NG7-40.5 Z Isatallation Guide
NG7-40.5 Z Isatallation Guide
5(Z)
NG7-12~40.5(Z)/T(630~2500)-31.5
metal-enclosed switchgear
5. General provisions
5.1 Running check
5.2 Main circuit insulation level check
5.3 Circuit breaker mechanical characteristics check
5.4 Maintenance of other components
6. Ordering instructions
NG7-40.5(Z)
1.Brief introduction
1.1 Product overview
1.2.1 The primary component adopts the full sealing design and is completely
sealed in the sealed gas box welded by the stainless steel plate. It is filled with
0.04MPa SF6 gas as the insulating medium, and the protection grade is IP67,
completely avoiding the influence of the external environment and climate on the
switchgear. Reliable operation in the harsh environment of the basement, plateau,
frozen soil, coastal, humid, etc., to achieve maintenance-free.
1.2.2 The modular design is realized. The side expansion busbar connector is
used in the cabinet, which is convenient to install and flexible to expand. The user
does not involve gas potting when the cabinet is connected at the site, and the air
leakage rate is extremely low.
1.2.3 It can realize manual and electric operation. The operating mechanism is
mature and reliable, and has perfect mechanical and electrical interlocking, which can
effectively prevent personal injury and equipment damage caused by misuse.
1.2.4 The design is compact, compared with the traditional air-insulated
switchgear, the volume is significantly reduced, the floor space is reduced by 30% to
70%, the space utilization rate is improved, and the comprehensive project cost is
effectively reduced.
1.2.5 Based on microprocessor protection and system technology, it integrates
protection, control, measurement, monitoring and communication functions to
achieve comprehensive automation requirements, and can be completely
unattended.·
·
a) ambient air temperature -40 ° C ~ +40 ° C, and the average value measured
within 24h ≤ 35 ° C;
2 Rated frequency Hz 50
Power frequency
withstand voltage
42 65 95
(interphase, ground,
vacuum fracture)
Power frequency
withstand voltage 48 79 118
Rated
(isolated fracture)
4 insulation kV
Power frequency
withstand voltage
level 2
(control and auxiliary
circuit)
Lightning impulse
withstand voltage
75 125 185
(interphase, ground,
vacuum fracture)
Lightning impulse
withstand voltage 85 145 215
(isolation fracture)
Rated peak
6 Main circuit kA 63/80
withstand
NG7-40.5(Z)
current
Grounding switch 63/80
breaker 10000
Mechanical
Three-position
14 Times
switch (isolation
life 3000
switch / grounding
switch)
Rated inflation
SF6 gas rated 0.04
pressure
pressure (20 °
15 Minimum MPa
C relative functional level 0.02
pressure
value)
1
6
2 7
3 8
9
4
10
Front
Prefabricated panels
Pre-buried 10# channel steel
Prefabricated panels
Foundation drawing
NG7-40.5(Z)
Embedded steel channel
Foot hole
Technical requirement:
1.The basic frame is made of 10# channel steel, galvanized, and the tolerance of flatness is ±1mm/m.
2.The geometrical tolerance requirements of the channel steel installation frame, the tolerance of straightness is ±1mm/m, and the total length is not more than 3mm.
3.See the attached file for specific parameter list.
voltage level
Figure 6 Cable trench and base channel size reference drawing (the specific shape
foundation map is provided according to the specific engineering order)
2.1.3 Basic precautions for on-site installation
2.1.3.1 The tightening torque is shown in Table 2.
M12 86 40
NG7-40.5(Z)
2.1.3.3 Unlubricated bolts The rated tightening torque is calculated from the coefficient
of friction of the thread of 0.14 (the actual value is inevitably errory, but partially
negligible); the tightening torque of the lubricated bolts is in accordance with DIN
43673.
2.1.3.4 Both the thread and the bolt head contact surface are coated with lubricant.
2.1.3.5 Data is only applicable to welded studs. Consideration should be given to the
torque specified in the detailed technical documentation (eg contact or device end) as
is recommended to apply lubricant (fat) to the thread and bolt head contact surfaces.
2.1.3.6 All parts, including the surface of the insulating parts, should be removed. For
the cleaning work, please refer to the installation and operation manual of each part.
2.1.3.7 SF6 gas should be prevented from leaking into the power distribution room
2.1.3.7.1 Otherwise, inaccurate data may be obtained during the leak test.
2.1.3.7.2 Ventilation should occur immediately and evacuate the power distribution
room.
2.1.3.7.3 Gas installation is not required for general installation. If gas operation is
a) Thoroughly clean the silicone rubber insulation and apply silicone grease evenly;
NG7-40.5(Z)
b) The switchgear cabinets are sequentially placed in accordance with the arrangement
order of the plan diagram to the installation foundation that meets the requirements;
c) pre-loading 3 busbar couplings on the side outlet casing that has been placed in the
d) Place another cabinet close to the cabinet and install the cabinet screw at the hole of
the cabinet;
e) The cabinet is pulled by the screw, and the screws are evenly tightened;
f) Lock the anchor bolts of each switch cabinet, or weld the switch cabinet to the
g) Before power transmission, all casings not equipped with expansion joints must be
b) Make the inner cone plug-in cable head in strict accordance with the "Inner Cone
d) Insert the cable installation block correctly between the inner cone plug-in terminal
and the air box plate, insert the cable end into the hole of the inner cone socket, and
e) Reliably fix the cable, otherwise it may cause accidents due to stress problems;
f) The cable grounding wire should be directly connected to the main grounding circuit
of the switchgear, and the grounding wire of the tailpipe should also be reliably
grounded;
g) Before sending power, it is necessary to check all the inner taper sockets of the
(5) Contact
(1) Endocone insulator
(6)Insulator sealing surface
(9) Earthing
Separable and
(4)deadfront arrester
a). Before installation, the fixed thickness H between the lower plane of the inner cone
insulator (1) and the upper plane of the arrester mounting flange (8) must be tested.
After installation, it is 13-15.5mm, otherwise the backing ring is added. ) to make
adjustments to ensure the required fixed thickness H.
b) Clean the inner sealing surface (6) of the inner cone insulator (1) with an industrial
NG7-40.5(Z)
wiping paper. After the sealing surface is completely dry, apply a layer of lubricating
grease.
c). Clean the exposed organic jacket sealing surface (7) on the upper end of the arrester
with industrial wiping paper. After the sealing surface is completely dry, apply a layer of
lubricating grease.
d). First pass the backing ring (3) through the arrester sealing surface (7), place it flat on
the end face of the mounting flange (8), and pass the M8×50 fixing bolt through the
flange wire hole.
e). Then put the arrester vertically upwards. When inserting the inner cone insulator,
gently turn the arrester and finally press it evenly with the fixing bolt until the arrester
mounting flange (8), the backing ring (3), the air chamber steel plate Complete contact
between the fixing flange (2).
f) After the arrester is installed, the grounding point (9) of the arrester must be reliably
grounded with a copper wire of not less than 10 mm2.
g). Arrest arrester with counter interface (10), the interface bolt must pass the counting
monitor or pass through the signal collector and be reliably grounded with copper wire
of not less than 10mm2, and the contact (9) should also be reliably grounded.
2.2.3 Installation of the outer cone plug-in cable terminal and the rear plug-in
arrester refer to the following figure:
bolt
connecting rod
insulating plug
bushing bolt
connecting rod termianl rear connector bolt
silver plated copper flat pad cap
stress cone
silver plated copper flat pad spring pad nut
front connector
earth cable spring pad nut
earth cable
b) Place the pad at the jack, pay attention to the installation direction, and it is suitable
to fit tightly;
c) Pour the PT into the socket and fix it with M8 bolt fasteners;
d) The secondary wiring is fixed and connected to the instrument room from the
1. Confirm that the density relay pointer 3. Rotate the “close/open switch” knob as
2. Turn the circuit breaker “local/remote
indicates more than 1.4bar (in the green indicated, hear the “beep” sound, the
switch” knob to position it in place.
area); after confirming, the lower door is circuit breaker opens the green light, and
5. Observe the grounding indication of the 6. After about 10s, the three-position switch
4. Turn the three-position “local/remote
three-position switch, confirm that it is in opening indicator light is on, and the
switch” knob to position it in place.
the grounding position, and press the three-position switch enters the opening
7. Press the three-position switch closing 8. Turn the “storage switch” knob 9. Turn the “close/open switch” knob as indicated,
button to close the three-position switch. After clockwise. After about 8 seconds, the and hear the “beep” sound and the circuit breaker
about 10 seconds, the three-position switch circuit breaker energy storage indicator closes. Observe that the circuit breaker closing
closing indicator will light red, confirming that lights up and the energy storage is indicator is red, confirm that the circuit breaker is in the
1. Confirm that the density relay pointer 3. Observe that the “separation indication” on
2. Open the front upper door; press the
indicates more than 1.4bar (in the green the panel of the circuit breaker mechanism is
circuit breaker opening button to open
area); after confirming, the lower door is displayed as (O), confirming that the circuit
the circuit breaker
closed. breaker is in the open state.
4. Observe and confirm that the 6. Pinch the mechanism to unlock the paddle,
5. Turn the handle clockwise until it can't
three-station mechanism is in the continue to rotate clockwise until the handle
rotate to reach the opening position.
grounding position, push the unlocking pin, can't rotate, the limit reaches the closing
and insert the operating handle into the position, and the operating handle is pulled
out.
7. Insert the energy storage handle into 8. Press the mechanical closing button
the energy storage operation hole and to hear the “beep” sound. Observe
rotate the handle clockwise until you hear that the circuit breaker mechanism
that the “storage indication” shows confirm that the circuit breaker is
operation is completed.
NG7-40.5(Z)
3.2Power failure operation
1. Confirm that the density relay pointer 3. Rotate the “close/open switch” knob according
2. Turn the circuit breaker
indication is greater than 1.4bar (in the to the instruction, and hear the “beep” sound. The
“local/remote switch” knob to
green area); the lower door is closed after circuit breaker opens and the green light is on,
position it in place.
confirmation confirming that the circuit breaker is open.
4. Turn the three-position “local/remote 5. Observe the closing indication of the 6. After about 10s, the three-position
switch” knob to position it in place. three-position switch, confirm that it is in switch opening indicator light is on, the
the closing position, and press the three-position switch enters the opening
three-station mechanism is in the closing until it can't rotate to reach the opening
hole.
NG7-40.5(Z)
3.3Power and interlock function
mechanism
Figure 5 Schematic diagram of electric switch mechanism for circuit breaker switch
operation
Switchgear assembled in the factory must be inspected for its assembly and
performance.
a) assemble several switch cabinets together and use them immediately on site;
b) Check whether the order requirements are met;
c) All switchgear cabinets have been routinely tested in accordance with relevant
standards;
d) The mounting materials and accessories are packaged separately;
e) Condition conditions of the gas compartment:
Insulating gas filled with rated working pressure;
Put in a desiccant bag;
Note: Air transport may be considered for discussion in individual cases.
4.2 Packaging
A special packing box is used, and a suitable desiccant is placed in the box, and has
signs such as rainproof, anti-collision, lifting position, and shipping address. Special
packaging requirements will be discussed separately.
4.3 Lifting, transportation
4.3.1 Single switch cabinets are hoisted and transported separately;
4.3.2 The weight of the transport unit should be considered;
4.3.3 The height of the center of gravity of the package should be considered;
4.3.4 The cabinet should be placed upright;
4.3.5 Various loading and unloading precautions should be carried out to ensure the
safety of personnel and articles. The following loading and unloading tools can be used:
crane;
a) The sling with hook should have sufficient carrying capacity (the opening angle of
the hook is ≥ 30mm);
b) The sling is connected to the four lifting rings at the top of the cabinet through the
hook, and the length of the sling should be no less than 4m;
c) Confirm that the sling/sling is strong and will not slip.
Forklifts (switch cabinets should stand on pallets).
The equipment should avoid tilting during handling. If it must be tilted, the tilt angle
should not exceed 5 degrees.
4.4 Acceptance
4.4.1 Check the package for damage;
4.4.2 Check whether the documents, accessories and spare parts are complete
according to the packing list of the product;
4.4.3 Check whether the model, specification, technical parameters and product
certification on the product nameplate meet the order requirements.
NG7-40.5(Z)
Note: Photographs must be shown to show damage.
4.5 Storage
This product should be stored upright in a room that is dry, ventilated, damp-proof,
shock-proof and resistant to harmful gases. The room temperature should not be lower
than -15 °C. For long-term storage, the circuit breaker should be in the opening
position and the environment should be checked regularly to meet the requirements.
Packing, unpacking and storage should be done in a dry room, and the product, its
components and accessories should be checked for completeness and consistency. The
switchgear should be placed upright and not allowed to be stacked.
4.6 Maintain
Maintenance keeps the switchgear in trouble-free operation and achieves the
longest possible service life. In accordance with GB/T 11022 and IEC 60694, the
following closely related work is included.
Check: Confirmation of actual operating conditions
Maintenance: measures to maintain the specified operating conditions
Overhaul: measures to restore the specified operating conditions
5 General provisions
Under normal operating conditions, the maintenance and repair work of this
product is very small. The mechanical mechanism can be used after 10 years of
operation, or after the circuit breaker is divided into 10,000 times. After the
three-position switch is divided into 1000 times, the manufacturer is sent to specialize.
The trained personnel perform the necessary maintenance. Under abnormal
environmental conditions (contamination, corrosion, etc.), the cycle of overhaul should
be shortened accordingly. Note: When it comes to the maintenance and treatment of
insulating gas, it is necessary to attach great importance to safety, ensure the
ventilation of the operating site, equip with necessary protective tools (such as
disinfection masks) and rescue measures to avoid suffocation caused by excessive gas
density.
5.1 Running check
During normal operation, the various indication states of the equipment should be
observed regularly, and the recorded information of the protection unit should be
classified and summarized. If an abnormal situation occurs, the maintenance plan
should be determined after consulting the manufacturer. If necessary, the
manufacturer sends someone to the factory. Conduct on-site guidance.
5.2 Main circuit insulation level check
In the case of 2.5, the power frequency withstand voltage test is performed on the
NG7-40.5(Z)
phase, relative and vacuum fractures of the main circuit in accordance with the
requirements in 2.5.3 test procedure. If the result is unsatisfactory, contact the
manufacturer for assistance.
5.3 Circuit breaker mechanical characteristics check
In the case described in 3.3.2, contact the manufacturer to inspect the mechanical
characteristics of the circuit breaker operating mechanism. If the result is unqualified,
the manufacturer is responsible for the adjustment process.
5.4 Maintenance of other components
For maintenance and overhaul of other components (high voltage primary cable,
lightning arrester, current transformer, voltage transformer, sensor and control
protection unit, etc.), please refer to the relevant standards and the requirements of the
respective manuals.
6 Ordering instructions
6.1 Determine the product model, name code, and technical parameters;
6.2 Determine the quantity of products and delivery period;
6.3 other special operational requirements;
6.4 Name and quantity of spare parts.