows three per-unit circuits of a single-phase two-winding
transformer. The ideal transformer, shown in Figure 3.9(a), satisfies the
per-unit relations E1p:u: ¼ E 2p:u: , and I1p:u: ¼ I2p:u: , which can be derived as
follows. First divide (3.1.16) by Vbase1 :
E1 N1 E2
E1p:u: ¼ ¼ ð3:3:6Þ
Vbase1 N2 Vbase1
Then, using Vbase1 =Vbase2 ¼ Vrated1 =Vrated2 ¼ N1 =N2 ,
N1 E2 E2
E1p:u: ¼ ¼ ¼ E 2p:u: ð3:3:7Þ
N2 N1 Vbase2
Vbase2
N2
SECTION 3.3 THE PER-UNIT SYSTEM 111
FIGURE 3.9
Per-unit equivalent
circuits of a single-phase
two-winding transformer
I1 N 2 I2
I1p:u: ¼ ¼ ð3:3:8Þ
Ibase1 N1 Ibase1
Then, using Ibase1 ¼ S base =Vbase1 ¼ S base =½ðN1 =N2 ÞVbase2 ¼ ðN2 =N1 ÞIbase2 ,
N2 I2 I2
I1p:u: ¼ ¼ ¼ I2p:u: ð3:3:9Þ
N1 N2 Ibase2
Ibase2
N1
Thus, the ideal transformer winding in Figure 3.2 is eliminated from the
per-unit circuit in Figure 3.9(a). The per-unit leakage impedance is included
in Figure 3.9(b), and the per-unit shunt admittance branch is added in Figure
3.9(c) to obtain the complete representation.
When only one component, such as a transformer, is considered, the
nameplate ratings of that component are usually selected as base values.
When several components are involved, however, the system base values may
be di¤erent from the nameplate ratings of any particular device. It is then
necessary to convert the per-unit impedance of a device from its nameplate
112 CHAPTER 3 POWER TRANSFORMERS
Three zones of a single-phase circuit are identified in Figure 3.10(a). The zones
are connected by transformers T1 and T2 , whose ratings are also shown. Using
base values of 30 kVA and 240 volts in zone 1, draw the per-unit circuit and
FIGURE 3.10
Circuits for Example 3.4
SECTION 3.3 THE PER-UNIT SYSTEM 113
determine the per-unit impedances and the per-unit source voltage. Then cal-
culate the load current both in per-unit and in amperes. Transformer winding
resistances and shunt admittance branches are neglected.
SOLUTION First the base values in each zone are determined. S base ¼
30 kVA is the same for the entire network. Also, Vbase1 ¼ 240 volts, as
specified for zone 1. When moving across a transformer, the voltage base
is changed in proportion to the transformer voltage ratings. Thus,
480
Vbase2 ¼ ð240Þ ¼ 480 volts
240
and
115
Vbase3 ¼ ð480Þ ¼ 120 volts
460
The base impedances in zones 2 and 3 are
2
Vbase2 480 2
Zbase2 ¼ ¼ ¼ 7:68 W
S base 30;000
and
2
Vbase3 120 2
Zbase3 ¼ ¼ ¼ 0:48 W
S base 30;000
and the base current in zone 3 is
S base 30;000
Ibase3 ¼ ¼ ¼ 250 A
Vbase3 120
Next, the per-unit circuit impedances are calculated using the system
base values. Since S base ¼ 30 kVA is the same as the kVA rating of trans-
former T1 , and Vbase1 ¼ 240 volts is the same as the voltage rating of the zone
1 side of transformer T1 , the per-unit leakage reactance of T1 is the same as
its nameplate value, XT1p:u: ¼ 0:1 per unit. However, the per-unit leakage
reactance of transformer T2 must be converted from its nameplate rating to
the system base. Using (3.3.11) and Vbase2 ¼ 480 volts,
460 2 30;000
XT2p:u: ¼ ð0:10Þ ¼ 0:1378 per unit
480 20;000
Alternatively, using Vbase3 ¼ 120 volts,
115 2 30;000
XT2p:u: ¼ ð0:10Þ ¼ 0:1378 per unit
120 20;000
which gives the same result. The line, which is located in zone 2, has a per-
unit reactance
Xline 2
Xlinep:u: ¼ ¼ ¼ 0:2604 per unit
Z base2 7:68
114 CHAPTER 3 POWER TRANSFORMERS
ZL 1 85
ZLp:u: ¼ ¼ ¼ 0:04340 85 per unit
Zbase 23:04
and
ZY 10 40
ZYp:u: ¼ ¼ ¼ 0:4340 40 per unit
Zbase 23:04
Also,
VbaseLL 480
VbaseLN ¼ pffiffiffi ¼ pffiffiffi ¼ 277 volts
3 3
and
Ean 277 30
Eanp:u: ¼ ¼ ¼ 1:0 30 per unit
VbaseLN 277
The per-unit equivalent circuit is shown in Figure 3.11. The per-unit line cur-
rent in phase a is then
FIGURE 3.11
Circuit for Example 3.5
116 CHAPTER 3 POWER TRANSFORMERS
3.4
THREE-PHASE TRANSFORMER CONNECTIONS AND
PHASE SHIFT