Interface Module XC: Protocol Converter / User Manual
Interface Module XC: Protocol Converter / User Manual
General
The Interface Module XC is designed for use with the EMH LZQJ-XC and DMTZ-XC
meters. The module is equipped with an M-Bus (2 wires) interface. The module can be plugged
easily into the module compartment of the meter. It can be mounted or exchanged during operation
(without breaking approval seal). An integrated M-Bus interface (Protocol Converter to DIN EN
13757-3) provides a simple means of connecting multi-energy meters. This makes multi-energy
applications an affordable proposition for domestic use. Due to the communication, the modules are
suitable for a lot of control centres.
Compatible meters
LZQJ-XC (special meter for industrial applications):
- Standard meter for direct connection
- Transformer connection version Cl. B (Cl. 1)
- Precision meter Cl. C (Cl. 0.5S)
- Precision meter Cl. 0,2S
DMTZ-XC (residential meter)
Functions
M-Bus interface (2 wires, passive) for bi-directional
communications;
Alternative: BFC-Bus (BAER Field Control, 56VDC);
Transmission protocol: M-Bus (DIN EN 13757-3:2013-08);
Internal communication interface for the transfer data
between the meter and the interface module (service data
list / table TS);
Protocol converter for meter data into M-Bus-Format
(non transparent data readout);
Internal power supply from meter;
Exchangeable during the meter operation;
Safety Notes
The owner of the interface modules is responsible that all persons engaged on
work with the modules:
• Are competent and qualified in accordance with national regulations (see ISSA
"Guideline for Assessing the Competence of Electrically Skilled Persons").
• Have read and understood the relevant sections of the user manual.
• Strictly observe the safety regulations (according to the following section) and
the instructions in the individual chapters.
The owner of the modules is also responsible for:
• The protection of persons.
• The prevention of material damage.
• The training of personnel.
The following safety regulations must be observed at all times:
• Devices which have fallen down should not be installed, even if no damage is apparent, and should
be returned for testing to an authorised service centre (internal damage possible).
• Modules must never be cleaned with running water or high pressure devices. Water can cause
short-circuits or damage el. components.
Page 2 from 12 Interface Module XC
E130506819092 Protocol Converter / User Manual
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
Installation Hints
The installation must be done in a way, that even in the case of cable break no dangerous voltages
are applied to touchable parts of the module. Generally, meters are delivered with the communication
modules installed. The fitting of a meter with a communication module is, therefore, an exception and
can be necessary e.g. when a module needs to be replaced.
Work on electrical installations and equipment may only be performed by adequately trained
qualified and in conformity with the applicable national rules and regulations.
Strictly observe the safety regulations!
The interface module is exchangeable during the meter operation. Fit the interface module in the meter
as follows:
LED Displays
Three LED’s display the current operating status of the module and give information about the data
transfer.
Status and communication via M-Bus interface:
Power/Tx
green LED signals, that the module is supplied with power
LED goes off during transmit data via M-Bus interface
Rx
yellow Communication via M-Bus interface: receive data
Baud rate
The Interface Module XC uses the same baud rate like the communication interface at the
meter. For setting use please the EMH COMBI-TOOL-Software:
Menu Meter Interfaces Electrical interface:
For correct working set please a fixed bad rate (e.g. 9600 baud). If you use the baud rate changeover
according to mode C: the communication is possible with 300 baud only. For the addressing set the
value “optionally” or “ignore”.
Note: In many M-Bus systems is the standard baud rate 2400 baud.
Reset
Note: The EMH LZQJ-XC meter performs automatically a daily reset at 00:00 in the interface module.
Page 4 from 12 Interface Module XC
E130506819092 Protocol Converter / User Manual
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
Note: The M-Bus module XC uses for ID-Addresses the OBIS Register 0.0.0 (secondary address)
and 0.0.1 (primary address) in the service data list TS.
In this example we use the identification number 1 (OBIS 0.0.1) for M-Bus primary address:
menu Meter Meter ID OBIS Register 0.0.1, e.g. value 123 (:= 00000123):
Further specifications:
The following definitions shall also apply for the selection of a new secondary address (SND_UD):
- the manufacturer code (15Hex A8Hex for “EMH”) will be evaluated, wildcard (FFHex FFHex) is possible;
- the version byte (Ver) will be ignored: all bytes are possible (e.g.: FFHex);
- the medium byte (02Hex for electricity) will be evaluated, wildcard (FFHex) is possible;
Data encryption is not allowed.
Max. telegram length: 252 bytes (max. ca. 30 values).
Support only for mode 1 (CI-Field): the least significant byte (LSB) of a multibyte record is
transmitted first.
Status byte: only bit 4 (“temporary error”) is used: internal communication error between the
modules and the meter.
Implementation of one FCB-Bit (Frame Count Bit) only (use either the primary or secondary
address).
Interface Module XC Page 7 from 12
Protocol Converter / User Manual E130506819092
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
Master: 10 7B 7B F6 16 (REQ_UD2: Request User Data with primary address: 123 = 7BHex)
Answer: 68 0F 0F 68 08 7B 72 87 98 16 04 A8 15 00 02 00 10 00 00 FD 16
(empty message)
Master: 10 5B 7B D6 16 (REQ_UD2: Request User Data with primary address: 123 = 7BHex)
Answer: 68 EA EA 68 08 7B 72 87 98 16 04 A8 15 00 02 01 00 00 00 04 03 C9 16
00 00 C4 05 03 6D 13 00 00 84 10 03 C2 10 00 00 C4 15 03 A8 0E 00 00
84 20 03 06 06 00 00 C4 25 03 C5 04 00 00 04 FB 82 73 90 03 00 00 C4
05 FB 82 73 06 02 00 00 84 10 FB 82 73 4A 02 00 00 C4 15 FB 82 73 54
01 00 00 84 20 FB 82 73 46 01 00 00 C4 25 FB 82 73 B1 00 00 00 04 2B
0C 00 00 00 04 AB FC 01 00 00 00 00 04 AB FC 02 00 00 00 00 04 AB FC
03 0C 00 00 00 04 FB 14 05 00 00 00 04 FB 94 FC 01 00 00 00 00 04 FB
94 FC 02 00 00 00 00 04 FB 94 FC 03 05 00 00 00 04 FD D8 FC 01 10 00
00 00 04 FD D8 FC 02 0E 00 00 00 04 FD D8 FC 03 13 03 00 00 04 FD C7
FC 01 3E 00 00 00 04 FD C7 FC 02 38 00 00 00 04 FD C7 FC 03 30 59 00
00 04 FB 2D 87 13 00 00 0C 16 (RSP_UD: Respond User Data)
Page 8 from 12 Interface Module XC
E130506819092 Protocol Converter / User Manual
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
Technical data
Housing: Polycarbonate housing with terminals for using with EMH LZQJ-XC and
DMTZ-XC meters for residential and industrial applications
Protection class: 2
Battery: None
Dimensions
Interface Module XC Page 11 from 12
Protocol Converter / User Manual E130506819092
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
Terminal assignment
Terminal block:
Terminal Description
a M-Bus (passive) or BFC-Bus
b M-Bus (passive) or BFC-Bus
Page 12 from 12 Interface Module XC
E130506819092 Protocol Converter / User Manual