0% found this document useful (0 votes)
178 views24 pages

User Guide CAN-Box - Ed02

Uploaded by

Segey
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
178 views24 pages

User Guide CAN-Box - Ed02

Uploaded by

Segey
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Elektronikon®

MkIV

Atlas Copco Elektronikon Systems


Interface: CAN-Box
Part number: 1900 0712 61

Name Elektronikon systems Serc. Class


Detail Interface: CAN-Box 1102 K/1
Detail PC Owner
Edition: 02 Modified from Print date AII

Family Written by Compare Replaces Designation


CTE.-RVDS 01
Design checked. Production checked. Approved Date 9820 4547 08
16/10/2007

1
INDEX

1. Document Information ....................................................................................................... 3


2 Safety precautions ................................................................................................................... 4
2.1 Safety icons ...................................................................................................................... 4
2.2 Safety precautions during installation .............................................................................. 4
2.2.1 General precautions................................................................................................... 4
2.2.2 Precautions during installation .................................................................................. 4
2.3 Safety precautions during operation................................................................................. 5
2.3.1 General precautions................................................................................................... 5
2.3.2 Precautions during operation..................................................................................... 5
2.4 Safety precautions during maintenance or repair ............................................................. 6
2.4.1 General precautions................................................................................................... 6
2.4.2 Precautions during maintenance or repair................................................................. 6
3 Preface..................................................................................................................................... 7
4 General Description................................................................................................................. 7
4.1 Introduction ...................................................................................................................... 7
4.2 General view .................................................................................................................... 8
5 Hardware installation .............................................................................................................. 9
5.1 Hardware connections ...................................................................................................... 9
5.1.1 Digital inputs ............................................................................................................. 9
5.1.2 Relay Outputs............................................................................................................ 9
5.1.3 Principal connection drawing.................................................................................. 10
6 Programming the CAN-Box via FDP ................................................................................... 11
7 Testing the hardware connections ......................................................................................... 12
7.1 Control mode.................................................................................................................. 12
7.1.1 Test control mode.................................................................................................... 12
7.1.2 How testing the hardware connections?.................................................................. 13
7.1.3 LAN control mode .................................................................................................. 14
8 Display specifications ........................................................................................................... 15
8.1 Main screen .................................................................................................................... 15
8.2 Inputs & Status indications ............................................................................................ 15
8.3 Description of the display icons ..................................................................................... 16
8.4 Data read-out .................................................................................................................. 16
8.5 Data registers.................................................................................................................. 17
8.6 Parameters ...................................................................................................................... 18
8.7 How to modify the parameters? ..................................................................................... 19
9 Addendum ............................................................................................................................. 20
9.1 Analogue Inputs ............................................................................................................. 20
9.1.1 Create an analogue Temperature Input ................................................................... 21
9.1.2 Create an analogue Pressure Input .......................................................................... 22
9.1.3 Creating an Service Warning on an analogue input................................................ 23
REMARK: adding protection functions on analogue inputs is NOT supported! ................ 23
9.2 Relay contacts ................................................................................................................ 24
K01: Start ......................................................................................................................... 24
K02: Compressor stop...................................................................................................... 24
K03: Compressor load/unload.......................................................................................... 24
K04 : Local/Central control.............................................................................................. 24
K05/K06 : Optional use for Service / Warning / Shutdown indication ........................... 24

2
1. Document Information

Edition Date Description Author

00 22/09/2006 First edition CTE-PVL


01 26/01/2007 Principal connection drawing updated CTE-PVL
02 16/10/2007 Complete update user guide CTE-RVDS

3
2 Safety precautions

2.1 Safety icons

Explanation

Danger for life

Warning

Important note

2.2 Safety precautions during installation

All responsibility for any damage or injury resulting from neglecting these precautions,
or non-observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

2.2.1 General precautions


1. The operator must employ safe working practices and observe all related local work safety
requirements and regulations.
2. If any of the following statements does not comply with local legislation, the stricter of the
two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorized,
trained, specialized personnel.
4. Before carrying out any maintenance, repair work, adjustment or any other non-routine
checks, stop the device. In addition, the power isolating switch must be opened and locked.

2.2.2 Precautions during installation


1. Place the device where the ambient air is as cool and clean as possible.
2. During installation or any other intervention on one of the connected machines, the
machine must be stopped, de-energized and the isolating switch opened and locked
before any maintenance or repair. As a further safeguard, persons switching on remotely
controlled machines shall take adequate precautions to ensure that there is no one
checking or working on the machine. To this end, a suitable notice shall be affixed to the
start equipment.
3. The electrical connections must correspond to the local codes. The device must be
earthed and protected against short circuits by fuses in all phases. A lockable power
isolating switch must be installed near the device.
4. For machines controlled by a central control system, a sign stating "This machine may
start without warning" must be affixed near the instrument panel.
5. In multiple compressor systems, manual valves must be installed to isolate each
compressor. Non return valves (check valves) must not be relied upon for isolating
pressure systems.
6. Never remove or tamper with the safety devices.

4
Also consult following safety precautions: Safety precautions during operation and
Safety precautions during maintenance or repair.
These precautions apply to electrical devices.
For precautions applying to the connected equipment consult the relevant instruction
book.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your device.

2.3 Safety precautions during operation

All responsibility for any damage or injury resulting from neglecting these precautions,
or non-observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

2.3.1 General precautions


1. The operator must employ safe working practices and observe all related local work
safety requirements and regulations.
2. If any of the following statements does not comply with local legislation, the stricter of the
two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by
authorized, trained, specialized personnel.
4. Before carrying out any maintenance, repair work, adjustment or any other non-routine
checks, stop the device. In addition, the power isolating switch must be opened and
locked.

2.3.2 Precautions during operation


1. Persons switching on remotely controlled machines shall take adequate precautions to
ensure that there is no one checking or working on the machine. To this end, a suitable
notice shall be affixed to the remote start equipment.
2. Never operate the device in the presence of flammable or toxic fumes, vapours or
particles.
3. Never operate the machine below or in excess of its limit ratings.
4. Keep all bodywork doors and panels closed during operation. The doors may be opened
for short periods only, e.g. to carry out routine checks. Wear ear protectors when opening
a door if applicable.
5. People staying in environments or rooms where the sound pressure level reaches or
exceeds 90 dB(A) shall wear ear protectors.
6. Periodically check that:
• All guards and fasteners are in place and tight
• All hoses and/or pipes are in good condition, secure and not rubbing
• There are no leaks
• All electrical leads are secure and in good order
7. Never remove or tamper with the safety devices.

Also consult following safety precautions: Safety precautions during installation and
Safety precautions during maintenance or repair.
These precautions apply to electrical devices.
For precautions applying to the connected equipment consult the relevant instruction
book.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

5
2.4 Safety precautions during maintenance or repair

All responsibility for any damage or injury resulting from neglecting these precautions,
or non-observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

2.4.1 General precautions


1. The operator must employ safe working practices and observe all related local work
safety requirements and regulations.
2. If any of the following statements does not comply with local legislation, the stricter of the
two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by
authorized, trained, specialized personnel.
4. Before carrying out any maintenance, repair work, adjustment or any other non-routine
checks, stop the device. In addition, the power isolating switch must be opened and
locked.

2.4.2 Precautions during maintenance or repair


1. Use only the correct tools for maintenance and repair work.
2. Use only genuine spare parts.
3. A warning sign bearing a legend such as "work in progress; do not start" shall be
attached to the starting equipment, including all remote start equipment.
4. Persons switching on remotely controlled machines shall take adequate precautions to
ensure that there is no one checking or working on the machine. To this end, a suitable
notice shall be affixed to the remote start equipment.
5. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety
precautions against toxic vapors of cleaning liquids.
6. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by
covering the parts and exposed openings with a clean cloth, paper or tape.
7. Never use a light source with open flame for inspecting the interior of the device.
8. All regulating and safety devices shall be maintained with due care to ensure that they
function properly. They may not be put out of action.
9 Before clearing the device for use after maintenance or repair, check that operating
pressures, temperatures and time settings are correct. Check that all control and shut-
down devices are fitted and that they function correctly.
10. Never use caustic solvents which can damage materials of the air net.

Also consult following safety precautions: Safety precautions during installation and
Safety precautions during operation.
These precautions apply to electrical devices.
For precautions applying to the connected equipment consult the relevant instruction
book.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

Units and/or used parts should be disposed of in an environmentally friendly and safe
manner and in line with the local recommendations and legislation.

6
3 Preface
This document is an Instruction Book which can help you with the installation and commissioning
of an Elektronikon Interface “the CAN-Box”.
This CAN-Box can be ordered with the part number: 1900 0712 61

4 General Description
This document describes the required hardware and the functionality of the ‘newest generation’
interface box for Electro Pneumatic compressors towards Elektronikon® Central Controllers, like MCC
ES4i) and ES-Millennium versions.

4.1 Introduction

The CAN-Box is a stand-alone interface, packed in a compact metal housing and foreseen to be
mounted on a DIN-rail.

The CAN-Box requires a 24Vac (-30% to +40% allowed) or a 24Vdc voltage as a power supply.

7
4.2 General view

6
2
4

7
5 3

13 14 15

8 9
11
10 12

1 Start button
2 Stop button
3 Enter button
4 Reset button
5 Arrows up or down buttons
6 Display
7 LAN connection
8 Digital inputs and supply
9 Analogue inputs (1 Pressure + 2 Temperatures)
10 Grounding
11 Shielded grounding
12 Digital outputs (voltage free relay output contacts (10A max)
13 Automatic operation LED
14 Warning LED
15 Power LED

8
5 Hardware installation

5.1 Hardware connections

5.1.1 Digital inputs

Æ Connector 2X9.

On connector 2x9, besides the power supply that is required, 3 Digital inputs and the DC supply for
these digital inputs (connected digital input contacts must be voltage-free) are present.

The following Functions are attached for the 3 Digital inputs by default.

Input Function Normal Input open Input closed


position
DIO1 Compressor running status Open Motor Motor
stopped running
DIO2 Compressor (un)load status Open Unloaded Loaded

DIO3 General Shutdown indication Closed Shutdown Normal

If no shutdown feedback from


the compressor is available;
input must be closed by wired
bridge.

5.1.2 Relay Outputs

Æ Connector 2X10.

Connector 2x10 is providing 6 voltage –free digital outputs (10 A max)


Remark: There is only a common and a normal open contact for each digital output. If normal
closed contact are required auxiliary relays must be used.

Output Function De-energized Energized


K01 Compressor start - Start

K02 Compressor stop - Stop

K03 Compressor load Unload Load

K04 Local / Central control Local Central

K05 Optional
K06 Optional

9
5.1.3 Principal connection drawing

Compressor CAN-Box Interface

K1. Blocking relay K01 Start relay


K3. Reset relay K02 Stop relay
K10. Time relay, delayed motor stopping K03 Load/Unload relay
P. Air pressure switch K04 Local/remote control relay.
S1. Start push button
S2. Stop push button Auxiliary Relays’
Y. Loading solenoid valve Kx1 & Kx2. Relays
St. Motor starter

10
6 Programming the CAN-Box via FDP

Power up the CAN-Box, and connect to the PC via a CAN download cable.
Check the CAN address of the CAN-Box:
The address is shown at power up after lighting up all icons.
If the module was already downloaded before, afterwards you have to scroll down from the main
screen to P02; press <Enter> and the actual Node ID is shown and can be modified (by default 31).

To download the module use the latest FDP version (Field Download Program) – can be downloaded
from the Lotus Notes Elektronikon Software database. Also use the latest database for
Communication Interfaces.
Select the model CANBOX and enter the serial number and generate a GUID, no other parameters
must be selected.

11
7 Testing the hardware connections

7.1 Control mode


Two basic control modes exist: Test control mode and LAN control.
These modes have two sub-modes: local and remote pressure sensing
By default the controller is in local test control mode.

7.1.1 Test control mode


The main screen is the test mode screen.

This mode is derived from the ‘local control’ mode and is specific for the CAN-Box to allow the
operator to check if the system is properly wired.
Using the display/keyboard, the operator can check the results upon all supported commands.
Remark: Start/Stop commands are executed in local test mode with respect of some timers (Minimum
Stop Time, Programmed Stop Time).
The commands are only executed if first the compressor is switched to the remote pressure sensing
mode.

12
7.1.2 How testing the hardware connections?

Step 1
Press the enter button → LAN icon is
blinking (Remote Pressure sensing mode)

Step 2
Press the start button → Motor is running
unload. The start command is only executed
after the minimum stop time is elapsed.

screen is changed ===Î!!!!!!!!


Step 3
Press the reset button to switch to load. The
load command is only executed after the load
delay is elapsed.

Step 4
Press the reset button again to switch to
unload.

Step 5
Press the stop button, compressor will run
unload until programmed stop time is
elapsed; then stop pulse will generated and
motor should stop.

Step 6
When the compressor is not available due to
a shutdown or any other reason, input Di03
should be opened. The CAN-Box will
indicate this status and the display show the
flashing shutdown icon and the shutdown
LED will also flash.

If one of the steps causes problems, hardware connections must be checked. After a
successful procedure, you can continue with the following chapter.

13
7.1.3 LAN control mode

Manually the controller must be put in LAN control mode; no external LAN commands are accepted in
local test mode.

From this moment on, the central controller can take over the control of the machine by steering it to
remote pressure sensing and revert to local if necessary by steering to local pressure sensing.

In the remote pressure sensing mode start/stop and load/unload commands can be sent by the central
controller over the CAN communication channel.

14
8 Display specifications

8.1 Main screen

By default there will be no analogue measurements, therefore the main screen will only show
the actual status of the compressor (Vessel & arrows icon).

When the pressure input is activated, it will be shown also on the main screen.

When the shut down input is opened, the Emergency Stop icon will blink. When a service is
triggered the service icon will blink.

The LAN icon will steady when the LAN control mode is active, it will not be visible in local
TEST control mode.

8.2 Inputs & Status indications

Special indications on main screen

Optional pressure
reading

Optional: Overpressure
safety (unload arrow &
bar
Vessel blinking)

Shutdown
input open

Service
triggered

Shut down input is open => Warning LED is blinking


Warning triggered => Warning LED is steady lit
CENTRAL control mode active => Automatic operation LED is steady lit
LAN icon steady lit => LAN control mode active

15
8.3 Description of the display icons

DISPLAY ICON Description Remarks

Shutdown When input Di03 is open => icon and


shutdown LED blinking
Motor running
Arrows are only shown when motor is
Load / Unload running

Service warning Icon shown (blinking) when a service is


triggered

LAN Control Icon shown when Canbox in LAN


Control mode

Value + MPa/psi/bar/ Pressure input OPTIONAL, only when pressure input is


active
Value + °F/°C First Temperature OPTIONAL, only when input is active
input

Value + °F/°C Second Temperature OPTIONAL, only when input is active


input
Warning triggered Warning LED steady lit

8.4 Data read-out

Other data
Measurements
Scroll list of analogue/digital measurements, starting from main screen
• main screen: always pressure reading (if defined)
• First temperature input (if defined)
• Second temperature input (if defined)
• Digital inputs (status of 3 inputs given in one screen)

16
8.5 Data registers.

Scroll list starting from main screen, after the analogue /digital inputs

ID + Number Icon lit Description


D. 01 Amount of hours the machine is running load or unload,
according to the feedback signal – digital input D01.
Running hours

D. 02 This function counts the number of motor starts (according


to the feedback signal from the compressor – digital input
D01)
The contents of this counter can also be programmed via
the external communication in order to allow exchange of
Motor starts counter modules or motor. The contents of this counter can only
be read out via the external communication line.
The initial value of this counter for a new controller
will be 0.
D. 03 The Module Hours Counter is a special application of the
Hours Counting Function.
The hours are counted continuously and without
interruption. The presence of supply power triggers the
counter.
Module hours
hrs The initial value for the Module Hours Counter is 0. The
Module Hours Counter cannot be reset.
The output of the Module Hours Counter is the number of
module hours, i.e. the number of hours the module has
been powered.

D. 04 Amount of hours the digital group is running load,


Running Loaded according to the feedback signal – digital input D02.
hours hrs
D. 05 Amount of switches of the load-Output-Relay, only
the transitions from de-energized to energized
Load relay counter situation of the K03 relay are counted.
D. 06 Service icon shows on the screen
After pressing the enter button the actual running hours
Service counter
are shown on the screen.
service icon
D. 07 After pressing the enter button, the last 4 digits of the
program version shows on the screen e.g. 4126
Program version

17
8.6 Parameters
Scroll list starting from main screen, after the analogue inputs and counters

ID + Number Icons Description


P. 01 Change the mode from Local to LAN network.
Controller Control
Mode (Local / LAN)
P. 02 Change the node ID or CAN address
Node ID
P. 03 Show the service icon and the
Service counter hrs for the next service
settings

P. 04 Change the temperature unit from °C to °F


°C °F
Temperature unit
P. 05 Change the unit of the temperature in MPa, psi or bar
Pressure unit MPa psi bar

P. 06 Change the start method: Y-d, doL


Start method (DOL
/ Y-D)

P. 07 Change the maximum allowed number of motor starts /


Nr starts/day day.

P. 08 Change the Y-time (only applicable for start method Y-D)


Y-time
S

P. 09 This is the absolute minimum time in seconds between the


moment that the full power is applied to the motor start
Load delay
S and the first loading of the compressor

P. 10 Time during which a compressor has to remain running


unloaded or must have been running unloaded before the
motor can be stopped.
Progr. Stop Time
S

P. 11 This is the absolute minimum time in seconds that the


motor power has to be left switched off, before it can be
switched on again.
Minimum Stop Time
S
P. 12 Whenever this time is elapsed without receiving
requests/commands from a central controller via the CAN
Comm. Timeout S communication, the CAN-Box will revert to local pressure
sensing mode.
P. 13
Activate / De-activate a password system
(No icon)
Password status

18
8.7 How to modify the parameters?
(Example change the temperature indication from °C to °F)
Use the arrow up or down key to scroll to the next screen.

Press the enter button 2 times, the actual temperature indication is blinking.

Use the arrow up or down key to change the indication in “°F”.

Confirm by pressing the enter button.


Press the reset button to go back to previous screen.

Remarks:
• Other Parameters can only be changed between the minimum/maximum limits. When
minimum, actual and maximum are equal the setting can not be modified.
• Restart delay can not be seen/modified via display (only using Commissioning & Service
Software - FSP)

19
9 Addendum

9.1 Analogue Inputs

Æ Connector 2X5.

This connector provides 2 temperature inputs (Pt1000) and 1 pressure input (for Kavlico type
transducers).
By using the Field Service Program (FSP) the inputs can be activated. By default they are not active.

Note:
Take into account that, if the analogue inputs are activated, they can be used for monitoring purpose
only!
However, an additional protection “Unload due to overpressure” can be installed using a pressure
sensor with the Identification number 509 (ID=509). If configured (FSP program) this way, the
compressor will be forced to Unload condition based upon the overpressure setting parameters.

20
9.1.1 Create an analogue Temperature Input

First open FSP → open Temperature Inputs.


Click right on the PT 1000 input; choose Add Function → From Pointlist.

Select Ambient Air (Function ID 1000) from the list and click ok.

In the new recipe, fill in following fields.


• Language 1.
• Language 2.
• Language 3.
• Status is only set as
an option.
• Range (must be
between -40°C to
340°C).
• Display Format
(change the number
of displayed
decimals).

If the Language field is


empty,
The following warning will
be shown on the FSP screen.

Close the recipe and save the configuration.


The display of the CAN-Box
shows following screen.

21
9.1.2 Create an analogue Pressure Input
First open FSP → Pressure Inputs
Click right on the Kavlico input; choose Add Function → From Pointlist.

Choose for Compressor Outlet


• Language 1.
• Language 2.
• Language 3.
• Status is only set as
an option.
• Range (must match
with connected
transducer e.g. from
0 to 17 Bar).
• Display Format
change the number of
displayed decimals).

If the Language field is


empty,
The following warning will
be shown on the FSP screen.

Close the recipe and save the configuration.

The display of the CAN-Box


shows following screen.
t is shown while the CAN-
Box is in test control mode

22
9.1.3 Creating an Service Warning on an analogue input

Open FSP
Click right on a PT 1000 Temperature Input, choose Add function → Service

Fill in this new recipe


• Choose between Low Level and High Level.
(When selected Low Level, warning LED shows if temperature is below 100°C if the
warning Level set as 100°C).
(When selected High Level, warning LED shows when temperature is higher then
100°C if the warning Level set as 100°C).
• If only a warning is needed select “Warning only”.
• Select Stop, Unload en load.
• Fill in the minimum and maximum levels.
• The warning level must be between Minimum and Maximum.

REMARK: adding protection functions on analogue inputs is NOT supported!

23
9.2 Relay contacts

K01: Start
The relay contact will be switched during 3 seconds after receiving and acknowledging a compressor
start command.
A start command will not be executed within the minimum stop time. The start command will be stored
however and will be executed after the minimum stop time is elapsed.
Start and (un)load commands during the programmed stop can be acknowledged as long as the motor
is still running. The stop procedure will be interrupted and compressor will run automatically (un)load
again. A start command can never be acknowledged if the compressor general shutdown contact is
open.

K02: Compressor stop


The relay contact will be switched during 3 seconds after receiving and acknowledging a compressor
stop command.
The K03 (compressor load/unload) relay contact will be de-energized after receiving and
acknowledging a programmed stop command; the stop pulse will be generated after elapsing the
programmed stop counter.

K03: Compressor load/unload.


After a (un)load command the load/unload relay can only be switched when the compressor running
contact is closed, i.e. when the compressor is running in remote control mode.
Conditions after a start procedure: compressor is running and the compressor start time (Y-time & load
delay time) must be elapsed.
The relay contact will be put in its normal, de-energized position by a compressor unload command.
The relay contact will be put in its energized position by a load command.
Special algorithm: the output will reflect the feedback signal, when there is no command executed and
the digital load/unload input changes, the output will be steered according to the input.
In remote control mode b.or d. (K04 is energized):
if the digital input is motor running (Di01=closed) the steering of the output follows the feedback input:
When Di02 is open K03 is de-energized
When Di02 is closed K03 is energized
If the motor is stopped (Di01=open) K03 is always de-energized
In local control mode a. (K04 is de-energized) the output K03 is always energized.

K04: Local/Central control


The relay will be in the normal, de-energized position for the local control condition.
The relay has to be energized for remote (central) control condition.
In the local control mode the relay will be energized only when the CAN-Box receives the remote
control command. The interface can never decide to switch to remote control under its own initiative.
The interface will take the decision to return to local control mode if under LAN remote control mode,
the CAN-Box receives no communication signals during the communication failure timeout.
if the local control command is received the AN-Box will revert to local pressure sensing mode.

K05/K06: Optional use for Service / Warning / Shutdown indication


The functionality is determined by measurement point number.
Shutdown: output de-energized. (The shutdown function can only be triggered by opening Di03)
Warning: output de-energized when warning is triggered (only possible on an optional analogue input)
Service: output energized when service is triggered (possible on an optional analogue input or based
on service plan)

24

You might also like