Typical Cable Sizes For DG Sets (Ref. M.7) : kVA Rating Amp Rating Cable Size Sq. Mm. X Runs
Typical Cable Sizes For DG Sets (Ref. M.7) : kVA Rating Amp Rating Cable Size Sq. Mm. X Runs
7)
Notes :
1. Use 3-1/2 core armored power cables with aluminium conductor. (AYFY)
2. Current rating of cables are taken based on operating temperature of 70o C.
3. For multiple runs of cables deration factor of 0.75 is considered i.e. 25% deration applied.
4. AYFY : Aluminium conductor, PVC insulation, Steel strip armour, PVC outer sheath.
5. Cable sizes mentioned are in square mm.
6. For sets above 1000 kVA use of proper busbars in bus ducts is recommended.
7. Earthing as per IEC rules to be provided.