Power Swing Blocking: Brief Description

The document discusses power swing blocking in the REL670 line distance protection relay. It provides a brief description, then details how the relay consists of measuring inner and outer impedance characteristics to recognize power swings and block distance zones for a period of time.

Uploaded by

mubarakkirko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
214 views3 pages

Power Swing Blocking: Brief Description

The document discusses power swing blocking in the REL670 line distance protection relay. It provides a brief description, then details how the relay consists of measuring inner and outer impedance characteristics to recognize power swings and block distance zones for a period of time.

Uploaded by

mubarakkirko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Power Swing Blocking

Brief Description

Restricted © Siemens 2020 siemens.com


Power Swing Blocking (ABB REL670)

∆Fw: distance between RLdOutFw and RLdInFw


RLdInRv: kLdRRv·RLdOutRv
kLdRRv : settable multiplication factor less than 1
∆Rv: distance between RLdOutRv and RLdInRv
R1FInRv: inner resistive characteristic in the second quadrant outside the load encr.

• Consists of measuring its inner and outer impedance characteristics.


• If an impedance transit duration between the outer and inner zone is
longer than time tP1 selected distance zones are blocked
• Swings are recognized as consecutive if the measured impedance leaves
the outer zone and returns back for a period of time shorter than tW
RLdInFw = kLdRFw·RLdOutFw
• In such a case, time element tP2 is used instead of tP1 because later
kLdRFw: settable multiplication factor less than 1 swings are generally faster.
LdAngle: slope of the load encroachment for inner and outer boundary • Blocking remains activated until measured impedance leaves outer zone.
Activation could be extended with tH setting
X1InFw: reactive reach inner boundary
R1LIn: line resistance for the inner boundary. • Power swing detection is disabled if measured impedance remains in
characteristics area longer than tR2 setting
R1FInFw: fault resistance coverage for the inner boundary
• Swing blocking can be disabled if there is SLG fault during swing.
Reference: Line distance protection REL670 Version 2.2 ANSI, Technical Manual Distance zones are unblocked after tR1setting.
Restricted © Siemens 2020
Page 2 2020-08 SI DG PTI
Application Notes of REL670

Restricted © Siemens 2020 Reference: Line distance protection REL670 Version 2.2 ANSI, ApplicationManual
Page 3 2020-08 SI DG PTI