3516 - Technical Spec Sheet
3516 - Technical Spec Sheet
STANDARD
3516B
1600 ekW/ 2000 kVA/ 50 Hz/ 1500 rpm/ 400 V/ 0.8 Power Factor
3516B
1600 ekW/ 2000 kVA
50 Hz/ 1500 rpm/ 400 V
Metric English
Package Performance
Genset Power Rating with Fan @ 0.8 Power Factor 1600 ekW
Genset Power Rating 2000 kVA
Aftercooler (Separate Circuit) 30.0 ° C 86.0 ° F
Fuel Consumption
100% Load with Fan 396.1 L/hr 104.6 gal/hr
75% Load with Fan 295.7 L/hr 78.1 gal/hr
50% Load with Fan 206.7 L/hr 54.6 gal/hr
25% Load with Fan 122.1 L/hr 32.3 gal/hr
Cooling System¹
Engine Coolant Capacity 233.0 L 61.6 gal
Radiator Water Capacity High Temp Circuit N/A N/A
Radiator Water Capacity Low Temp Circuit N/A N/A
Radiator Total Capacity N/A N/A
Inlet Air
Combustion Air Inlet Flow Rate 139.8 m³/min 4936.5 cfm
Max. Allowable Combustion Air Inlet Temp 43 ° C 109 ° F
Exhaust System
Exhaust Stack Gas Temperature 432.9 ° C 811.2 ° F
Exhaust Gas Flow Rate 346.5 m³/min 12235.4 cfm
Exhaust System Backpressure (Maximum Allowable) 6.7 kPa 27.0 in. water
3516B
1600 ekW/ 2000 kVA/ 50 Hz/ 1500 rpm/ 400 V/ 0.8 Power Factor
Heat Rejection
Heat Rejection to Jacket Water 533 kW 30312 Btu/min
Heat Rejection to Exhaust (Total) 1477 kW 83997 Btu/min
Heat Rejection to Aftercooler 378 kW 21497 Btu/min
Heat Rejection to Atmosphere from Engine 124 kW 7052 Btu/min
Heat Rejection to Atmosphere from Generator 120 kW 6824 Btu/min
Alternator²
Motor Starting Capability @ 30% Voltage Dip 4040 skVA
Current 2887 amps
Frame Size N4343L4
Excitation PM
Temperature Rise 125 ° C
Emissions (Nominal)³
NOx 2935.2 mg/Nm³ 5.9 g/hp-hr
CO 89.2 mg/Nm³ 0.2 g/hp-hr
HC 73.8 mg/Nm³ 0.1 g/hp-hr
PM 12.0 mg/Nm³ 0.0 g/hp-hr
1. For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing
restriction from factory.
2. UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting
characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.
3. Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E
and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77° F,
28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 btu/lb. The nominal emissions data shown is
subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100%
load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.
Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for
availability.
3516B
1600 ekW/ 2000 kVA/ 50 Hz/ 1500 rpm/ 400 V/ 0.8 Power Factor
CONTINUOUS:Output available with non-varying load for an unlimited time. Average power output is 70-100% of the
continuous power rating. Typical peak demand is 100% of continuous rated ekW for 100% of operating hours.
Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions
Fuel Rates are based on fuel oil of 35º API [16º C (60º F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when
used at 29º C (85º F) and weighing 838.9 g/liter (7.001 lbs/U.S. gal.). Additional ratings may be available for specific
customer requirements, contact your Cat representative for details. For information regarding Low Sulfur fuel and
Biodiesel capability, please consult your Cat dealer.