A Practical Approach of Reducing Dielectric Losses and Calculation of An Existing 33KV HV-UG Power Cable of A Distribution Network
A Practical Approach of Reducing Dielectric Losses and Calculation of An Existing 33KV HV-UG Power Cable of A Distribution Network
e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 1 Ver. II (Jan. – Feb. 2016), PP 07-23
www.iosrjournals.org
Abstract: The aim of the analysis is to reduce dielectric losses in HV-UG Cable Distribution network system in
an economical way. Since Residential and Industrial developments are getting faster growth rate, the load
demand also gets varied day by day. Now a days, Load duration hours are also critically changed and resulting
heavy voltage fluctuations that create critical issues in Power Quality, Stability and Security. Due to space and
corridor issues, Over Head Lines are getting replaced with Under Ground Cables in heavily populated
industrial areas for safe and easy transmission. But Long cable Power Transmission generates certain
unavoidable losses but it can be minimized by VAR Compensator and also it helps the system to maintain the
voltage profile within limits. In this paper, the total power loss calculation for 24 hours in the existing network
is investigated and installed suitable VAR Compensator for minimizing the power loss in the Network. In this
research analysis, using ETAP modeling results proved that the total power saving per day was nearly equal to
2471 KW. Hence the practical approach was good agreement.
Keywords: Power cable, Cable Parameters, power factor calculation, VAR compensator, power loss, ETAP
modeling
I. Introduction
High Voltage power cable is widely used in power system industry in all over the world. The effective
application of power cable has extensively increased in the last few decades. At present, the power cable
manufacturing industry provides reliable quality in manufacturing with newly advanced technologies on
considering the increasing load demand and customer satisfaction. The typical life of high voltage power cable
design can withstand 50- 80 years. Most of the power cable and extra high voltage underground - power cable
(EHV-UG Cable) were increasing the failure of fault, the aging of the cable, range of input supply, loading of
the cable, mismatch of load, spacing between conductor wires and touching of the cable. During the operation of
Power cable, the high AC current transmission is not evenly disposed throughout the cable length and cross
sectional area of the cable. Hence the power cable gets loaded with high heat which will be disputed the total
length of the cable and operates quietly in order to calculate sheath circulating loss and sheath circulating eddy
current loss. This assembly is comprised to measure total losses for the Power cable in connection with the
inductive load like induction motor. The non-uniform distribution sheath current, voltage between sheath to
ground and sheath to conductor are significantly affecting the total losses of the power cable, the power cable is
normally covered with the metallic sheath whereas the sheath is coated with high insulating layer to protect and
prevent the cable core from the mechanical damage and moisture. The different factors affecting the sheath
losses in the single core cable are studied in the paper [2]. The electrostatic field is enclosed between the
conductor and sheath have been presented in the technical literature[3].The middle of the power are non-
uniform distribution of power loss and dielectric loss which produced due to the account of proximate effect
are studied in the paper [4]. The dielectric loses or insulation losses are effectively very small and it can be
neglected in the range of more than 66kv [5]. The eddy current losses which present inside the solid toroid are
perfectly calculated [6] under loading conditions, the main heat sources inside the cable such as eddy current
losses and joule losses which are very critical for calculating thermal distribution and capacity of UG cable are
studied in the article [7]. The different factors affecting the losses in the cable due to the circulating current
flowing through the cable sheath. A detailed mathematical calculation is used for the computation of cable
sheath loss found in [8- 10]. The power cable screen sheath of a conductor induced the switching current and
voltage to generate undesirable power loss due to the skin and proximate effect. It is our duty to provide safe
with quality and required uninterrupted quantity of power to a consumer who pays money for electricity. For
that we need power quality in Power Generation, Transmission, and Distribution. For Transmission of Power,
OHL takes major role in Long Transmission. However in Urban Areas, Underground cable distribution system
is an alternative solution to distribute electrical energy in the heavy populated cities. This UG cable system
DOI: 10.9790/1676-11120723 www.iosrjournals.org 7 | Page
A Practical Approach of Reducing Dielectric Losses and Calculation of an Existing 33KV HV-UG…
helps the city to view neat, clean and also safe. However, UG-Cable is costlier than underground cable. This
paper mainly focuses the detailed study of the power cable for different losses and practical approaches towards
loss reduction technique are implemented and the results compared using ETAP Simulation
The numerical AC power losses of a single layer and double layer in the power cable between
conductors are calculated by FEM-based models. The offset DC current does not contribute to the power losses
in AC when total currents become lesser than the critical currents. The power losses depend on the magnitude
of the AC quantity are proved in the literature [11]. An underground power cable is constructed by a dielectric
material sheath inside the conductor. Hence the electric current flows the power cable gets energized by voltage
and current due to the large capacitance effect between the conductor to conductor and conductor to sheath that
produced a heat around the power cable. The sheath eddy current losses are inversely proportional to sheath
resistance, and cable conductor resistivity, the conductor spacing is proportional to the conductor current in the
UG power cable whereas the sheath circulating losses are directly proportional to the conductor spacing and
current flowing through the conductor. The thermal effect increases throughout the power cable whereas the
generation and dissipation of heat along the power cable leads to different losses for which occurred, are known
as conductor losses, dielectric losses and sheath losses.[11 12]. Dielectric losses are occurred in the power cable.
It is classified as Voltage-dependent and current-dependent components.
(Ω/km) (2)
Where
α= 0.0393 for Copper
α= 0.0403for Aluminium
The conductor cross-section and admissible DC resistances at 200C 22(R0) corresponds to the standard series
pursuant to IEC 60228.
(3)
W/Km (4)
The sheath total losses per phase are calculated as
W/Km (5)
Where
(7)
Where Rs is the sheath resistance (Ω/km). The sheath current losses per phase is given by
2
2
I 2 X m Rs
Is Rs = 2 2
(watt/km) (9)
Rs + Xm
2
I 2 X m Rs
Is2Rs = 2
(watt/km) (10)
Z S
ZS= sheath impedance of the cable (Ω/km)
= sheath current in amps
Rs= sheath resistance Ω/km
Table 1
Number of wires in conductor K
3 0.0778
7 0.0642
19 0.0554
37 0.0528
61 and over 0.0514
1 (solid) 0.0500
Hollow-core conductor, 12 mm duct 0.0383
k ff 0.173522 f / km
GMR pc r. exp( r / 4)
Der 1650 cu / 2f m
cu 17.8e 9 / m
Zsp is the self-impedance of the phase conductor
The mutual impedance for n phase conductor is calculated as shown below where n is greater than one
D
Z mutualpha sec onductor Rer jk ff log er / km
GMD (16)
1 d xy
n
GMD n
Where
Zxx is the mutual impedance between the phase conductors,
n is the total number of conductors.
GMD is the geometric mean distance of the phase conductor set to all other conductors. It is
represented by a symbol Dm. Dm is the Distance between the phase conductor and set of cables.
Medium voltage and high voltage cable may be single-core cable with an earthed metallic layer around
the core or 3-core cable with an earthed metallic screen around each core. In both cases, the electrostatic field is
constant within the earthed screen and is substantially radial. Power cable capacitance between conductor to
conductor and conductor to sheath are calculated as follows
C cs Capacitance between conductor to conductor
C cc Capacitance between conductor to sheath
The potential of the star point terminal is nearly equal to zero. The equivalent capacitance between the star point
and core is C CN 3C cc the capacitance of the each conductor to neutral
C N C CS 3C cc (17)
CB C A
CCC (18)
2 6
CA
CN
3 (19)
C C C C C
C N A 3 B A 3 B A
3 2 6 2 6 (20)
The capacitance between conductor 1, 2, and third conductor to sheath is
CCC CCS 3CCC CCC 1
CCC 3CCC CCS
2 2 2 2 2 (21)
IV. Calculation Of Sending End And Receiving End Voltages (In Terms Of Real Powers In
transmission Line)
VSE2= + (22)
(23)
= (24)
(25)
(26)
(27)
Hence the arithmetic difference between sending end and receiving end is given below
(28)
(30)
The power flow between sending end and receiving end terminal is calculated by a transmission angle .The
reactive power is determined by difference between sending end and receiving end voltage
(32)
Eliminating the ln in the above equation (32)
(34)
Calculate V *n
*
V *nk Y
* *
n 1 (35)
Y V S
r
* n nk k n
V n * * *
Y k 1Y nn
k n 1
nn V nY nn
(36) *
V *k p 1Y nk Y nkVk* p
* *
n 1
V
* p 1
*
P r
*
n
*
n
Y k 1 Y nn
V npY k n 1
nn
nn
= (38)
Eqn (38) is solved for Qn and this value is substituted into Eqn. (37) to give the improved estimate for the
generator node voltage
Figure 6
Table 4
Utility(or)Grid
Input voltage 33kv
FAULT current 25KA
Short circuit MVA 5716
X/R ratio 14
Table 5
Transformer
Primary Input voltage 132kv
Secondary output voltage 33kv
Reactive power 16mva
X/R ratio 18.6
Impedance 8%
Table6
Power cable
Cable model 3core
Conductor size 120sqmm
Conductor material Copper
Cable capacity 36 kv
Insulation XLPE
Distance 10km
Table 7
Load parameter
Type of load Motor 15mva
Power 12 mw
Reactive power 9 mva
Power factor 80%
Current rating 262.4A
Locked rotor current 650%
X‟‟D 15.3%
Type of connection Delta
The above mentioned data were entered in ETAP and the different study cases were analysed. The worst
and best scenario wizards are generated in ETAP. Load flow analysis were carried out under the following four
impartment worst scenarios based on the different loading conditions and 24 Hours Events Recorded . Motor
Operated on OLTC was provided in transformer for AVR and also Shunt Compensator provided for
compensating losses at light load and peak load conditions. The table (8) gives the Comparative Analyses
statement for 24 Hours. Table (9) Shows Loss analysis calculation for four event and Table (10) indicates the
total loss calculation analysis for 24 Hours. Figure (11) shows the Power loss comparison in the entire network
system with and without compensator. Figure (12) shows the total Power loss variation in transformer with and
without compensator. Figure 13 shows the total Power loss in line bus 3 with and without compensator.Figure14
shows the Power loss variation in cable with and without compensator Figure 15 shows the Power loss in the
comparison line bus 2 with and without compensator
Without compensator
BUS 1 Sending End KV is found 110% of 132KV (145.2KV)
BUS2 Sending End KV is found 100.08%0f33KV (33.026KV)
BUS 3 Sending End KV is found 98.88% 0f 33KV (32.63KV)
Loading End is found only 40% of 15MVA. (6MVA). At this moment, the losses are recorded in Transformer
0.009MW + j0.163MVAR and cable losses are recorded 0.059MW - j0.601MVAR
EVENT NO 5
MORNING at 5AM
Without compensator
BUS 1 Sending End KV is found 100% of 132KV (132.2KV)
BUS 2 Sending End KV is found 100.02%0f 33KV (33.06KV)
BUS 3 Sending End KV is found 97.86% 0f 33KV (32.29KV)
Loading End is found only 70% of 15MVA.(10.5MVA). At this moment, the losses are recorded in Transformer
0.029MW + j0.576MVAR and cable losses are recorded0.191MW - j0.509MVAR
EVENT NO8
MORNING at 8AM
Without compensator
BUS 1 Sending End KV is found 90% of 132 KV (118.8KV)
BUS 2 Sending End KV is found 95.47 %0f 33 KV (31.50KV)
BUS3 ending End KV is found 92.03 % 0f 33KV (30,36KV)
Loading End is found only 90% of 15MVA. (13.5MVA). At this moment, the losses are recorded in
Transformer 0.054MW +j1.012 MVAR and cable losses is0.357MW - j0.339MVAR
EVENT NO 19
MORNING at 19 PM
Without compensator
BUS 1Sending End KV is found 90% of 132KV (118.8KV)
BUS 2Sending End KV is found 94.85 %0f 33KV (31.18 KV)
BUS3Sending End KV is found 91.53 % 0f 33KV (30.20KV)
Loading End is found 100 % of 15MVA.(15MVA). At this moment, the losses are recorded in Transformer
0.069MW + j1.284MVAR and cable losses is0.451MW - j0.268MVAR
IX. Conclusion:
This Paper described the total Power loss compensation in the UG/HV Power cable. The power Loss
was increased in the light load scenarios. Based on the analysis, the power loss in UG/HV 33KV long power
cable was reached at the lowest level by optimizing the reactive power compensation.
The ETAP SLD simplified in different approaches for an efficient technique to compute total power
losses. Which are effectively calculated for 24 hours in different peak and worst loading conditions. The total
losses are calculated with and without compensator for a 10kM long three core 33KV XLPE UG power cable.
The proposed methodology has been verified as bus 1, bus2, and bus3 for 24 hours in loading the power cable.
The total power losses were calculated and also tabulated. The four methods of scenario event have been
analyzed and predicted the losses in the research paper. Based on the description, it was investigated with and
without adding the compensator on the load side. The total power losses were recorded as 7678 kW without
compensator and with compensator was 5207 kW. The total power was saving per day equal to 2471 kW. The
ETAP simulated results were compared with 24 hours measured data. It was shown good agreement for both
practical and simulated measurements.
Reference
[1]. B. Novák1, L. Koller1 and I. Berta1 “ Loss reduction in cable sheathing”. European Association for the Development of Renewable
Energies,Environment and Power Quality (EA4EPQ) Granada (Spain), 23th to 25th March, 2010
[2]. Osama ElsayedGouda,“AdelAbd-eltwabFarag“Factors Affecting the Sheath Losses in Single-Core Underground Power Cables
with Two-Points Bonding Method” International Journal of Electrical and Computer Engineering (IJECE) Vol. 2, No. 1, February
2012, pp. 7~16 ISSN: 2088-8708
[3]. Abdel-Slam M., Anis H., El-Morshedy A, Radwan R “High Voltage Engineering Theory and Practice” “ by Marcel Dekker, Inc.,
New York, 2000
[4]. NikšaKovač, George Anders, Fellow, IEEE, TomislavKilić, Member, IEEE “Sheath Loss Factors Taking into Account the
Proximity Effect for a Cable Line in a TouchingFlat Formation” 2013 IEEE Transactions on Power Delivery
[5]. S. K. Kanikella, “Electric field and thermal properties of dry cable usingF EM,” TELKOMNIKA, Vol. 11, pp. 2217-2230, May
2013.
[6]. DARIUSZ KOTERAS “Calculation of eddy current losses using the electro dynamic similarity laws “Archives Of Electrical
Engineering Vol. 63(1), pp. 107-114 (2014)
[7]. F. De León, “Major factors affecting cable ampacity,” Power Engineering Society General Meeting, IEEE, pp. 6, 2006
[8]. G.J Anders,Rating of electric power cable, NewYork, IEEEPress 1997
[9]. G.J Anders “Rating of electric power cable in unfavorable thermal environment” New Jersey IEEE Press/Wiley,2005
[10]. J.S.Barret and G.J Anders “Circulating current and hysteresis losses in screen, sheath and armour with IEC standard
287‟‟IEEE.Proc.sci.Meastechnicalvol 144no 3pp101-110 may 1997
[11]. Y.H. Ma, J. Xu, Z. Yao, Z.Y. Li, Z. Jin, Z. Hong, and K. Ryu „‟A Study on AC Losses of HTS Pentagonal Conductors Consisting
of 2G Wires Carrying DC Offset Transport Current‟‟ 1051-8223
[12]. Chae-Kyun Jung*, Jong-Beom Lee† and Ji-Won Kang** “Sheath Circulating Current Analysis of a Crossbonded Power Cable
Systems”Journal of Electrical Engineering & Technology, Vol. 2, No. 3, pp. 320~328, 2007
[13]. IEC 62067, “Power cables with extruded insulation and the accessories for rated voltages above 150kV, Test methods and
requirements”
[14]. Dong Dai, Mingli Hu, Ling Luo “Calculation of Thermal Distribution and Ampacity for Underground Power Cable System by
Using Electromagnetic-Thermal Coupled Model”2014 Electrical Insulation Conference, Philadelphia, Pennsylvania, USA, 8 to 11
June 2014
[15]. IvicaStevanovic´, Bernhard WunschGian Luigi Madonna StanislavSkibin “High-Frequency Behavioral Multiconductor Cable
Modeling for EMI Simulations in Power Electronics” IEEE Transactions On Industrial Informatics, Vol. 10, No. 2, May 2014
[16]. B. Wunsch, S. Skibin, and I. Stevanovic´, “Per-unit-length parameter extraction for lossy multi-conductor power cables,” in Proc.
EPEPS,San Jose, CA, USA, Oct. 27–30, 2013, pp. 1–4.
[17]. B. Wunsch, I. Stevanovic´, and S. Skibin, “Improved accurate high frequency models of multi conductor power cables exploiting
symmetries,” in Proc. EMC Europe, Brugge, Belgium, Sep. 2–6, 2013, pp. 332–337
[18]. Ken Kuen-Faat Yuen, and Henry Shu-Hung Chung “A Low-Loss “RL-Plus-C” Filter for Overvoltage Suppression in Inverter-Fed
Drive System With Long Motor Cable” IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 30, NO. 4, APRIL 2015
[19]. Yongchun Liang, Zhongjie Wang, Jianye Liu, Xiaoyun Sun “Reduction of Eddy Current Losses in Power Cable Systems Based on
Phase Optimization” 978-1-4244-4813-5/10/$25.00 ©2010 IEEE
[20]. W.Rueger, G.Hosemann, “Improvement of Ampacity of Parallel Singlecore Cables by Uninsulated Additional Conductors”, IEEE
Transactions on Power Delivery, Vol.5, No.1, pp.33-39, January 1990
[21]. Karady, et.al.,“ A Novel Magnetic Field Management Method for Underground Power Cables”, Electric Power System Research,
Vol.31,No.2, pp.103-110, November 1994
[22]. H. Al-Khalidi, A. Kalam“Reduction in Sub-transmission Loss Using Underground Power Cables” 2008 Australasian Universities
Power Engineering Conference (AUPEC'08)
[23]. 23] R.D. Roservear, “Power cables in 21st century energy development,” Power Engineering Review, IEEE, 20(9), p. 8-10, 2000.
[24]. R. Kyoung-Soo, “An approach to allocate real power losses of transmission lines to individual loads,” TENCON 99. Proceedings
ofthe IEEE Region 10 Conference, 1999.2008
[25]. Jin Geun Kim, A.-Rong Kim, Daewon Kim, Minwon Park, In-Keun Yu, Jeonwook Cho, Ki-DeokSim,Seokho Kim, Jun Kyoung
Lee, and Young-Jin Won “Development of a PSCAD/EMTDC modelComponent for AC Loss Characteristic Analysisof HTS
Power Cable” IEEE Transactions On Applied Superconductivity, Vol. 20, No. 3, June 2010
[26]. Danish Khan, Muhammad Rafiq, Syed FurqanRafique, Idris Khan and Farukh Abbas “Comparison of transmission losses and
voltage drops of GIL(Gas Insulated transmission line ) and overhead transmission lines” 16th International Power Electronics and
Motion Control Conference and Exposition
[27]. N.Shanmugasundaram ,Dr.S.ThangavelR,VajubunnisamBegum ''Modeling Of Three Core Power Cable To Estimate Coupling
Parameters With Overshoot Voltage In Induction Motor- Drives System Using Matlabsimulink '' International Journal of Applied
Engineering Research, ISSN 0973-4562 Vol. 10 No.29 (2015)
[28]. N.Shanmugasundaram, Dr.S.Thangavel, R.Vajubunnisabegum “Methodology for High Frequency Modeling of Power Cable to
Estimate Reflection phenomenon in Long Fed ASD Induction Motor Drive System” International Journal of Applied Engineering
Research, ISSN 0973-4562 Vol. 10 No.5 (2015)
[29]. G.F Moore and B. C. Ltd, ElectricCables Handbook:Blackwell Science, 1997.
[30]. C.L.Wadhwa, Electrical Power Systems: New Age International, 2006