Huawei SPD Introduction

The document discusses surge protection for DC and AC sides of photovoltaic systems. For the DC side, it recommends a customized SPD with a 10kA nominal discharge current and integrated tripping device. For the AC side, it recommends a customized SPD with 5kA protection capability and 10kA nominal discharge current, as well as adding higher grade external SPD for sites with frequent storms or long AC wiring. Rocket triggered lightning tests showed the system withstood 38.05kA lightning currents over four months.

Uploaded by

lkt_pestech
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views

Huawei SPD Introduction

The document discusses surge protection for DC and AC sides of photovoltaic systems. For the DC side, it recommends a customized SPD with a 10kA nominal discharge current and integrated tripping device. For the AC side, it recommends a customized SPD with 5kA protection capability and 10kA nominal discharge current, as well as adding higher grade external SPD for sites with frequent storms or long AC wiring. Rocket triggered lightning tests showed the system withstood 38.05kA lightning currents over four months.

Uploaded by

lkt_pestech
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Surge protection—DC side

Trigger
SPD Product model PV20K510-MH
device Supplier HPXIN
Rated Voltage 230 VAC
Maximum Continuous Uc 510 VAC / 820VDC
Nominal discharge
10kA (8/20μs)
current-In
Maximum discharge
20kA (8/20μs)
current -Imax
Customized
SPD

DC side customized SPD(according to EN61643-11):


• Maximum current rating for DC side SPD( nominal discharge current 10KA), Type 2
• in series with tripping device, when SPD leakage current increase it will be tripped and prevent
catching fire

Similar to
DEHN
DG M YPV SCI
1000 FM (952
515)

System design recommendation:


SUN2000 inverter reaches Type II protection level on the DC side, and is able to handle typical
inductive lightning shocks to be faced in PV system.

HUAWEI TECHNOLOGIES CO., LTD. 10/29/2019 RS 1 Huawei Confidential


Surge protection—AC side

Product model PV20K385-MH


Supplier HPXIN
Rated Voltage 230 VAC
Maximum Continuous 385 VAC /
Uc 505VDC
Nominal discharge
10kA (8/20μs)
current-In

Maximum discharge
Customized SPD 20kA (8/20μs)
current -Imax

AC side customized SPD:


• Design capability is 5KA for protection, SPD capability is 10KA( nominal discharge current 10KA),
Type II
• Test result showed that 5KA is ok for the AC surge protection

System design recommendation:


•The SUN2000 inverter reaches Type III protection level on the AC side, and is able to handle normal
electric surges. However, if the installation site is expected to face frequent thunderstorm weather, and
if the AC wiring is very long, it is recommended to add separate higher grade SPD component in the
AC combiner box.

HUAWEI TECHNOLOGIES CO., LTD. 10/29/2019 RS 2 Huawei Confidential


Rocket Triggered Lightning Test - Guangdong Conghua

The test lasted four months, the security lightning current withstands 38.05 KA

HUAWEI TECHNOLOGIES CO., LTD. 10/29/2019 RS 3 Huawei Confidential