1 Input Data: WWW - Hilti.in

The document provides input data and results for designing an M12 anchor bolt with an effective embedment depth of 50mm to be installed in cracked concrete with a compressive strength of 31.94 N/mm2. It analyzes the anchor bolt under tension and shear loading and verifies that the steel strength, pullout strength, concrete breakout strength, and pryout strength are sufficient based on the given loads and capacities. The analysis finds that all load cases meet the required strength criteria.

Uploaded by

Sudhir Kotkar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
95 views

1 Input Data: WWW - Hilti.in

The document provides input data and results for designing an M12 anchor bolt with an effective embedment depth of 50mm to be installed in cracked concrete with a compressive strength of 31.94 N/mm2. It analyzes the anchor bolt under tension and shear loading and verifies that the steel strength, pullout strength, concrete breakout strength, and pryout strength are sufficient based on the given loads and capacities. The analysis finds that all load cases meet the required strength criteria.

Uploaded by

Sudhir Kotkar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 26

www.hilti.in Profis Anchor 2.7.

1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

Specifier's comments: DESIGN OF ANCHOR @ BASE PLATE.PA2

1 Input data
Anchor type and diameter: HST3-R M12 hef1
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 50 mm, hnom = 60 mm
Material: A4
Evaluation Service Report: ETA-98/0001
Issued I Valid: 11/6/2015 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 10 mm
Anchor plate: lx x ly x t = 200 mm x 150 mm x 10 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, , fc = 31.94 N/mm2; h = 500 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting according to fib (07/2011), 10.1.5.2 present

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y 1 2
Tension
1 6.399 2.350 0.000 -2.350
2 6.399 2.350 0.000 -2.350 x
max. concrete compressive strain: 0.17 [‰]
max. concrete compressive stress: 5.01 [N/mm2]
resulting tension force in (x/y)=(0/25): 12.797 [kN]
resulting compression force in (x/y)=(0/-68): 11.257 [kN]

Compression

3 Tension load SOFA (fib (07/2011), section 10.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 6.399 30.357 22 OK
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 12.797 17.094 75 OK
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
42.500 1.400 30.357 6.399

3.2 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm]
37500 22500 1.667 75 150
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.700 15.385 1.500 17.094 12.797

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

4 Shear load SOFA (fib (07/2011), section 10.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 2.350 24.880 10 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 4.700 47.522 10 OK
Concrete edge failure in direction y-** 4.700 13.150 36 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
31.100 1.250 24.880 2.350

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm] k4
37500 22500 1.667 75 150 2.780
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
15.385 1.500 47.522 4.700

4.3 Concrete edge failure in direction y-


lf [mm] dnom [mm] kV a b
50 12.0 1.700 0.071 0.065
c1 [mm] Ac,V [mm2] A0c,V [mm2] y A,V
100 60000 45000 1.333
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V y 90°,V
1.000 1.000 1.000 0 1.000 1.000 2.000
V0Rk,c [kN] gM,c VRd,c [kN] VSd [kN]
14.794 1.500 13.150 4.700

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.211 0.094 2.000 6 OK
concrete 0.749 0.357 1.500 87 OK
baN + baV <= 1

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 4.740 [kN] dN = 0.311 [mm]
VSk = 3.481 [kN] dV = 0.763 [mm]
dNV = 0.824 [mm]
Long term loading:
NSk = 4.740 [kN] dN = 1.243 [mm]
VSk = 3.481 [kN] dV = 1.134 [mm]
dNV = 1.683 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

7 Warnings
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

8 Installation data
Anchor plate, steel: - Anchor type and diameter: HST3-R M12 hef1
Profile: no profile Installation torque: 0.060 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 10 mm Hole depth in the base material: 70 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Seismic/Filling set
• Properly sized drill bit • Torque wrench
• Hammer
y

100 100

50

75
1 2

100 x

75

50 100 50

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -50 25 - - 100 -
2 50 25 - - 100 -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
HST3 (-R) subject to:
Anchor size M8 M10 M12 M16 M20 M24
Hammer drilling*

TE2(-A) – TE30(-A) TE40 – TE70

Diamond core drilling*

DD-30W, DD-EC1

Setting tool*
Setting tool HS-SC -

Hollow drill bit drilling*

- TE-CD, TE-YD

Seismic Set/ Filling Set**

Seismic/Filling Set M8-M20 (Carbon and Stainless Steel A4) -

*Installation methods provided in ETA-98/0001


**Seismic set needed to fill the annular gap between anchor and fixture:
No annular gap, double design resistance (agap=1)
www.hilti.in Profis Anchor 2.7.1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

Specifier's comments: DESIGN OF ANCHOR @ VERTICAL PLATE OF L BRACKET.PA2

1 Input data
Anchor type and diameter: HSA-R M10 hnom1
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 40 mm, hnom = 50 mm
Material: A4
Evaluation Service Report: ETA 11/0374
Issued I Valid: 4/28/2016 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 10 mm
Anchor plate: lx x ly x t = 200 mm x 160 mm x 10 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: uncracked concrete, , fc = 31.94 N/mm2; h = 500 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting according to fib (07/2011), 10.1.5.2 present

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
1 2
Anchor Tension force Shear force Shear force x Shear force y Tension
1 7.509 0.770 0.000 -0.770
2 7.509 0.770 0.000 -0.770 x
max. concrete compressive strain: 0.18 [‰]
max. concrete compressive stress: 5.52 [N/mm2]
resulting tension force in (x/y)=(0/30): 15.017 [kN]
resulting compression force in (x/y)=(0/-69): 10.317 [kN]

Compression

3 Tension load SOFA (fib (07/2011), section 10.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 7.509 25.000 31 OK
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 15.017 19.221 79 OK
Splitting failure** 15.017 25.190 60 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
35.000 1.400 25.000 7.509

3.2 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm]
26400 14400 1.833 60 120
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
11.000 15.726 1.500 19.221 15.017

3.3 Splitting failure


Ac,N [mm2] A0c,N [mm2] y A,N ccr,sp [mm] scr,sp [mm] y h,sp
55100 36100 1.526 95 190 1.574
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1
0 1.000 0 1.000 1.000 1.000 11.000
N0Rk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
15.726 1.500 25.190 15.017

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

4 Shear load SOFA (fib (07/2011), section 10.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 0.770 18.080 5 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 1.540 46.131 4 OK
Concrete edge failure in direction y-** 1.540 18.604 9 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
22.600 1.250 18.080 0.770

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm] k4
26400 14400 1.833 60 120 2.400
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
15.726 1.500 46.131 1.540

4.3 Concrete edge failure in direction y-


lf [mm] dnom [mm] kV a b
40 10.0 2.400 0.062 0.062
c1 [mm] Ac,V [mm2] A0c,V [mm2] y A,V
105 65363 49613 1.317
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V y 90°,V
1.000 1.000 1.000 0 1.000 1.000 2.000
V0Rk,c [kN] gM,c VRd,c [kN] VSd [kN]
21.182 1.500 18.604 1.540

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.300 0.043 2.000 10 OK
concrete 0.781 0.083 1.500 72 OK
baN + baV <= 1

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 5.562 [kN] dN = 0.365 [mm]
VSk = 1.141 [kN] dV = 0.211 [mm]
dNV = 0.421 [mm]
Long term loading:
NSk = 5.562 [kN] dN = 0.729 [mm]
VSk = 1.141 [kN] dV = 0.317 [mm]
dNV = 0.795 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

7 Warnings
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

8 Installation data
Anchor plate, steel: - Anchor type and diameter: HSA-R M10 hnom1
Profile: no profile Installation torque: 0.025 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 10 mm
Plate thickness (input): 10 mm Hole depth in the base material: 55 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Seismic/Filling set
• Properly sized drill bit • Installation torque control bar with suitable
screw driver or torque wrench
• Hammer
y

100 100

50

80
1 2

x
110

80

50 100 50

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -50 30 - - 105 -
2 50 30 - - 105 -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/9/2018
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

Specifier's comments: DESIGN OF ANCHOR @ BASE PLATE_CANOPY.PA2

1 Input data
Anchor type and diameter: HST3-R M16 hef1
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 65 mm, hnom = 78 mm
Material: A4
Evaluation Service Report: ETA-98/0001
Issued I Valid: 11/6/2015 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Anchor plate: lx x ly x t = 300 mm x 300 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, , fc = 28.60 N/mm2; h = 1000 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting according to fib (07/2011), 10.1.5.2 present

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads
3 4
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 2.266 27.750 27.750 0.000
2 1.634 27.750 27.750 0.000 x
Tension
3 2.266 27.750 27.750 0.000
4 1.634 27.750 27.750 0.000
max. concrete compressive strain: - [‰]
max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 7.800 [kN] 1 2
resulting compression force in (x/y)=(0/0): 0.000 [kN]

3 Tension load SOFA (fib (07/2011), section 10.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 2.266 49.571 5 OK
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 7.800 49.526 16 OK
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
69.400 1.400 49.571 2.266

3.2 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm]
152100 38025 4.000 98 195
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
16 0.861 0 1.000 1.000 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.700 21.581 1.500 49.526 7.800

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

4 Shear load SOFA (fib (07/2011), section 10.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 27.750 38.880 72 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 111.000 196.243 57 OK
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
48.600 1.250 38.880 27.750

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm] k4
152100 38025 4.000 98 195 3.410
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
21.581 1.500 196.243 111.000

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.046 0.714 2.000 52 OK
concrete 0.157 0.566 1.500 49 OK
baN + baV <= 1

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 1.678 [kN] dN = 0.112 [mm]
VSk = 20.556 [kN] dV = 2.588 [mm]
dNV = 2.590 [mm]
Long term loading:
NSk = 1.678 [kN] dN = 0.317 [mm]
VSk = 20.556 [kN] dV = 3.919 [mm]
dNV = 3.932 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

8 Installation data
Anchor plate, steel: - Anchor type and diameter: HST3-R M16 hef1
Profile: no profile Installation torque: 0.110 kNm
Hole diameter in the fixture: df = 18 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 12 mm Hole depth in the base material: 88 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 120 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Seismic/Filling set
• Properly sized drill bit • Torque wrench
• Hammer
y

150 150

50
3 4

150
200

x
150

1 2
50

66 200 34

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -84 -100 - - - -
2 116 -100 - - - -
3 -84 100 - - - -
4 116 100 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
HST3 (-R) subject to:
Anchor size M8 M10 M12 M16 M20 M24
Hammer drilling*

TE2(-A) – TE30(-A) TE40 – TE70

Diamond core drilling*

DD-30W, DD-EC1

Setting tool*
Setting tool HS-SC -

Hollow drill bit drilling*

- TE-CD, TE-YD

Seismic Set/ Filling Set**

Seismic/Filling Set M8-M20 (Carbon and Stainless Steel A4) -

*Installation methods provided in ETA-98/0001


**Seismic set needed to fill the annular gap between anchor and fixture:
No annular gap, double design resistance (agap=1)
www.hilti.in Profis Anchor 2.7.1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

Specifier's comments: DESIGN OF ANCHOR @ BASE PLATE_TIE ROD CONNECTION.

1 Input data
Anchor type and diameter: HSA-R M16 hnom3
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 120 mm, hnom = 132 mm
Material: A4
Evaluation Service Report: ETA 11/0374
Issued I Valid: 4/28/2016 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Anchor plate: lx x ly x t = 300 mm x 300 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: uncracked concrete, , fc = 28.60 N/mm2; h = 1000 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting according to fib (07/2011), 10.1.5.2 present

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads
3 4
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 31.084 15.000 15.000 0.000
2 22.416 15.000 15.000 0.000 x
Tension
3 31.084 15.000 15.000 0.000
4 22.416 15.000 15.000 0.000
max. concrete compressive strain: - [‰]
max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 107.000 [kN] 1 2
resulting compression force in (x/y)=(0/0): 0.000 [kN]

3 Tension load SOFA (fib (07/2011), section 10.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 31.084 62.643 50 OK
Pullout Strength* 31.084 39.441 79 OK
Concrete Breakout Strength** 107.000 114.453 94 OK
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
87.700 1.400 62.643 31.084

3.2 Pullout Strength


NRk,p [kN] yc gM,p NRd,p [kN] NSd [kN]
50.000 1.183 1.500 39.441 31.084

3.3 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm]
313600 129600 2.420 180 360
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
16 0.917 0 1.000 1.000 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
11.000 77.335 1.500 114.453 107.000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

4 Shear load SOFA (fib (07/2011), section 10.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 15.000 45.200 34 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 60.000 361.787 17 OK
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
56.500 1.250 45.200 15.000

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm] k4
313600 129600 2.420 180 360 2.900
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
77.335 1.500 361.787 60.000

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.496 0.332 2.000 36 OK
concrete 0.935 0.166 1.500 98 OK
baN + baV <= 1

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 23.025 [kN] dN = 2.032 [mm]
VSk = 11.111 [kN] dV = 0.840 [mm]
dNV = 2.198 [mm]
Long term loading:
NSk = 23.025 [kN] dN = 2.419 [mm]
VSk = 11.111 [kN] dV = 1.260 [mm]
dNV = 2.727 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

8 Installation data
Anchor plate, steel: - Anchor type and diameter: HSA-R M16 hnom3
Profile: no profile Installation torque: 0.080 kNm
Hole diameter in the fixture: df = 18 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 12 mm Hole depth in the base material: 140 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 180 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Seismic/Filling set
• Properly sized drill bit • Installation torque control bar with suitable
screw driver or torque wrench
y • Hammer

150 150

50
3 4

150
200

x
150

1 2
50

66 200 34

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -84 -100 - - - -
2 116 -100 - - - -
3 -84 100 - - - -
4 116 100 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Profis Anchor 2.7.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 3/10/2018
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

You might also like