Chillers, AHU, RTU How They Work - The Engineering Mindset
Chillers, AHU, RTU How They Work - The Engineering Mindset
In this article we will be looking at how chillers, AHU’s and RTU’s work together, the
difference between them and the basic working principles behind each of them.
Chillers, Air Handling Units and Rooftop units are used extensively within HVAC
systems for commercial properties. You can watch the video on this article by
scrolling to the bottom!
If you’re looking for high quality refrigeration components and solutions, then I
recommend checking out what Danfoss has to offer. Danfoss has a wide variety of air
conditioning solutions available for Chillers, Air Handling Units (AHU’s) and Rofftop
Units (RTU’s). Their parts portfolio includes compressors, heat exchangers, drives,
electronics and sensors, valves, and system protectors, all designed to help you boost
efficiency and bring your systems in line with current and future refrigerant
regulations. Learn more about Danfoss air conditioning solutions at
http://www.airconditioning.Danfoss.com
Chillers
https://theengineeringmindset.com/chillers-ahu-rtu-work/ 1/8
10/22/2020 Chillers, AHU, RTU How they work - The Engineering Mindset
Chillers are used to generate chilled, or cold, water which is pumped around the
building to provide air conditioning by collecting unwanted heat.
There are two main types of chillers, Air cooled and Water cooled. The term “Air” or
“Water” cooled just tells the engineer how the chillers condenser is rejecting heat from
the building.
Water cooled chillers are typically located in the basement or lowest floor of a building.
This type of chiller needs a cooling tower to reject the heat from the building. The
chiller produces chilled water and pushes this around the building to Air Handling Units
(AHU’s) and Fan Coil Units (FCU’s) etc. These units circulate air around the local space
as well as the building. The air is forced across heat exchangers, containing the chilled
water, which extracts the unwanted heat before the air is distributed throughout the
building.
https://theengineeringmindset.com/chillers-ahu-rtu-work/ 2/8
10/22/2020 Chillers, AHU, RTU How they work - The Engineering Mindset
The unwanted heat, that is extracted from the air, collects in the chilled water loop.
This loop circulates back to the chiller and once it reaches the evaporator, the
unwanted heat will be transferred over to the chillers condenser via a refrigerant loop.
The condenser absorbs this heat and then dumps it into the “condenser water” loop
which runs between the chillers condenser and the cooling tower. The cooling tower
will force ambient air across the condenser water to extract the unwanted heat. The
fan within the cooling tower forces this heat to leave the system, and building, and is
ejected into the atmosphere. In this instance the condenser of the chiller has been
cooled by water so it is a water cooled chiller.
Water cooled chillers are typically used on large commercial properties with high
cooling loads, you can tell if a building has a water cooled chiller because it will need
cooling towers which are typically on the roof. There will usually be more than 1 chiller
and cooling tower, its not uncommon to have at least 2 or 3 or even more just for
redundancy as well as variations in cooling demand.
https://theengineeringmindset.com/chillers-ahu-rtu-work/ 3/8
10/22/2020 Chillers, AHU, RTU How they work - The Engineering Mindset
Air cooled chillers are typically located on the roof of the building or outside e.g. in the
car park. Air cooled chillers also generate chilled water which is pumped around the
building to air handling units as well as other apparatus such as fan coil units etc. This
is to cool the building down by picking up unwanted heat.
The air is forced to circulate around the building, and local space, and will pass across
heat exchangers within the AHU and FCU’s. This unwanted heat is again transferred
over to the condenser of the chiller from the evaporator. It is transferred via a
refrigerant which loops continuously between the evaporator and condenser and is
forced by the compressor. The difference with this type of chiller is that a fan blows air
over the condenser which removes the heat. So in this instance the condenser of the
chiller has been cooled by air, therefore it is an air cooled chiller.
https://theengineeringmindset.com/chillers-ahu-rtu-work/ 4/8
10/22/2020 Chillers, AHU, RTU How they work - The Engineering Mindset
Air cooled chillers are typically located outside because they need access to a lot of
ambient air in order to reject the heat. This type of chiller can usually be found on
medium to large commercial properties.
These two system both serve a very similar purpose and can look fairly alike. Both of
these are used to distribute air around the building and will contain fans to achieve
this. They will both take in fresh ambient air and clean this through a filter before
heating or cooling the air to suit the demands within the building. The main difference
between the two is how the air is heated or cooled and we’ll look at each of these to
learn the basics of how the work.
https://theengineeringmindset.com/chillers-ahu-rtu-work/ 5/8
10/22/2020 Chillers, AHU, RTU How they work - The Engineering Mindset
AHU in building
Air handling units are also referred to as AHU’s for short. AHU’s are typically located
inside the building although you can also find these within rooftop plant rooms and its
becoming more common to find robust, weather tight, AHU’s sitting out in the open on
the roof, to free up valuable space inside the building. Their purpose is to distribute air
around defined areas within the building.
Sometimes one AHU will supply the whole building but its common in newer buildings
to have multiple smaller AHU’s feeding different parts to provide a better indoor
environment as well as energy savings. AHU’s typically do not have their own cooling
system built in, instead they will be connected to a central plant water or air cooled
chiller, occasionally they will use some sort of split a/c unit and you can also find these
connected to district cooling networks.
AHU’s are connected to duct work which provides a defined route for the air to travel
around the building. In a simple form, an AHU will use a fan to suck in fresh ambient
outside air which will then pass through some filters to remove any dirt and dust. It
will then pass through the cooling and heating coil heat exchangers which, as
discussed, are typically fed from central plant units. Once the air has passed over
these coils it will be pushed out around the building. Another set of duct work will be
collecting the warm used air from the rooms and will bring this back to the AHU via
another fan. This fan will then eject the air from the AHU and building.
https://theengineeringmindset.com/chillers-ahu-rtu-work/ 6/8
10/22/2020 Chillers, AHU, RTU How they work - The Engineering Mindset
RTU on roof
These units are always located on the roof, as the name suggests. They are very
common in shops and small commercial properties and are popular because they are
simple, compact, self contained, all in one HVAC units. Their purpose is to distribute
conditioned air around define areas within a building. RTU’s are also connected to duct
work which provides a defined route for the conditioned air to travel along. RTU’s
typically have their own inbuilt refrigeration system to provide cooling only, but they
can also contain a heat pump or a separate heat source such as gas fired heater.
RTU’s house all the components within the rooftop unit. This contains a number of
dampers to control the flow of air and can allow air re circulation, if conditions are
right. The unit will also contain filters, to clean the air, as well as heating and cooling
coils and at least 1 central fan. The refrigeration system is also connected, typically to
the back or side, to control the temperature.
The fresh ambient air is sucked in via the fan and passes across the dampers. It then
passes through the filters to remove any dust and dirt before its temperature is
adjusted in the heat exchanger. The fan then pushes this out into the building to
condition the space. Another duct will collect the warm used air from the rooms and
will distribute this back to the rooftop unit where it will be ejected or recirculated, if
that option is available and conditions are right.
https://theengineeringmindset.com/chillers-ahu-rtu-work/ 7/8
10/22/2020 Chillers, AHU, RTU How they work - The Engineering Mindset
[vc_video link=”https://youtu.be/UmWWZdJR1hQ”]
Paul Evans
http://www.TheEngineeringMindset.com
https://theengineeringmindset.com/chillers-ahu-rtu-work/ 8/8