Power Trafo Transient
Power Trafo Transient
net/publication/321817431
CITATIONS READS
0 196
4 authors, including:
Xudong Hao
East China Normal University
7 PUBLICATIONS 10 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Research and development of a photovoltaic forecast system based on multiple sensors View project
Research of Transformer Modeling Considering the Influence of Tap Positions on Original Parameters View project
All content following this page was uploaded by Asad Ahmad on 08 January 2019.
,(((
Aim of this paper is to representing the summary of transient C. Fault Analysis of ThreePhase Model
single phase double winding transformer and three phase Transformer is one the exorbitant element of power grid.
three winding transformer models in a power system Usually transformers are highly assured but maloperations
equipped with on-load tap changers on transformers high normally occur in protection devices. In order to study such
voltage sides considering the influence of taps and its effects condition, in case of fault directly shot the power transformer
on winding resistance and inductance with respects to on-load another three phase model is designed having symmetrical
tap changer. Also the fault analysis results and comparison of and un-symmetrical faults just before the designed
proposed and traditional model is discussed in detail. transformer model.
II. DELINEATION OF TRANSFORMER MODELS IN
POWER SYSTEM
A. Single Phase Model
Dynamic impacts of tap changer on power system have
completely different behaviors on voltage and current within
the event of variation of tap positions. These changes in
voltage and current conjointly turn out the consequences on
power transformer winding X/R ratio and inductance values.
Single phase step down transformer model 70 MVA 132/33
kV is integrated in a power network as shown in figure to
understand the impacts of tap changer on single phase Figure 3. Three Phase Grid Interconnected Scheme In case of Fault
transformer as shown in Fig. 1. III.TRANSIENT MODELING OF SINGLE AND THREE PHASE
TRANSFORMER
A. Inductance Matrix Model for Single Phase Double
Winding Transformer
In previous paper single phase double winding
transformer model was represented with deviations as the tap
changes. In this paper, single phase double winding
transformer is simulated using the mathematical model which
provides us more accurate results to implement this model.
The magnetic circuit diagram of a single phase double
Figure 1. Single Phase Grid Interconnected Scheme winding transformer, in which the arrows denote the
B. Three Phase Model reference direction for voltage, current and magnetic flux [1],
[2].
Challenges in power network having the three phase I
transformer with tap changer are totally different from single i1 i2
B. Inductance Matrix Model for Three Phase Three maximum values of voltage and current but having the certain
Winding Transformer differences in values.
The three-phase transformer can still be regarded as the
multi-branch resistance and inductance coupling circuit, but
the mutual inductance between the three phase windings due
to the common magnetic circuit should be considered. This
means the coupling problem existing between different
windings of different phases. Conceptually, from a single
phase transformer to three-phase transformer, each winding
in single-phase transformer should change to three windings
respectively in iron core winding I II III of three-phase
transformer [2],[3],[4]. The short circuit reactance is
calculated as
ª X ss13 X ms 13 X ms 13 º
« s »
X 11' X 13s « X m13 X ss13 X ms 13 »
« X ms 13 X ms 13 X ss13 »¼
¬ (4)
abnormal conditions due to external factors result in stresses
on the transformer e.g. Overloading, System faults,
Overvoltage, and Under-frequency operation. So the main
focus of this paper is to enlighten the one of the external
factor “System faults” causing the damage to transformer
directly [5],[6]. For analyzing the faults in proposed power
system fault logic is designed to having 10 positions every
position represents a different fault.
A. Symmetrical Faults
Ideally when the symmetrical faults occurs, symmetrical
fault current of abnormally high magnitude flows through the
network equal in magnitude and displaced 120º from each
other and the voltage at fault point is reduced to zero. But
practically here it is observed that voltage is not reduced to
zero in between the time interval 0.500 to 0.560. When a
Figure 8. Single Line to ground fault at default position of OLTC
symmetrical fault occurs at any point in a system, the
short-circuit current is limited by the impedance of the system C. Double Line to Ground Fault (L — L —G)
upto the point of fault. During the interval of fault current is Consider the double line-to-ground fault involving B–C
abnormally high because the value of resistance is reduced lines and earth. Fault dial positions 4, 5 and 6 are having the
abruptly and displaced by 120º as shown in Fig.7. Phase AB to ground, Phase AC to ground and Phase BC to
ground. Here just the position 6 is discussed because other
two positions of fault dial also having the same effect [8], [9].
When the fault occur at Phase BC to ground so ideally fault
conditions are I A 0 and VB Vc 0 . During the interval of
fault current of Phase BC is abnormally high because the
value of resistance is reduced abruptly and current of Phase A
is almost equal to zero while the voltage of faulty phases is
not reduced to zero as compare to healthy phase A as shown
in Fig.9.
voltage of the both faulty phases is disturb but not purely VII. CONCLUSION
equal to each other as shown in Fig.10.
In conclusion, it can be summarized that the conventional
transformer in power grid transient stability and steady state
analysis, is commonly modeled as consistent impedance
connected to a non-standard turn ratio. It is found that the
genuine parameters of transformers, such as the resistance
and inductances of transformer winding also have variations
with alternation of tap positions. Case studies on this advance
model is also performed, the results have shown which
proves the every step is having the divergence which produce
inaccuracy in power system analysis.
ACKNOWLEDGMENT
I would like to take this opportunity to express my
gratitude to my parents, supervisors and Xian Jiaotong
University. Their support and encouragement provides me the
opportunity to complete this research work successfully. I
Figure 10. Line to Line fault at default position of OLTC believe this way of guidance is really unique and would be
very helpful for further studies.
Here only the results of default position is shown only but Mr.Kaleem Ahmad & Mr.s Tahira Kaleem (Parents)
when the tap position is changed from 1 to 9 its fault current Prof. Wanliang Fang & Prof. Jun Liu (Supervisors)
and voltage of primary side and secondary is also increased
which also having the impact on its winding resistance and REFERENCES
inductance. In both symmetrical and un-symmetrical faults, [1] Jun Liu, Ahmad Asad, Kejian Nie, Wanliang Fang, Junxian Hou, Zutao
Xiang. "Research of transformer modeling considering the influence of
all the variations in between the interval 0.500 to 0.560 are
tap positions on original parameters", 2016 IEEE PES Asia-Pacific
because this model is having the Fault ON resistance of 0.01 Power and Energy Engineering Conference (APPEEC), 2016.
ohm but ideally this resistance is infinity. Three phase three [2] Brandwajn, V., H.W. Donnel and I.I. Dommel. "Matrix Representation
winding transformer reduces the unbalancing in primary due of Three-Phase N-Winding Transformers for Steady-State and
Transient Studies." IEEE Transactions on Power Apparatus & Systems,
to the unbalancing in three phase loads also in fault analysis it
1982, vol. PAS-101, no. 6, pp. 1369-1378.
redistributes the flow of fault currents, so it provides the more [3] Shruthi, B S, and K Modelling and simulation studies Panduranga
practical results in contrast to traditional model. Vittal. “of interwinding faults in a three phase distribution transformer
using EMTDC/PSCAD", 2013 IEEE Innovative Smart Grid
VI. COMPARISON OF PROPOSED AND TRADITIONAL MODEL Technologies-Asia (ISGT Asia), 2013.
According to the comparison of proposed and traditional [4] Dzafic I, Jabr R A, Neisius H T. "Transformer Modeling for Three-
Phase Distribution Network Analysis." IEEE Transactions on Power
transformer models it has been found that both models have Systems, 2015, vol. 30, no.5, pp. 2604-2611.
severe differences in values which may be produce the [5] Gustavsen, B. "Wide-Band Transformer Modeling Including Core Non-
inaccuracy in power system analysis if it’s to continue to use Linear Effects." IEEE Transactions on Power Delivery, 2016, vol. 31,
the traditional transformer models. Almost the 18 tap no.1, pp. 219 - 227.
[6] N TLEIS. "Modelling of transformers, static power plant and static
positions of proposed and traditional model are compared load", Power Systems Modelling and Fault Analysis, 2008.
having both the positive and negative values of tap changer. [7] Chu Yun-long. "Study on the Transformer Protection Principle Based
Difference between the both models is shown below on The Equivalent Circuit Equation", 2005 IEEE/PES Transmission &
in Fig. 11. Distribution Conference & Exposition Asia and Pacific, 2005.
[8] Martinez, J. A., and Mork, B.A. "Transformer Modeling for Low- and
Mid-Frequency Transients—A Review." IEEE Transactions on Power
Delivery, 2005, vol. 20, no.2, pp. 1625-1632.
[9] Pedra, J., et al. "Harmonic nonlinear transformer modeling." IEEE
Transactions on Power Delivery, 2004, vol. 19, no. 2, pp. 884-890.