The new DC-isolated xi-series.
f u l l o f e n e r g y.
For the Operator
Operator’s Instructions
Powador 1501xi / 3501xi / 4501xi
General Remarks
With the inverter manufactured by KACO Gerätetechnik Note!
GmbH you have purchased a device that excels by Useful information and remarks!
highly reliable and powerful technology. You will benefit
from our long-standing experience in the field of current
inverter technology and power electronics.
Important!
Powador 01xi inverters are electrically isolated, robust Non-adherence to these
inverters, which are operated without any blowers and instructions may adversely affect
offer a high degree of efficiency. An illuminated display the operating convenience or
and intuitive menu guidance enables you to display the functionality of the device.
most important grid feeding data of the inverter. The
inverter data can be transmitted to a PC for
visualization.
This symbol designates a required
Protection class IP 54 makes the inverters ready for use action
in any kind of environment – our inverters are even
suitable for use in agricultural and industrial
applications. 1.3 CE Certification
CE labeling is used to document that the Powador
inverter indicated on the type label meets the
1 About this document fundamental requirements according to the following
The following information will guide you through the directives:
entire operator’s manual. Further documents will be - Directive concerning Electromagnetic Compatibility
valid in conjunction with these operating and installation with Class B (Council Directive 89/336/EWG)
instructions. - Low Voltage Directive (Council Directive 73/23/EWG)
We shall not be liable for any damage caused by
non-adherence to the instructions given in this 1.4 Type Label
manual. The type label indicating the exact device description is
located on the support plate at the underside of the
Pertaining documents enclosure.
During the inverter installation please observe all
assembly and installation instructions for components 2 Safety information and
and other parts of the system. These instructions are
shipped together with the respective installation instructions
components or supplementary equipment.
Danger!
1.1 Attachment and Maintenance of documents Danger due to lethal voltages!
Please keep these operating and installation Hazardous live voltages are present
instructions in a safe place to ensure that they are inside the device/instrument and power
available if needed. Danger lines. Therefore, the device/instrument
must only be installed and opened by a
1.2 Symbols used in this document skilled electrician.
Please observe the safety information provided in this Even when the device/instrument is
manual when operating your inverter! switched off, dangerous live voltages
may still be present inside the
instrument.
Warning!
Lethal Hazard!
Regulations concerning the prevention of accidents
Warning The inverter must be installed by an approved skilled
electrician who is responsible for the adherence to
existing standards and regulations.
Danger! The proper and safe operation of the device/instrument
Lethal Hazard by Electric requires proper transportation, storage, erection and
Shock! assembly, as well as careful operation and
Danger maintenance.
Use exclusively the original packaging for returning the Despite all these quality-assuring measures, however,
inverter – only this material will ensure safe disturbances may occur in very rare cases. KACO
transportation. GERÄTETECHNIK GmbH will offer a maximum of
assistance if one of these cases should arise. KACO
3 Notes concerning installation and GERÄTETECHNIK GmbH will take every effort to
remedy any defects fast and without unnecessary
operation bureaucracy. Please contact our service department
directly – and you will be aided and supported very
3.1 Factory guarantee and liability quickly.
KACO Gerätetechnik GmbH grants a guarantee of six 3.3 Intended use (normal use)
years on Powador inverters, starting from the date of Powador inverters are built according to state-of-the-art
installation and max. 78 months after shipment by and approved safety requirements. However, improper
KACO. use may cause lethal hazards for operators or third
parties and/or damage of instruments/devices or other
During this time, KACO Gerätetechnik GmbH property.
guarantees the proper function of the devices and free The device is intended to convert the direct voltage
repair in the event that a defect should occur which we generated in the photovoltaic (PV) modules into
are accountable for. alternating voltage (AC) and feed this voltage into the
grid.
Should your device show a defect or malfunction during The inverter must only be operated in connection with a
the guarantee period, please contact your specialist fixed/stationary connection to the public grid. Inverters
dealer or, respectively, your installation expert. are not intended for mobile use.
Guarantee claims shall be excluded in the following Any use other than the specified intended use shall not
cases: be deemed intended or normal use, and the
- Use of the device for other than the intended use manufacturer/supplier shall not be liable for any
(normal use) damage caused by such unintended use. Damage
- Improper use and installation that does not comply caused by unintended use is at the sole risk of the
with the required standards operator.
Caution!
Using the device for any purposes
other than intended/normal use is
prohibited!
Caution
Total yield
Clear grid-feeding
Display yield meter Press the start key (1) at the
underside of the device for approx. 5
seconds, until a message appears
Clear grid-feeding meter on the display and the LEDS “Grid
feeding“ and “Disturbance“ are no
longer lit up.
Select and set RS485 interface
address You may now scroll through the menu and retrieve the
values of the current day. If no key is pressed for longer
than one minute the device will be switched off again
automatically.
The inverter will only store the latest values of a day.
Figure 4.5: Set Mode Menu The values of “operating hours per year”, “Total
operating hours”, “Annual fed-in power” and “Total grid
Set hour and date
feeding power” will be stored and added up. These
The set values are consecutive, i.e. as soon as you
values will not be lost even if the device is not operated
have reached the max. value the display will be reset to
for a longer period of time. The date and hour may have
the min. value after pressing the „display (1) button
to be reset if the device has not been used for several
once again. The display for setting the date covers a
days.
range up to 2050. After that, the value will be reset.
Column 1 2 3 4 5 6 7 8 9 10
04.06.2005 16:55:30 4 363.8 0.37 134 226.1 0.53 103 23
04.06.2005 16:55:40 4 366.0 0.39 142 226.1 0.53 112 23
04.06.2005 16:55:50 4 359.5 0.41 147 226.1 0.53 116 23
04.06.2005 16:56:00 4 369.8 0.42 155 226.1 0.58 118 23
04.06.2005 16:56:10 4 377.0 0.43 162 226.1 0.63 131 23
04.06.2005 16:56:20 4 373.6 0.45 168 226.1 0.63 133 23
04.06.2005 16:56:30 4 364.0 0.48 174 226.1 0.68 146 23
04.06.2005 16:56:40 4 364.3 0.49 178 226.1 0.68 146 23
Important!
Due to measuring tolerances the
measured values may not always
correspond to the actual values. The
measuring sensors of the inverter
have been selected in a way to ensure
maximum solar yields.
Figure 4.1 Due to the tolerances the daily yields
displayed on the inverter may deviate
This interface enables monitoring several inverters at from the values of your Utility
the same time. By means of the Powador-proLOG Company’s grid-feeding meter by up
series you can receive your yield and operating data or to 15% (admissible meter tolerance
error messages by SMS or e-mail. This monitoring approved by your Utility Company:
option is especially recommended in cases where you
± 2%).
are unable to check the functionality of your installation
on-site at regular intervals, i.e. if your domicile is too far
away from the installation site. In addition, you can use
the Powador-link in your installation, so as to bridge
long distances between several inverters or between an Using the operating keys (see Section 4.3 ) the values
inverter and proLOG by means of a wireless RF and data listed in Table 4-3 can be shown.
connection. Please contact your installer if you wish to
integrate remote monitoring in your system.
2 Solar generator Existing voltage and current of the solar generator connected to
xxx.x V xx.xx A the inverter. Shown in volts and amps; voltage tolerance ± 3 %;
current tolerance ± 5% at rated power. Greater tolerances are
possible when smaller generator currents are displayed.
3 Grid xxxx W Actual grid voltage, grid current and power (measurement of the
xxx.x V xx.xx A phase into which power is delivered); displayed in volts, amps
and watts; voltage tolerance: ± 3%; current tolerance: ± 3 %.
4 Daily peak
Capacity xxxx W Short-team peak grid feeding capacity of the day,
displayed in W. According to the regulations stipulated by the
Power companies, this peak capacity must not exceed 10 % of
the rated power of the inverter. However, the generator may be
dimensioned for higher capacities.
5 Temperature inside
the device xx ° Display of the actual heat sink temperature, in °C. The inverter
will limit grid feeding if the temperature exceeds 65°C. If the
device temperature exceeds 80°C it will switch off automatically.
Status: Waiting for Waiting for night shutdown. The generator capacity is no longer
shutdown sufficient for grid feeding, and the device waits for the night
shutdown.
Status: Device
The device changes over to night shutdown.
switches off
Error
Grid frequency The grid frequency is not correct (excessive or low frequency),
making the grid-feeding process impossible.
Safety A grid voltage error, grid current problem, grid frequency or grid
shutdown impedance problem has occurred. The inverter has switched off
to protect against damage.
8 Internal failure
xxx xxx xxx xxx An internal failure occurred. It will clear itself and the unit starts
again.
9 Date xx.xx.200x
Hour xx:xx:xx
Indicates date and hour
10 Yield today
xxxxx kWh Power delivered since sunrise. Display in watt hours (not kWH!)
11 Total yield
xxxxx kWh Power delivered during the current calendar year (January 1 to-
date)
12 Operating hours
Today xxxxx:xx Power delivered since the time of inverter startup.
13 Operating hours Today’s operating hours since sunrise. Displayed in hours and
Year xxxxx:xx minutes.
14 Operating hours
Total xxxxx:xx Operating hours during the past calendar year (January 1 to-
date).
Caution!
If the values for date and hour are
set incorrectly, this will also affect
the display of operating hours and
Caution
yields!
5 Accessories
KACO Gerätetechnik GmbH offers its customers a wide Powador-easyLOG
range of useful accessories. The product range Powador-easyLOG is used to transmit the operating
includes devices of superb quality for monitoring, data of your inverter via a wireless connection and
display, data transfer and visualization. display such data either on the Powador-Display or on a
PC.
Powador-Display
You wish to see what your installation is doing and
whether everything is the way it should be? Then
Powador-display is the right choice for you. Via an RF
module, the inverter transmits its data to the display,
where you can observe the daily curve or read the
current output or daily yield. You will be able to
recognize any problems in your installation very quickly.
The attractive display is suitable for use in home or
office surroundings.
Figure 5.3:Powador-easyLOG
Powador -go
If you simply wish to know if your installation is working
properly Powador-go is the right choice for you. If your
PV installation or your modules stop producing current,
Powador-go-Set will provide an acoustic warning signal
after 24 hours. The entire processes are independent of
the inverter, so just lean back and relax – your
installation will tell you if there is a problem.
Figure 5.1: Powador-Display
Powador-proLOG
You wish professional monitoring and data recording of
your installation? Powador-proLOG is the high-end
solution to provide error messages by SMS, fax or e-
mail, remote access to installation data, display of your
PV installation on the web or many other things – it’s
just no problem for Powador-proLOG. Up to 32 devices
can be connected to Powador-proLOG by means of the
RS485 interface.
Daily yield values do not Tolerances of the Measuring errors are caused by tolerances of the measuring
correspond to the values inverter’s internal elements. The tolerances of the individual measuring values are
shown on the power measuring elements shown in Table 4-3, Display Operation and Settings. The daily
meter of the Utility yield value may deviate from the value shown on the power
company. meter by up to 15%.
No display shown Device is in the night shut- The inverter shuts down over night.
down mode If the display should not be illuminated during a normal time of
No grid voltage is present the day you should check on the power meter whether or not
Solar generator voltage is the device delivers power. If power is delivered the display
less than 110V module is defective, and the inverter has to be returned to
KACO for repair.
If no power is delivered you should check that grid voltage is
present and that the solar generator voltage is higher than 125
V.
If this is the case but the inverter still fails to deliver power the
device has to be returned to KACO for repair.
Inverter does not start Device is in its night shut- The inverter shuts down over night.
down mode If the display should not be illuminated during a normal time of
No grid voltage is present the day you should check on the power meter whether or not
The solar generator the device delivers power. If power is delivered the display
voltage is less than 125 V module is defective and the inverter has to be returned to
KACO for repair.
If no power is delivered you should check that grid voltage is
present and that the solar generator voltage is higher than 125
V.
If this is the case but the inverter still fails to deliver power the
device has to be returned to KACO for repair.
Inverter is active but Insufficient generator After sunrise, at sunset, and during times of low insolation due
does not deliver power – voltage. Voltage to bad weather conditions the generator voltage or,
the display reads: Start measured < 125V respectively, generator power fed from the roof may be
from 125 V insufficient for grid feeding
Measurement:
xxx V
Inverter is active but The inverter has After an interruption of grid feeding due to a malfunction (grid
does not deliver power – interrupted grid feeding power failure, overtemperature, overload, etc.) the inverter
the display reads: due to a always waits for approx. 3 minutes before resuming its grid
Start from 125 V malfunction/disturbance. feeding operation. Grid failures may cause interruptions during
Measurement: the day. If more than 10 interruptions should occur over several
xxx V (measured voltage weeks you should contact your solar installation provider.
is higher than 125V)
Grid fuse triggers Insufficient grid fuse rating At times of high insolation the inverter may exceed its rated
Inverter hardware is current for a short time, depending on the type of solar
damaged generator. Therefore, the grid fuse should have a higher rating
than the max. grid feeding current.
The grid fuse acts immediately if the inverter changes over to
grid feeding (i.e. on termination of the start-up period). In this
case, the inverter hardware is damaged and the device has to
be returned to KACO for repair.
Inverter causes noise Special environmental Under special environmental conditions the devices may cause
conditions audible noise. This may be due to the following causes:
- Grid effects and/or grid disturbances caused by special
consumers (motors, machines, etc.), which are connected to
the same grid point or which may be installed in the vicinity of
the inverter.
- Dynamic weather conditions (frequent changes between sun
and clouds) may cause a slight um due to high energy
- Certain grid conditions may result in grid resonance between
the input filter of the device and the grid, which may continue
to be audible even after the inverter is switched off.
- People with very sensitive ears (children, in particular) may
perceive high-frequency hum of the inverter, caused by the
operating frequency of 18 kHz.
- This noise does not affect the operation of the inverter or
inverter performance and will not result in failure, damage or
shorter useful life of the devices.
Installation Instructions
Powador 1501xi / 3501xi / 4501xi
- Operation of the devices with defective protective Some of the documents which are needed for these
equipment applications and acceptance are attached to these
- Manipulation of the device or makeshift repairs installation instructions.
- Influence of foreign objects or Act of God
(lightning, overvoltage, tempest, fire)
- Inadequate ventilation of the device Caution!
- Non-adherence to the relevant safety instructions Using the device for any purpose
(VDE (Association of German Engineers), a.o. other than intended/normal use is
- Transport damage prohibited!
Caution
UMpp (+60°C) > min. input voltage (125VDC) 4.3 Mechanical dimensions
Even at very high external temperatures (+60°C) the
MPP voltage of the connected string should remain
within the admissible input voltage range. If the
temperature rises from 25°C to 60 °C, the MPP voltage
of 12V modules will decrease by approx. 3.6 V per
module (7.2 V for 24V modules). The MPP voltage of
the entire string should be > 125 V.
Even if the MPP voltage is beyond the admissible input
range, the installation nevertheless will continue to work
properly. However, the delivered power is slightly less
than the maximum yield.
Provided that the input voltage is within the admissible
input voltage range, the inverter will not be damaged if
a connected PV generator should supply current above
the max. usable input current.
If the PV generator should supply more than the max.
PV generator power of the inverter for a short time,
particularly due to clouds and relatively low module
temperatures, it is possible that the inverter switches off Figure 4.1: Dimensions of Powador
for safety reasons and automatically switches on again Type Height Width Depth
after approx. 10 seconds. The overload status is shown 1501xi 450mm 340mm 200mm
on the display in plain text. Under normal 3501xi 500mm 340mm 200mm
circumstances, however, the dynamic control of the 4501xi 650mm 340mm 220mm
inverter ensures that this condition is recognized and
the inverter operation is continued without any
interruption.
PV generator connection by means of screwed The assembly of the Tyco and MC-type connectors is
cable gland fittings depicted in Figure 5.6 and. Figure 5.7.
Caution!
Figure 5.4: Connection of three PV strings The PV generator should not be
PV generator connection by means of multi-contact disconnected from the Powador
or Tyco plug-type connectors Caution inverter (i.e. by pulling the
MC or Tyco plug-type connectors may be enclosed to connector) under load except in
the inverter as options. These connectors may be used absolute emergency cases. It
instead of the screwed cable gland fittings-type fittings should by all means be avoided
mounted on the device (shipping condition). In this during the normal grid feeding
case, please remove the screwed cable gland fittings- operation.
type fittings and assemble the appropriate connectors Prior to disconnecting, always
instead. disconnect grid voltage by
deactivating the grid fuses.
Remove the screwed cable gland -type If this is not observed, arcing may
connectors from the provided apertures occur and damage the connectors
in the baseplate of the inverter. Insert – both parts of the connector will
the Tyco- or MC connector from outside have to be replaced.
into the apertures and fasten them
inside by means of the black plastic
nuts (see Figure 5.5).
5.4 Connecting the fault-signal relay 5.6 Connection of the RS485 interface
The inverter is equipped with a potential-isolated relay On the control board (at the rear side of the door of the
contact to signal faults. If a fault occurs, this contact will Powador inverter), there are four terminals marked
be closed. RS485 A and B (see Figure 5.10). To connect several
Max. contact load: 30V / 1A. Powador inverters, terminal A of the first Powador must
be connected to terminal A of the second Powador;
terminals B are connected in the same way.
Important! You need a twisted and shielded data cable for
In the event of a power failure in the connection, such as an ISDN cable. The connection to
public grid the relay will not trigger. proLOG is established analogously. The wiring plan is
In this case, all LEDs and the display shown in Figure 5.11. The total length of the RS485
will be extinguished and the inverter wiring should not exceed 250 m.
will be shut down completely.
A fault signal will not be possible in
this case!
S0 Interface
Set parameters
Delete parameters
Figure 5.13: Jumper position in the programming mode
Display setings
- SO interface:
The “Set” key is used to change the The SO interface is used to control a large display. Use
respective parameter. Depending on the this parameter to adjust how many pulses per kWh are
parameter, the value increases or to be transmitted. The possible settings are 500, 2000
decreases. The values are continuous, and 1500 pulses per kWh.
i.e. if you have reached the max. value,
they will be reset to the min. value. After changing these parameters the inverter must be
reset to its original condition.
8. Troubleshooting
7. Switching off the inverter Within the scope of our continuously expanding Quality
The inverter must be switched off for adjusting, Assurance System, our goal is to rule out and eliminate
maintenance and repair work. Please proceed as any faults and defects. You have purchased a product
follows: that has left our factory in a proper condition. Each
individual device has successfully passed extensive
inspection tests for proper operation and functioning of
protective devices, as well as a long-duration test at our
factory.
The sequence of work, especially when
Should your PV installation not work properly despite all
using DC connectors as DC circuit
these measures, we recommend the following
breakers, must be observed by all
procedure for remediation:
means.
Check the solar generator and grid connections leading
Otherwise, arcing might occur when
to the PVI, observing all the safety instructions given in
disconnecting the DC connector under
this manual. Please observe the inverter carefully and
load. This will destroy the connectors.
take note of the display messages and LED displays.
Below is a summary of possible error and
recommended remedies:
Danger!
Lethal hazard by electric shock!
Hazardous live voltages can be
Danger present in the inverter even if the
electrical connections have been
switched off or disconnected.
Please wait for five minutes before
accessing the inverter. If you have to
carry out any work on the solar
generator you must additionally
disconnect all connections of the DC
main switch on the generator
connection box (or DC connector). It
is not sufficient to switch off the grid
voltage in this case!
Daily yield values do not Tolerances of the Measuring errors are caused by tolerances of the measuring
correspond to the values inverter’s internal elements/sensors. The tolerances of the individual measuring
shown on the power measuring values are given in the Operator’s Instructions. The daily yield
meter of the Utility elements/sensors value may deviate from the value shown on the power meter by
company. up to 15%.
Grid fuse triggers - Insufficient grid fuse At times of high insolation the inverter may exceed its rated
rating current for a short time, depending on the type of solar
- Inverter hardware is generator. Therefore, the grid fuse should have a higher rating
damaged than the max. grid feeding current.
The grid fuse acts immediately if the inverter changes over to
grid feeding (i.e. on termination of the start-up period). In this
case, the inverter hardware is damaged and the device has to
be returned to KACO for repair.
No display shown - Device is in the night The inverter shuts down over night.
shut-down mode If the display should not be illuminated during a normal time of
- No grid voltage is the day you should check on the power meter whether or not
present the device delivers power. If power is delivered the display
- Solar generator voltage module is defective, and the inverter has to be returned to
is less than 100 KACO for repair.
If no power is delivered you should check that grid voltage is
present and that the solar generator voltage is higher than 125
V.
If this is the case but the inverter still fails to deliver power the
device will have to be returned to KACO for repair.
Inverter does not start - Device is in its night The inverter shuts down over night.
shut-down mode If the display should not be illuminated during a normal time of
- No grid voltage is the day you should check on the power meter whether or not
present the device delivers power. If power is delivered the display
- The solar generator module is defective and the inverter has to be returned to
voltage is less than 100 KACO for repair.
V If no power is delivered you should check that grid voltage is
present and that the solar generator voltage is higher than 125
V.
If this is the case but the inverter still fails to deliver power the
device has to be returned to KACO for repair.
Inverter is active but Insufficient generator After sunrise, at sunset, and during times of low insolation due
does not deliver power – voltage. Voltage to bad weather conditions the generator voltage or,
the display reads: Start measured < 125V respectively, generator power fed from the roof may be
from 125 V insufficient for grid feeding
Measurement:
xxx V
Inverter is active but The inverter has After an interruption of the grid feeding process due to a failure
does not deliver power – interrupted grid feeding (grid power failure, overtemperature, overload, etc.) the inverter
the display reads: due to a always waits for approx. 3-4 minutes before resuming its grid
Start from 125 V malfunction/failure. feeding operation. Grid failures may cause interruptions during
Measurement: the day. If more than 10 interruptions per day should occur over
xxx V (measured voltage several weeks you should contact your solar installation
is higher than 125V) provider.
The inverter terminates Defective grid isolation Although there is enough insolation, the inverter delivers power
grid feeding shortly after relay in the inverter. for a few seconds only and switches off again. During this short
starting-up although time a grid feeding value between 0 – 5 W is displayed. If
there is enough insufficient generator power can be ruled out in this case the
insolation. grid isolation relay is presumably defective and prevents the
inverter from being activated.
Inverter Data:
- Serial number of the device
- Inverter type
- Short description of errors the fault or error
reproducible? (If so, please provide a short
description).
- Does the fault or error occur sporadically?
- Describe the insolation conditions prevailing when the
error occurred.
- Hour of the day
10. Appendix
10.1 EU Declaration of Conformity
This is to confirm that the devices stated above are compliant with the protection requirements set forth in The EU
Council Directive as of May 3 1998 for the Harmonization of Legal Stipulations of the Member States concerning
Electromagnetic Compatibility (89/336/EWG) and the Low Voltage Regulations (72/23 EWG).
Therefore, the types stated above are designated with the CE label.
Any manipulation or modifications on the supplied devices and/or any use for other than for the intended purposes shall
render this Certificate of Conformity null and void.
st
Neckarsulm, 21 June 2005
KACO GERÄTETECHNIK GmbH
p.p.
Matthias Haag
Head of the Photovoltaics Division
10.2 Declaration of Conformity concerning the rated power and max. output of photovoltaic inverters
The AC peak power has been indicated as a mean value measured over a period of 10 minutes.
The cosφ of the inverters is 0.999 at rated load. Therefore, the AC power in W is equivalent to the apparent power in VA.