0% found this document useful (0 votes)
71 views4 pages

Project Name: Project Number:: EXTERIOR (Insert Pipe Type)

This document contains calculations for the sizing of water piping for an exterior and interior system. It lists pipe sections, sizes, lengths, and equivalent lengths to calculate total pressure losses. Fittings including elbows, tees, and valves are also accounted for. The available pressure and pressure losses are calculated and compared to determine if the design meets requirements.

Uploaded by

John A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views4 pages

Project Name: Project Number:: EXTERIOR (Insert Pipe Type)

This document contains calculations for the sizing of water piping for an exterior and interior system. It lists pipe sections, sizes, lengths, and equivalent lengths to calculate total pressure losses. Fittings including elbows, tees, and valves are also accounted for. The available pressure and pressure losses are calculated and compared to determine if the design meets requirements.

Uploaded by

John A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

PROJECT NAME:

PROJECT NUMBER:
TOTAL
EQUIVALEN
QUANTIT SIZE OF LENGTH EQUIVALEN
SECTION GPM T LENGTH
Y PIPE (FT) T LENGTH
(FT)
(FT)
EXTERIOR (Insert Pipe Type)
SUPPLY PRESSURE 1000.00
STATIC HEAD
INTERNAL PIPING LOSS AB 2 2 500.00 50.00 100.00
BC 1 2 500.00 50.00 50.00
CD 1 2 500.00 50.00 50.00
DE 1 2 500.00 50.00 50.00
EF 1 2 85.00 50.00 50.00
FG 1 2 85.00 50.00 50.00
HI 1 2 85.00 50.00 50.00
FITTINGS 90 ELBOW 5 2 500.00 10.00 50.00
45 ELBOW 1 2 500.00 5.00 5.00
BRANCH TEE 1 2 500.00 20.00 20.00
RUNNING TEE 1 2 500.00 10.00 10.00
VALVES 1 2 500.00 25.00 25.00
TOTAL PRESSURE LOSS

SUCTION PRESSURE

INTERIOR (insert pipe type)


STATIC HEAD
HIGHEST/FURTHEST FIXTURE 1 3/4 25.00
INTERNAL PIPING LOSS AB 1 2 75.00 100.00 100.00
BC 1 2 75.00 25.00 25.00
CD 1 1 50.00 50.00 50.00
503883534.xls 12/21/2020
DE 1 1 50.00 25.00 25.00
EF 1 3/4 50.00 50.00 50.00
FG 1 3/4 50.00 25.00 25.00
HI 1 3/4 25.00 25.00 25.00
FITTINGS 90 ELBOW 5 2 75.00 10.00 50.00
2 1 50.00 8.00 16.00
45 ELBOW 2 2 75.00 5.00 10.00
2 1 50.00 4.00 8.00
BRANCH TEE 3 2 75.00 20.00 60.00
2 1 50.00 15.00 30.00
RUNNING TEE 2 2 75.00 10.00 20.00
1 1 50.00 8.00 8.00
VALVES 5 2 75.00 25.00 125.00
3 1 50.00 18.00 54.00
METER 1 2 75.00
RPZ 1 2 75.00
PRV 1 2 75.00
TOTAL PRESSURE LOSS

PRESSURE:
EXCESS (PUMP)

503883534.xls 12/21/2020
BY:
DATE:
PRESSURE
PRESSURE AVAILABLE
LOSS PER HEIGHT PSI/FT
LOSS PRESSURE
100 FEET

100.00
5.00 0.43 2.17
5.02 5.02
5.02 2.51
5.02 2.51
5.02 2.51
5.02 2.51
5.02 2.51
5.02 2.51
5.02 2.51
5.02 0.25
5.02 1.00
5.02 0.50
5.02 1.26
27.77

72.23

10.00 0.43 4.33


25.00
5.02 5.02
5.02 1.26
3.78 1.89
503883534.xls 12/21/2020
3.78 0.95
2.10 1.05
2.10 0.53
2.10 0.53
5.02 2.51
4.20 0.67
5.02 0.50
4.20 0.34
5.02 3.01
4.20 1.26
5.02 1.00
4.20 0.34
5.02 6.28
4.20 2.27
5.00
5.00
5.00
73.72

(1.48)

503883534.xls 12/21/2020

You might also like